background image

SYSTEM SERVICE

NOTE: Service on this equipment is to be performed by qualified refrigeration personnel. Causes for repeated tripping of safety

controls must be investigated and corrected. CAUTION: Disconnect all power before doing any service inside the unit.

FILTER-DRIERS

To change the filter-drier, pump each refrigerant circuit down
by closing the manual liquid line shutoff valve while a com-
pressor is running. After both refrigerant circuits are pumped
down, move the system switch to the “Emergency Stop” posi-
tion. This will remove all liquid refrigerant from the evaporator
and section of liquid line up to the shutoff valve. Only a small

amount of vapor will remain in the liquid line/filter-drier sec-
tion. Front seat the compressor suction valve(s), Remove and
replace the filter-drier(s). Evacuate the lines through the li-
quid line manual shutoff valves to remove non-condensables
that may have entered during filter replacement. A leak check
is recommended before returning the unit to operation.

NOTE: On Arrangement A units, the filter-drier cores are shipped in the unit
control box and are to be Installed prior to evacuating and charging the unit.

LIQUID LINE SOLENOID VALVE

The liquid line solenoid valves, which are responsible for
automatic pumpdown  during normal unit operation, do not

normally require any maintenance. However, in the event of
failure they may require replacement of the solenoid coil or
of the entire valve assembly.

The solenoid coil may be removed from the valve body

without opening the refrigerant piping by moving Circuit 1 and
Circuit 2 switches to the “Pumpdown and Stop” position.

The coil can then be removed from the valve body by simply

removing a nut or snap-ring located at the top of the coil. The

coil can then be slipped off its mounting stud for replacement.

Be sure to replace the coil on its mounting stud before return-
ing the unit to operation.

To replace the entire solenoid valve, follow the steps involv-

ed when changing a filter-drier.

THERMOSTATIC EXPANSION VALVE

The expansion valve is responsible for allowing the proper
amount of refrigerant to enter the evaporator regardless of
cooling load. It does this by maintaining a constant superheat.
(Superheat is the difference between refrigerant temperature
as it leaves the evaporator and the saturation temperature cor-

responding to the evaporator pressure.) All WHR chillers are
factory set for between 8°F and 12°F  superheat at full load.
If it is necessary to increase the superheat setting of the valve,
remove the cap at the bottom of the valve to expose the ad-

justment screw. Turn the screw clockwise (when viewed from
the adjustment screw end) to increase the superheat and

counterclockwise to reduce superheat. Allow time for system
rebalance after each superheat adjustment.

The expansion valve, like the solenoid valve, should not nor-

mally require replacement, but if it does, the unit must be
pumped down by following the steps involved when chang-
ing a filter-drier.

If the problem can be traced to the power element only,

it can be unscrewed from the valve body without removing

the valve, but only after pumping the unit down.

WARNING: Adjustment of expansion valve should only be

performed by a qualified service technician.

Figure 

30.

Inlet

Power Element
(Contains Diaphragm)

Adjustment Screw

NOTE: Superheat 

 vary with compressor unloading, but should be approx-

imately as follows- between 6°F and 12°F at full load; between 6°F and 10°F
at part load.

EVAPORATOR

The evaporator is of the direct expansion, shell-and-tube type
with refrigerant flowing through the tubes and water flowing
through the shell over the tubes. The tubes are internally
finned to provide extended surface as well as turbulent flow
of refrigerant through the tubes. Normally no service work is

required on the evaporator. There may be instances where
a tube will leak refrigerant into the water side of the system.
In the cases where only one or two tubes leak, the problem

can best be solved by plugging the tube at both ends. When
the tube must be replaced, the old tube can be removed and

replaced.

To remove a tube, the unit should be temporarily pumped

down. Follow the steps involved when changing a filter-drier.
These steps will insure a minimum amount of refrigerant loss
when the evaporator is opened up. The tubes are mechanical-
ly expanded into the tube sheets (see Figure 31) at each end
of the cooler. In order to remove the tubes, it is necessary
to break this bond by collapsing the tube. After doing this at

both ends of the shell, the tube can be removed for replace-
ment. The new tube can then be inserted and re-expanded
into the tube sheet.

