76
WGS 130A to 190A
OM WGS-5
View Circuit Status
In the following VIEW CIR screens, the N field indicates which circuit (#1, #2) is being
viewed. Certain screens located in the circuit controller are also displayed here on the unit
controller for convenience.
VIEW CIR N STATUS(1)
{Circuit Status}
Slide Pos= 000.0%
Slide Target=000.0%
Circuit Status will display one of the following:
Off:Ready
Off:Cycle
Timer Off:Low
OAT
Lock
Off:Keypad Disable
Off:Pumpdown Switch
Off:Alarm
Off:Test
Mode
EXV
Preopen
Run:Pumpdown
Run:Normal
Run:LWT PullDn Limit
Run:Unit Cap Limit
Run:High LWT Limit
Run:Evap Press Low
Run:Lift Press High
Off:pLAN failure
VIEW CIR N STATUS(2)
Hours = XXXXX
Starts = XXXXX
VIEW CIR STATUS (3)
Current (amps)
L1 L2 L3 Avg
XXX XXX XXX XXX
VIEW CIR STATUS (4)
Voltage
L1-2 L2-3 L3-1 Avg
XXX XXX XXX XXX
VIEW CIR STATUS (5)
PF= 0.XX %RLA=XXX.X
KW= XXX
KVA= XXX
View Refrigerant
In the following VIEW REFR screens, the N field indicates which circuit (#1, #2) is being
viewed.
VIEW REFR CIR N (1)
Evap Press=XXX.X psi
Cond Press=XXX.X psi
Summary of Contents for WGS130AA: WGS140AW