OM WGS-5
WGS 130A to 190A
33
Description Default
Range
PW
EXV
EXV control
Auto
Auto, manual
M
Manual EXV position
0
0-6386
M
Service Pumpdown
No
No,Yes
M
Preopen Timer (water cooled only)
20
20 to 120 seconds
M
Sensors (NOTE 1)
Evap pressure offset
0
-10.0 to 10.0 psi
M
Cond pressure offset
0
-10.0 to 10.0 psi
M
Suction temp offset
0
-5.0 to 5.0 deg
M
Discharge temp offset
0
-5.0 to 5.0 deg
M
Slide Minimum Position Offset
0
-15 to 15%
M
Slide Maximum Position Offset
0
-15 to 15%
M
Fans (available for air-cooled only)
Fan VFD enable
On
Off, On
M
Number of fans
4
4 to 6
M
Saturated Condenser Temp Target Min
90.0
80.0-110.0
o
F M
Saturated Condenser Temp Target Max
110.0
90.0-120.0
o
F M
Stage 1 On Deadband
8.0
1.0-20.0
o
F M
Stage 2 On Deadband
10.0
1.0-20.0
o
F M
Stage 3 On Deadband
11.0
1.0-20.0
o
F M
Stage 4 On Deadband
12.0
1.0-20.0
o
F M
Stage 2 Off Deadband
20.0
1.0-25.0
o
F M
Stage 3 Off Deadband
16.0
1.0-25.0
o
F M
Stage 4 Off Deadband
11.0
1.0-25.0
o
F M
Stage 5 Off Deadband
8.0
1.0-25.0
o
F M
VFD Max Speed
100%
90 to 110%
M
VFD Min Speed
25%
20 to 60%
M
Forced Fantrol 1
2
1 to 4
M
Forced Fantrol 2
3
1 to 4
M
Forced Fantrol 3
4
1 to 4
M
Notes
:
1.
Offsets are used to fine-tune certain readings generated by sensors. For example, if the controller was
showing a 125 psi value and a calibrated pressure gauge at the same location showed 127 psi, an offset of
+2 psi would be entered and the controller would then read the corrected value of 127 psi.
Table 15, RLA/FLA Values
Compressor 575V
460V
380V
230V
208V 400V
(50Hz)
RLA
197
113 141 178 282
312 141
179
94 122 145 240
267
122
167
85 112 128 210
232
112
FLA
All
113 141 178 282
312 141
NOTE
: Table values used for circuit controller input.