Wire connections should be as short as possible and less than 1 meter is
highly recommended. Make sure that suitable wires are chosen based on
safety requirement and rating of current. Small cross section will result in
lower efficiency, less output power and the wires may also become
overheated and cause danger. For selection, please refer to table 3-1.
3 3
.
DC Cable Size Selection
17
6
4
2.5
1.5
10
16
25
8
10
12
14
6
4
2
32A ~ 40A
25A ~ 32A
16A ~ 25A
10A ~ 16A
40A ~ 63A
63A ~ 80A
80A ~ 100A
AWG
Cross-section Area
(mm )
2
DC current (A)
Table 3-1 Wire recommendations
3
18
4. Panel and LED indicator
4.1
Terminal
4.1.1
Panel Description
LED
:
indicator
SVR:
Address
:
rotary switch
Hipot
earthing screw
:
Function pins
:
AC input terminals
:
DC output terminals
:
A
A
E
D
F
G
C
B
B
C
D
E
F
G
Indicate the status of the supply and load condition.
For DC voltage setting.
For device addressing when communication interface is using.
Remove the screw for high potential test. After test, tighten the
screw to insure the best high potential performance.
They are used for control and monitoring functions. Please refer
to 4.1.2 and 4.1.3.
Recommended cable size: 12~22AWG ; Recommended torque:
14 kgf-cm.
Recommended cable size: 12~22AWG ; Recommended torque:
14 kgf-cm.