background image

DUAL CONDENSER HEAT RECOVERY - ARRANGEMENT H

Dual condenser heat recovery chiller models have two water

cooled condensers per refrigerant circuit. The upper con-
denser is the heat recovery condenser and is piped into the

building’s hot water system. The lower condenser is the tower
condenser and is piped to an open cooling tower. Condens-
ing is done in either the tower condenser or heat recovery
condenser, or partial condensing is done in each. The tower
and heat recovery water circuits are independent and do not
intermix. This use of an open tower and the closed heat

recovery loop prevents fouling of the building’s heating
system.

A subcooling circuit is provided in the tower condenser to

provide optimum cooling efficiency. When the unit is
operating on maximum heat recovery, the cooling tower will
be modulated down to its minimum capacity, usually about
5% of full capacity. This provides subcooling for the system
during heat recovery operation. Water can be heated up to

135°F in the heat recovery condensers to satisfy a heating
load. If all of the condenser heat of rejection cannot be
used, the remainder is rejected out through the cooling tower.

The cooling tower should be sized to reject all of the con-

denser heat during summer operation. Freeze protection for
the cooling tower must be provided if it is to operate in below
freezing temperatures, Adequate capacity control must be

provided to maintain a constant water temperature leaving

the cooling tower. Head pressure and water temperature are
controlled by the tower capacity control. Fan cycling and

modulating fan discharge dampers should be used. Consult

Figure 

12. Typical Dual Condenser (Per Circuit) Heat Recovery

the cooling tower manufacturer for information on specific
applications.

If the available condenser heat cannot satisfy all of the heat

load, an auxiliary heat source must be provided. The aux-
iliary heat source should be located between the heat
recovery condenser and the heat load and interlocked with
the cooling tower so that auxiliary heat is not being supplied
unless the cooling tower is modulated down all the way. The
chiller operation is always controlled by the building’s cool-
ing load and not the heating load.

TYPICAL OPERATION - On a call for cooling the chiller
starts. If a heating load is sensed by mode switch 

 , the heat

recovery water pump 

 will start and the cooling tower

dampers will modulate to control the heat recovery condenser
by means of proportional temperature controller T3. If max-

imum heat recovery is required, the tower dampers close and

the fans shut off. The tower will then provide 

only subcool-

ing. If more heat is required than the heat recovery con-

densers can provide, the auxiliary heat source is activated.

When mode switch 

 senses that a heating load no longer

exists, the heat recovery pump shuts off 

and the cooling 

tower

modulates to control the entering tower condenser water
temperature by means of proportional controller T2 and a sen-
sor located in the tower sump. Proportional controller T2 is

set at a temperature lower than T3 to provide optimum
efficiency.

COOLING TOWER

COOLER

PUMP

 

NOTE: 

The 

schematic shows one refrigerant circuit. 

Heat recovery 

WHR models with two refrigerant circuits

have two heat recovery condensers and two tower condensers.

Page 

12   IM 508

Summary of Contents for WHR 040

Page 1: ......

Page 2: ......

Page 3: ...d be carefully inspected for damage upon acceptance is not the responsibility of McQuay arrival All shipping damage should be reported to the car NOTE Unit shipping and operating weights are available...

Page 4: ...PAK water chiller If necessary additional structural members should be provided to transfer the weight of the unit to the nearest beams NOTE Unit shipping and operating weights are available in the ph...

Page 5: ......

Page 6: ...inlet consult pump manufacturer for recommendations The use of a strainer will prolong pump life and thus keep system performance up A preliminary leak check of the water piping should be made before...

Page 7: ...ompressors on startup It also serves to shut down the unit in the event that water flow is interrupted to guard against evaporator freeze up Fioure 7 A flow switch is available from under ordering num...

Page 8: ...the glycol system GPM To determine gpm or I T knowing n T or gpm and tons Glvcol gp pm 24 x Tons WW A T x G from table PRESSURE DROP To determine glycol pressure drop through the cooler enter the wate...

Page 9: ......

Page 10: ...ation These typical systems depending on the specific application must maintain a constant condensing pressure regardless of temperature conditions and must assure enough head pressure for proper ther...

Page 11: ...circuit manufacturer for information on specific applications An auxiliary heat source is necessary if the available con denser heat is not sufficient to satisfy all of the heat load The auxiliary he...

Page 12: ...Fan cycling and modulating fan discharge dampers should be used Consult Figure 12 Typical Dual Condenser Per Circuit Heat Recovery the cooling tower manufacturer for information on specific applicati...

Page 13: ...ints and the compressor crankcase may become starved It is recommended that any discharge lines coming into a horizontal discharge header rise above the center line of the discharge header This is nec...

Page 14: ...a tion not less than 15 feet above the adjoining ground level and not less than 20 feet from any window ventilation open ing or exit in any building The piping must be provided with a rain cap at the...

Page 15: ......

Page 16: ......

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ......

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ......

Page 29: ...tion with single power supply or disconnect switch it is not available with multi point option On water cooled units only optional compressor overloads are available allowing reduced unit ampacity rat...

Page 30: ......

Page 31: ......

Page 32: ......

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ......

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ......

Page 41: ......

Page 42: ...t ches to on This will energize crankcase heaters Wait a minimum of 12 hours before starting up unit Check compressor oil level Prior to startup the oil level should cover at least one third of the oi...

Page 43: ...lution should be used according to the manufacturer s directions Systems with remote air cooled condensers require periodic cleaning of the finned surface of the condenser coil Cleaning ing may be acc...

Page 44: ...ove from one compressor crankcase to the other during normal operation and balance between the two when the compressors are off This method of equali zation prohibits the oil level from dropping below...

Page 45: ...emperature cor responding to the evaporator pressure All WHR chillers are factory set for between 8 F and 12 F superheat at full load If it is necessary to increase the superheat setting of the valve...

Page 46: ...he evaporator permitting operation at lower loads than available with com pressor unloading It also keeps the velocity of refrigerant gas high enough for proper oil return at light load conditions A s...

Page 47: ...spor tation charge will be charged against its original credit value On all out of warranty compressor failures Copeland offers the same field facilities for service and or replacement as described ab...

Page 48: ...ion valve TCheck for leaks and repair Add refrigerant 2 Check riser sizes 3 Check pitch of lines and refrigerant velocities 4 Replace compressor 1 Check supply voltage for excessive line drop 2 Replac...

Page 49: ...y Claims Department P 0 Box 1551 Minneapolis MN 55440 telephone 612 553 5330 THIS WARRANTY CONSTITUTES THE BUYER S SOLE REMEDY IT IS GIVEN IN LIEU OF ALL OTHER WARRAN TIES THERE IS NO IMPLIED WARRANTY...

Reviews: