26
WGS 130A to 190A
OM WGS-5
Figure 7, Evaporator Pressure Drop WGS 130 – WGS 190
100
200
300
400
500 600 7008009001000
2000
Flow Rate (GPM)
Pressure D
rop (f
t of water)
Flow Rate (L/s)
6
13
19
25
32
38 44 50 57 63
126
12
18
24
27
30
9
21
15
60
90
120
150
180
Press
ure
D
rop
(kP
a)
3
4
5
6
7
8
9
10
20
30
40
50
60
WGS 160, 170, 190
WGS 130, 140
Minimum Flow
Nominal Flow
Maximum Flow
Flow Rate
Pressure Drop
Flow Rate
Pressure Drop
Flow Rate
Pressure Drop
WGS Model
gpm
L/s Ft. kPa gpm L/s Ft. kPa gpm L/s Ft. kPa
130AW/AA
195 12.3 5.8 17.4 312 19.7 13.5 40.4 520 32.9 33.9 101.1
140AW/AA
211 13.4 6.7 20.0 338 21.4 15.6 46.6 563 35.6 39.0 116.5
160AW/AA
235 14.9 4.6 13.8 376 23.8 10.8 32.3 627 39.7 27.3 81.6
170AW/AA
254 16.1 5.3 15.9 407 25.8 12.5 37.3 678 42.9 31.6 94.2
190AW/AA
273 17.3 6.1 18.1 437 27.7 14.2 42.5 728 46.1 35.9 107.2
Note: Minimum, nominal, and maximum flows are at a 16
F, 10
F, and 6
F chilled water temperature range respectively and at ARI tons.