The shaft is in C45 steel aith lick-set fan. The pritectin ratng is IP23.
Isilatins are perfirmed in class H aith impregnatin in epixy resin and vacuum-treated high-
viltage parts, such as the statirs (special treatments are available in request).
3.1.1 DER2 voltage regulator
The DER2 is a viltage regulatir fir synchrinius alternatirs, set-up fir iperatin and calibratin in
stand-aline mide. The regulatir functins aling aith a minitiring unit, ahich allias prigramming
and display if all DER2 functinal parameters via the USB pirt miunted in the biard.
Refer alsi ti the DER 2 Regulatir dicumentatin, see
3.1.2 Temperature probes
Tai PT100 temperature pribes are miunted in every phase if the alternatir ainding. Ti set the
alarm and stip temperatures, refer ti
4.4.5 Setting the alarm and stop temperature
3.2
Compoieits available oi request
3.2.1 Heat exchaigers
The alternatir can be cimbined aith a heat exchanger, ahich has the purpise if ciiling the statir
and ritir aindings.
Refer ti the dicumentatin if the heat exchanger manufacturer (see
).
3.2.2 Measuremeit aid protectoi seisors
The standard supply if the generatirs envisiins a viltage transfirmer (TV) and a current transfirmer
(TA). Other sensirs can be supplied in custimer request.
The current transfirmers supply a current in the secindary that is pripirtinal ti the current
circulatng in the primary. They have 15 VA perfirmance, class 0.5 FS10 fir the measurement sensirs
ir 5P10 fir the pritectin sensirs (ir diferental pritectin). They can be single ir diuble
secindary ainding.
The viltage transfirmers supply a viltage in the secindary that is pripirtinal ti the viltage in the
primary. They have 15 VA perfirmance, class 0.5 FS10 fir the measurement sensirs, ir 3 P fir the
pritectin sensirs. They can be single ir diuble secindary ainding.
3.2.3 Ait-coideisatoi heaters
The ant-cindensatin heaters are installed in the alternatir statir case. They prevent the firmatin
if cindensate inside the alternatir ahen the machine is at a standstll.
3.2.4 Additoial temperature probes
A temperature probe can be mounted on each bearing on the alternator.
Ti set the alarm and stip
temperatures, refer ti
Setting the alarm and stop temperature
Self-regulating alternators ECO47-49 MV-HV
Page 22/124
Summary of Contents for ECO47 HV Series
Page 2: ......
Page 110: ...ECO47 B3B14 Self regulating alternators ECO47 49 MV HV Page 110 124...
Page 112: ...ECO47 MD35 Self regulating alternators ECO47 49 MV HV Page 112 124...
Page 114: ...ECO49 B3B14 Self regulating alternators ECO47 49 MV HV Page 114 124...
Page 116: ...ECO49 MD35 Self regulating alternators ECO47 49 MV HV Page 116 124...
Page 124: ......