NOTE: The bond produced by expansion must be refrig-

erant tight. This bond must be produced by applying Locktite
(red) to the 

 and rolling it into the 

 sheet.

IM 508   Page 45

Summary of Contents for WHR 040

Page 1: ......

Page 2: ......

Page 3: ...d be carefully inspected for damage upon acceptance is not the responsibility of McQuay arrival All shipping damage should be reported to the car NOTE Unit shipping and operating weights are available...

Page 4: ...PAK water chiller If necessary additional structural members should be provided to transfer the weight of the unit to the nearest beams NOTE Unit shipping and operating weights are available in the ph...

Page 5: ......

Page 6: ...inlet consult pump manufacturer for recommendations The use of a strainer will prolong pump life and thus keep system performance up A preliminary leak check of the water piping should be made before...

Page 7: ...ompressors on startup It also serves to shut down the unit in the event that water flow is interrupted to guard against evaporator freeze up Fioure 7 A flow switch is available from under ordering num...

Page 8: ...the glycol system GPM To determine gpm or I T knowing n T or gpm and tons Glvcol gp pm 24 x Tons WW A T x G from table PRESSURE DROP To determine glycol pressure drop through the cooler enter the wate...

Page 9: ......

Page 10: ...ation These typical systems depending on the specific application must maintain a constant condensing pressure regardless of temperature conditions and must assure enough head pressure for proper ther...

Page 11: ...circuit manufacturer for information on specific applications An auxiliary heat source is necessary if the available con denser heat is not sufficient to satisfy all of the heat load The auxiliary he...

Page 12: ...Fan cycling and modulating fan discharge dampers should be used Consult Figure 12 Typical Dual Condenser Per Circuit Heat Recovery the cooling tower manufacturer for information on specific applicati...

Page 13: ...ints and the compressor crankcase may become starved It is recommended that any discharge lines coming into a horizontal discharge header rise above the center line of the discharge header This is nec...

Page 14: ...a tion not less than 15 feet above the adjoining ground level and not less than 20 feet from any window ventilation open ing or exit in any building The piping must be provided with a rain cap at the...

Page 15: ......

Page 16: ......

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ......

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ......

Page 29: ...tion with single power supply or disconnect switch it is not available with multi point option On water cooled units only optional compressor overloads are available allowing reduced unit ampacity rat...

Page 30: ......

Page 31: ......

Page 32: ......

Page 33: ......

Page 34: ......

Page 35: ......

Page 36: ......

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ......

Page 41: ......

Page 42: ...t ches to on This will energize crankcase heaters Wait a minimum of 12 hours before starting up unit Check compressor oil level Prior to startup the oil level should cover at least one third of the oi...

Page 43: ...lution should be used according to the manufacturer s directions Systems with remote air cooled condensers require periodic cleaning of the finned surface of the condenser coil Cleaning ing may be acc...

Page 44: ...ove from one compressor crankcase to the other during normal operation and balance between the two when the compressors are off This method of equali zation prohibits the oil level from dropping below...

Page 45: ...emperature cor responding to the evaporator pressure All WHR chillers are factory set for between 8 F and 12 F superheat at full load If it is necessary to increase the superheat setting of the valve...

Page 46: ...he evaporator permitting operation at lower loads than available with com pressor unloading It also keeps the velocity of refrigerant gas high enough for proper oil return at light load conditions A s...

Page 47: ...spor tation charge will be charged against its original credit value On all out of warranty compressor failures Copeland offers the same field facilities for service and or replacement as described ab...

Page 48: ...ion valve TCheck for leaks and repair Add refrigerant 2 Check riser sizes 3 Check pitch of lines and refrigerant velocities 4 Replace compressor 1 Check supply voltage for excessive line drop 2 Replac...

Page 49: ...y Claims Department P 0 Box 1551 Minneapolis MN 55440 telephone 612 553 5330 THIS WARRANTY CONSTITUTES THE BUYER S SOLE REMEDY IT IS GIVEN IN LIEU OF ALL OTHER WARRAN TIES THERE IS NO IMPLIED WARRANTY...

Reviews: