OM WGS-5
WGS 130A to 190A
29
Toggle:
Setpoints that have two choices, such as ON and OFF are toggled between the two
settings using the Up or Down keys on the controller.
NOTE
: in some software versions the terms “inhibit” and “hold” are used interchangeably.
Table 5, Unit Controller Setpoints
Description Default
Range
Type
PW
Unit
Unit Enable
OFF
OFF, ON
N
O
Unit Mode
Cool
Cool, Ice, Test
M
O
Control source
Switches
Switches, Keypad, Network
N
O
Available Modes
Cool
Cool, Cool w/Glycol, Cool/Ice
w/Glycol, ICE w/Glycol, TEST
N T
Cool LWT
44
F
30(40) to 60
F
N O
Ice LWT
25
F
20 to 38
F
N O
Start Delta T
10
F
0 to 10
F
M O
Stop Delta T
1.5
F
0 to 3
F
M O
Stage Up Delta T
2
F
0 to 3
F
M O
Stage Down Delta T
1
F
0 to 3
F
M O
Max Pulldown
5
F/min 0.5-5.0
F /min
M M
Evap Recirc Timer
30
0 to 300 seconds
N
M
Evap Pump Select
#1 Only
#1 Only, #2 Only, Auto
N
M
Water-cooled Yes
No,
Yes
N
M
Cond Recirc Timer (water-
cooled only)
30
0 to 300 seconds
N
M
Cond Pump Select (water-
cooled only)
#1 Only
#1 Only, #2 Only, Auto
N
M
LWT Reset Type
NONE
NONE, RETURN, 4-20mA, OAT
N
M
Max Reset
0
F
0 to 20
F
N M
Start Reset Delta T
10
F
0 to 20
F
N M
Soft Load
Off
Off, On
N
M
Begin Capacity Limit
40%
20-100%
N
M
Soft Load Ramp
20 min
1-60 minutes
N
M
Demand Limit
Off
Off, On
N
M
Low OAT Operation
(air-cooled only)
No No,
Yes
N
M
Low Ambient Lockout (air
cooled only)
55
F
-10(35) to 70
F
N M
Ice Time Delay
12
1-23 hours
N
M
Clear Ice Timer
No
No,Yes
N
M
Evap LWT sensor offset
0
-5.0 to 5.0 deg
N
M
Evap EWT sensor offset
0
-5.0 to 5.0 deg
N
M
Cond EWT/OAT sensor offset
0
-5.0 to 5.0 deg
N
M
Cond LWT sensor offset
0
-5.0 to 5.0 deg
N
M
Units
F/psi
F/psi,
C/kPa
N M
BAS Protocol
Modbus
BACnet, LonWorks, Modbus
N
M
Ident number
1
0-200
N
M
Baud Rate
19200
1200,2400,4800,9600,19200
N
M
Compressors
Sequence # Cir 1
1
1-2
M
M
Sequence # Cir 2
1
1-2
M
M
Max Comps ON
2
1-2
N
M
Start-start timer
20 min
15-60 minutes
M
M
Stop-start timer
5 min
3-20 minutes
M
M
Pumpdown Pressure
25 psi
10 to 40 psi
M
M
Pumpdown Time Limit
120 sec
0 to 180 sec
M
M
Light Load Stg Dn Point
25%
20 to 50%
M
M
Continued next page.