background image

MODELS WHR-070A THRU 120A (Continued)

O F F   C Y C L E

(Refer to Diagrams 5 & 6)

On a decrease in entering water temperature thermo-

stat (TC1), stage #2 will be satisfied and the con-

tacts will open.

1. LT7 cooling light will turn off.

2. R5 relay will be de-energized, contacts R5 will

open and de-energize contactors  M5  & M7.

3. Compressor 1B will turn off immediately.

A further decrease in entering water temperature

wi II open thermostat contacts #1.

1. R1 relay will be de-energized, opening contacts R1

which allows the liquid line solenoid to close.

2. Refrigerant flow to the evaporator will be shut off

and the unit will begin to pump down.

3. The compressor will continue to operate thru pump-

down relay R3 since R1 is open.

4. The suction pressure will drop until low pressure

switch LP1 opens. Contactors  Ml & M3 and relay

R3 will open and compressor 1A will turn off and
stay off until relay R1 is again energized thru the

thermostat.

In the event compressor 1A is off on oil pressure

safety (OP1) or motor overload protection MP1, then

compressor 1B will serve as the pumpdown  compress-
or.

1.

2.

3.

4 .

Again thermostat #2 will open and de-energize re-

lay R5 and open contacts R5.

The compressor 1B will continue to operate thru
pumpdown relay R7. R7 will be in the circuit in

this case since the auxiliary contact on 

Ml 

con-

tactor  is closed.

#1 thermostat will open on further decrease in

water temperature, closing the liquid line solenoid
(LLS1) thru R1 relay.
C o m p r e s s o r  1B will continue to run until the cir-
cuit is opened by low pressure control LP1.

FIGURE 18 COMPRESSOR LOCATION

(REFERENCE TO ELECTRICAL DIAGRAMS 1 & 2)

COMP. 1A

COMP. 1B

COMP. 20

-

COMP. 2A

-

I

CONTROL

PANEL NO. 1

CONTROL

PANEL NO. 2 1

TOP VIEW OF UNIT

T A B L E   7   COMPRESSOR HORSE POWER

Page 13

Summary of Contents for Seasonpak PWA-008A

Page 1: ...BLE OF CONTENTS CONTROLS CHECKING 24 CROSSREFERENCE NEW TO OLD MO 2 ELECTRICAL 22 23 CONTROL CENTER SERVICE 26 27 ELECTRICALDATA 22 23 WIRING 10 13 WIRING DIAGRAMS 14 21 MAINTENANCE 26 29 MOVING PLACI...

Page 2: ...LL UNIT FROM ANYTHING OTHER THAN water cooled condensers Arrangement 1 is supplied THE BASE MOVING AND PLACING THE UNIT MOVING THE UNIT The McQUAY SEASONPAK water chiller is mounted on heavy wooden sk...

Page 3: ...EARANCE FOR COOLER TUBE RE MOVAL MEASURED FROM CENTER LINE OF CHILLED WATER CONNECTION ON EITHER END TABLE NO 1 MINIMUM CLEARANCE UNIT SIZE I MINIMUM CLEARANCE 007A THRU 015A 72 020A THRU 041A 96 050A...

Page 4: ......

Page 5: ......

Page 6: ...nded beyond the pro FIGURE NO 7 TO COOI ER 4 posed insulation thickness to make them accessible CHILLED WATER THERMOSTAT WHR 008A thru 060A The chilled water thermostat is mounted inside the control c...

Page 7: ...oop at the outlet end is recommended See Figure 9 WATER REGULATING VALVES EACH CONDENSER FIGURE NO 8 3 WAY WATER REGULATING VALVES COi lNG TOWER PURGE 4 MAIN CONDENSER WATER SUPPLY FROM PUMP BY PASS B...

Page 8: ...cal discharge riser is too low considerable oil may collect in the riser and the horizontal header causing the compressor to lose its oil and resultant damage due to lack of lubrication Another danger...

Page 9: ...E NO 11 PURGE VALVE DISCHARGE LINE HECK VALVE LIQUID LINE FIGURE NO 13 DISCHARGE LINE I TO EVAPORATOR RECEIVER LrQuro LINE EVAPORATORS or and receiver The discharge line piping in this case is not too...

Page 10: ...TAT 12 INDICATOR LIGHTS 6 HIGH MANUAL RESET AND LOW PRESSURE CUTOUTS 7 CONTROL SYSTEM ON OFF SWITCH FIGURE NO 16 MODELS WHR 070A THRU 120A 1 FREEZESTAT MANUAL RESET 7 CONTROL SYSTEM ON OFF SWITCH 2 OI...

Page 11: ...020A THRU 060A FIGURE NO 17 TOP VIEW OF UNIT Models WHR OO8A thru 015A are single compressor units 3 4 5 6 7 8 9 10 25 The power from 25 is fed thru NC contacts to relay R3 and R4 to energizethe compr...

Page 12: ...e operating before power can be applied to start this system Note that the crankcase heaters will be energized regard less of water flow The flow switch is recommended and does not have the shortcomin...

Page 13: ...itch LP1 opens Contactors Ml M3 and relay R3 will open and compressor 1A will turn off and stay off until relay R1 is again energized thru the thermostat In the event compressor 1A is off on oil press...

Page 14: ......

Page 15: ......

Page 16: ......

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ......

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...aches the prescribed differential within 120 seconds the thermal time delay is de energized and the control circuit remains closed If during the operation the oil pressure differential falls below 10...

Page 25: ...d unloading sequence of the unit based on a full load cooling range of 10F It should be realized however that there will be a fluctuation in the leaving water temperature as the unit cycles unloads an...

Page 26: ...eaning of the finned surface of the conden ser coil Cleaning may be accomplished by using a cold water spray brushing vacuuming or high pres sure air No tools should be used that could damage the coil...

Page 27: ......

Page 28: ...s t e m c P u r g e t h e n o n c o n d e n s i b l e s d S y s t e m o v e r c h a r g e d w i t h r e f r i g e r a n t d R e m o v e e x c e s s e D i s c h a r g e s h u t o f f v a l v e p a r t...

Page 29: ...n d t i g h t e n s y s t e m k R e p l a c e g a s k e t I Adjust t h e r m a l e x p a n s i o n v a l v e C o m p r e s s o r l o s e s o i l _ _ _ a L a c k o f r e f r i g e r a n t a C h e c k f...

Page 30: ...ber and serial number of the date of installation of the unit and date of failure along with an explanation of the malfunctions and a the unit as stamped on the serial plate attached to the unit If re...

Reviews: