background image

E L E C T R I C A L

MODELS WHR-008A THRU 060A

F I E L D   W I R I N G

Only three main power leads need be hooked up to the
chiller on Models WHR-008A thru 060A. Models WHR-

070A thru 120A have a dual control panel, each sec-
tion handling one circuit of the unit and require separ-
ate service connections to each panel. Table 8, Page

22 gives the recommended lead wire size when only
three conductors are used in a raceway. Refer to the
National Electrical Code for othertype wire or special

instructions.

Although there is no specific requirement,

inter-

locking of a flow switch and the condenser pump start-

er (or air cooled condenser fan) is suggested for the
most dependable and economical system operation.
The cooler pump should operate continuously,
when the unit is not operating.

even

The condenser pump should be field interlocked by

connecting the pump starter coil to terminal 7 and

terminal 12 as shown on Schematic Wiring Diagrams 1
and 2 and terminals 8 & 14 and 12 & 14 on Schematic
Wiring Diagrams 3 and 4, Pages 14 thru 17. This
cycles the condenser pump (or air cooled condenser
fan) with the compressor.

Referring to Diagrams 1 thru 4, the flow switch is

interlocked by removing jumpers between terminals 13

and 14 for single units and 25 and 26 for dual units,
and wiring the switch contacts into the system as is
shown on the Schematic Wiring Diagrams. When so

wired, the chilled water pump must be operating be-
fore power can be applied to start this system. Note
that the crankcase heaters will be energized regard-

less of water flow. The flow switch is recommended

and does not have the shortcomings of interlocking the
the cooler pump starter. A flow switch must be used
for leaving water temperature of 42 F and lower.

STARTING SEQUENCE

(Refer to Diagrams 1 thru 4)

Variations or options

in the control system will

change the basic wiring diagrams slightly, however,
the sequence of events will be similar.

The following starting sequence is for dual com-

pressor units. The sequence for single compressor
units is identical except for the obvious reference to

the second unit. Once the system ON-OFF switch is
pushed on the ON position, the unit will operate com-
pletely automatically.

1. Check or throw to “auto” position switches S3

and S4 (pumpdown switches). Switch is in “auto”

position during normal operation.

2. With main power on, power to the control circuit

from L1 and L2 is fed through fuse F1 to terminal

COMPRESSOR LOCATION

WHR-020A THRU 060A

FIGURE NO. 17

TOP VIEW OF UNIT

M o d e l s  WHR-OO8A thru 015A are

single compressor units.

3.

4.

5.

6.

7.

8.

9.

10.

25. The power from 25 is fed thru NC contacts to
relay R3 and R4 to energizethe compressor crank-
case heaters, when the compressors are not oper-
ating. The indicator lights should show the heaters
on. Power is also supplied to the main system On-

Off switch, S1.
Closing switch S1 energizes System No. 1 and

System No. 2.

Referring to System No. 1, power at terminal 2 in-

dicates power to the system by lighting the red
“Power on” liaht.
P r o v i d e d  operating

safety controls are closed

(FS1, OP1, HP1 and MP1 or OL1  w h e n   e x t e r n a l
overloads are used), power at terminal 3 will ener-
gize safety light, indicating the system is ready

to run.

Referring to the standard non-recycle, pumpdown

operation of the Schematic Wiring Diagram, relay
R1 and R3 are normally open and power cannot
reach compressor starter. Power can reach starter
only by energizing R1 which is controlled by ther-

mostat TC1 through the compressor lead-lag switch
(dual units only) and the pumpdown switch S3.

When cooling is required, power is supplied to
terminal 4 through water thermostat TC1 energiz-

ing relay R1, indicator light LT5.

When R1 relay is energized, contact R1 will close
and open the liquid line solenoid valve LLS1.

If low pressure control LP1 is open, the opening

of LLS1 will allow refrigerant to flow into the low

side building up pressure which will close LP1

and the compressor will start.
Meanwhile, time delay TD3 is timing the second
compressor. After the time delay closes, power is
fed to control system No. 2 and the same sequence
of starting for the second compressor is repeated.

O F F   C Y C L E

Referring to the Schematic Wiring Diagrams

when

t h e r m o s t a t   TC1 is satisfied, the electrical circuit to
terminal No. 4 (or No. 10 for second system), will be

broken opening relay R1 de-energizing the liquid line
solenoid and indicator light LT5. The compressor wi II
continue to operate through the contacts of R3 relay.
Note that R3 relay is now energized through its own

contacts and the compressor is on the pumpdown
cycle. When the compressor has pumped most of the

liquid refrigerant from the cooler, the low pressure

cut out, LP1 will open and de-energize R3 relay. This

locks the compressor off the line until the thermostat

TC1 calls for cooling again, energizing LLS1 and R1
and closing LPI.

COMPRESSOR HORSEPOWER

TABLE NO. 6

M O D E L

N U M B E R

C O M P R E S S OR NOMINAL HP

1 C O M P . 2

WHR-008A 7%

10
15

. . ...1-020A

10

 

15 15

2 0

2 0

 

 

 

WHR-050A 2.5

  W H R - 0 6 0 A

35

 11

Summary of Contents for Seasonpak PWA-008A

Page 1: ...BLE OF CONTENTS CONTROLS CHECKING 24 CROSSREFERENCE NEW TO OLD MO 2 ELECTRICAL 22 23 CONTROL CENTER SERVICE 26 27 ELECTRICALDATA 22 23 WIRING 10 13 WIRING DIAGRAMS 14 21 MAINTENANCE 26 29 MOVING PLACI...

Page 2: ...LL UNIT FROM ANYTHING OTHER THAN water cooled condensers Arrangement 1 is supplied THE BASE MOVING AND PLACING THE UNIT MOVING THE UNIT The McQUAY SEASONPAK water chiller is mounted on heavy wooden sk...

Page 3: ...EARANCE FOR COOLER TUBE RE MOVAL MEASURED FROM CENTER LINE OF CHILLED WATER CONNECTION ON EITHER END TABLE NO 1 MINIMUM CLEARANCE UNIT SIZE I MINIMUM CLEARANCE 007A THRU 015A 72 020A THRU 041A 96 050A...

Page 4: ......

Page 5: ......

Page 6: ...nded beyond the pro FIGURE NO 7 TO COOI ER 4 posed insulation thickness to make them accessible CHILLED WATER THERMOSTAT WHR 008A thru 060A The chilled water thermostat is mounted inside the control c...

Page 7: ...oop at the outlet end is recommended See Figure 9 WATER REGULATING VALVES EACH CONDENSER FIGURE NO 8 3 WAY WATER REGULATING VALVES COi lNG TOWER PURGE 4 MAIN CONDENSER WATER SUPPLY FROM PUMP BY PASS B...

Page 8: ...cal discharge riser is too low considerable oil may collect in the riser and the horizontal header causing the compressor to lose its oil and resultant damage due to lack of lubrication Another danger...

Page 9: ...E NO 11 PURGE VALVE DISCHARGE LINE HECK VALVE LIQUID LINE FIGURE NO 13 DISCHARGE LINE I TO EVAPORATOR RECEIVER LrQuro LINE EVAPORATORS or and receiver The discharge line piping in this case is not too...

Page 10: ...TAT 12 INDICATOR LIGHTS 6 HIGH MANUAL RESET AND LOW PRESSURE CUTOUTS 7 CONTROL SYSTEM ON OFF SWITCH FIGURE NO 16 MODELS WHR 070A THRU 120A 1 FREEZESTAT MANUAL RESET 7 CONTROL SYSTEM ON OFF SWITCH 2 OI...

Page 11: ...020A THRU 060A FIGURE NO 17 TOP VIEW OF UNIT Models WHR OO8A thru 015A are single compressor units 3 4 5 6 7 8 9 10 25 The power from 25 is fed thru NC contacts to relay R3 and R4 to energizethe compr...

Page 12: ...e operating before power can be applied to start this system Note that the crankcase heaters will be energized regard less of water flow The flow switch is recommended and does not have the shortcomin...

Page 13: ...itch LP1 opens Contactors Ml M3 and relay R3 will open and compressor 1A will turn off and stay off until relay R1 is again energized thru the thermostat In the event compressor 1A is off on oil press...

Page 14: ......

Page 15: ......

Page 16: ......

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ......

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...aches the prescribed differential within 120 seconds the thermal time delay is de energized and the control circuit remains closed If during the operation the oil pressure differential falls below 10...

Page 25: ...d unloading sequence of the unit based on a full load cooling range of 10F It should be realized however that there will be a fluctuation in the leaving water temperature as the unit cycles unloads an...

Page 26: ...eaning of the finned surface of the conden ser coil Cleaning may be accomplished by using a cold water spray brushing vacuuming or high pres sure air No tools should be used that could damage the coil...

Page 27: ......

Page 28: ...s t e m c P u r g e t h e n o n c o n d e n s i b l e s d S y s t e m o v e r c h a r g e d w i t h r e f r i g e r a n t d R e m o v e e x c e s s e D i s c h a r g e s h u t o f f v a l v e p a r t...

Page 29: ...n d t i g h t e n s y s t e m k R e p l a c e g a s k e t I Adjust t h e r m a l e x p a n s i o n v a l v e C o m p r e s s o r l o s e s o i l _ _ _ a L a c k o f r e f r i g e r a n t a C h e c k f...

Page 30: ...ber and serial number of the date of installation of the unit and date of failure along with an explanation of the malfunctions and a the unit as stamped on the serial plate attached to the unit If re...

Reviews: