background image

6

Sound Pressure Level

NOTES:

1.   MICROPHONE POSITION: 1M IN FRONT OF THE UNIT AND 1M BELOW THE VERTICAL CENTER LINE OF THE UNIT.

2.   THE SOUND LEVEL IS TESTED UNDER 11.5DBA BACKGROUND NOISE IN A BAFFLE CHAMBER WITH ESP OF 50 PA 

AND 75PA.

3.   THE NOMINAL AIR FLOW, POWER INPUT AND CAPACITY TEST IS UNDER THE POWER SUPPLY OF 220V/1PH/50HZ.

ESP

50Pa

75Pa

UNIT

SPEED 

1/1 Octave Sound pressure level(dBA, ref 20μPa)

Overall

dB(A)

1/1 Octave Sound pressure level(dBA, ref 20μPa)

Overall

dB(A)

63

125 250 500

1k

2k

4k

8k

63

125 250 500

1k

2k

4k

8k

200D

HIGH

18

27

37

39

39

33

24

15

43.4

22

28

37

39

38

33

26

17

43.5

MEDIUM

18

27

35

37

38

32

22

14

42.3

19

30

37

38

38

32

25

16

42.9

LOW

16

24

32

35

34

28

17

12

38.9

16

24

34

35

34

27

19

12

39.6

300D

HIGH

16

29

36

38

38

34

24

15

43.3

18

30

36

38

39

37

33

24

44.1

MEDIUM

16

27

35

37

37

33

23

15

42.1

17

29

35

37

38

36

31

22

43.1

LOW

15

25

32

34

33

29

19

13

38.7

16

28

33

35

36

33

26

17

40.8

400D

HIGH

19

31

40

42

41

38

28

18

46.5

19

32

39

41

41

38

32

25

46.2

MEDIUM

18

31

40

41

40

37

27

17

45.9

19

32

39

41

40

37

29

20

45.9

LOW

17

30

37

39

38

34

23

15

43.4

18

30

37

39

38

35

25

17

43.8

500D

HIGH

21

31

41

42

41

38

29

20

46.9

21

30

40

41

41

38

32

24

46.6

MEDIUM

21

31

40

42

41

38

28

19

46.5

21

31

40

41

40

38

31

23

46.2

LOW

18

29

38

40

39

35

25

16

44.4

20

30

38

40

38

36

28

19

44.6

600D

HIGH

22

31

41

42

43

40

30

20

48.0

24

32

42

42

43

40

32

23

48.3

MEDIUM

22

31

41

42

43

40

30

19

47.6

24

32

42

42

42

39

31

22

47.9

LOW

19

30

38

39

40

37

26

15

44.7

23

31

40

41

41

37

28

19

46.2

800D

HIGH

24

34

43

47

45

41

31

24

50.5

24

35

43

47

44

41

33

27

50.4

MEDIUM

23

33

43

46

44

40

31

24

50.1

23

35

43

46

44

41

33

26

50.0

LOW

22

32

41

45

43

39

29

21

48.6

23

34

42

45

43

39

31

24

49.1

900D

HIGH

22

35

43

44

43

40

31

21

49.0

23

36

44

44

43

40

31

20

49.2

MEDIUM

22

35

42

44

43

40

30

20

48.6

23

35

43

44

43

40

31

20

48.8

LOW

21

33

40

42

41

38

28

17

46.7

22

35

42

42

41

38

29

18

47.4

1000D

HIGH

24

36

43

43

45

39

31

21

49.2

25

35

43

43

45

40

31

21

49.4

MEDIUM

24

36

43

43

44

39

31

21

49.0

23

36

43

43

44

39

31

20

49.1

LOW

22

35

41

42

42

36

28

18

47.1

23

34

41

42

43

37

29

18

47.4

1200D

HIGH

28

35

45

48

51

44

37

29

53.9

29

35

46

48

51

45

37

30

54.0

MEDIUM

26

34

44

47

50

43

36

28

53.2

26

34

45

47

50

44

36

29

53.3

LOW

23

31

40

44

46

39

30

22

49.5

27

31

41

45

47

39

31

22

49.9

1400D

HIGH

27

38

45

47

50

45

41

36

53.7

27

39

45

47

50

45

41

36

53.6

MEDIUM

26

38

44

46

50

44

40

35

53.1

27

38

45

46

49

44

40

35

53.0

LOW

23

34

41

43

46

41

36

29

49.6

24

36

41

44

47

41

37

30

50.3

Summary of Contents for MCW1000D

Page 1: ...ING CONCEALED Chilled Water Fan Coil Unit Models MCW200D MCW800D MCW300D MCW900D MCW400D MCW1000D MCW500D MCW1200D MCW600D MCW1400D Technical Manual Engineered for flexibility and performance TM MCWD...

Page 2: ...in illustrations cover the general appearance of McQuay International products at the time of publication We reserve the right to change design and construction specifications at any time without noti...

Page 3: ...ler L Extended Drain Pan Controller M Extended Drain Pan 2 Way Valve Controller N Extended Drain Pan 3 Way Valve Controller O Standard Drain Pan 2 Way Valve Controller P Standard Drain Pan 3 Way Valve...

Page 4: ...customer requirements the new FCUs adopt the most reasonable and optimization water circuit design and utilize the national level thermal test room to guarantee both the perfect performance and a low...

Page 5: ...75 75 75 75 75 75 in wg 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 RATED POWER INPUT W 74 98 107 123 167 268 275 304 501 555 SOUND PRESSURE LEVEL DB A 42 9 43 1 45 9 46 2 47 9 50 0 48 8 49 1 53 3 53 0 C...

Page 6: ...n TESTING PRESSURE Pressure test 3 3MPa for 1 minute Leakage test 1 6MPa for 5 minutes TUBE MATERIAL COPPER DIAMETER mm 9 52 in 3 8 THICKNESS mm 0 3 in 0 012 FIN MATERIAL ALUMINIUM THICKNESS mm 0 11 i...

Page 7: ...20 46 9 21 30 40 41 41 38 32 24 46 6 MEDIUM 21 31 40 42 41 38 28 19 46 5 21 31 40 41 40 38 31 23 46 2 LOW 18 29 38 40 39 35 25 16 44 4 20 30 38 40 38 36 28 19 44 6 600D HIGH 22 31 41 42 43 40 30 20 4...

Page 8: ...5 14 5 3 4 2 4 0 344 15 8 MCW500D 75 24 0 17 9 5 5 14 5 3 8 2 7 0 389 7 2 MCW600D 75 24 0 17 9 5 5 14 5 5 0 3 7 0 482 11 4 MCW800D 75 24 0 17 9 5 5 14 5 6 2 4 6 0 618 10 0 MCW900D 75 24 0 17 9 5 5 14...

Page 9: ...783 1651 1536 1420 1408 1347 1241 1120 L 1496 1413 1365 1281 1233 1143 1096 1088 1002 892 900D H 2197 2113 2027 1920 1795 1683 1622 1560 1455 1325 M 2078 1994 1902 1814 1685 1586 1538 1477 1370 1247 L...

Page 10: ...ING LIMITS Maximum water side pressure 16 bar Minimum entering water temperature 3 C Maximum entering water temperature 95 C Minimum air inlet temperature 5 C Maximum air inlet temperature 43 C Power...

Page 11: ...30 40 50 60 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 Water Flow m 3 h Water Pressure Drop kPa 400D 300D 200D 600D 500D 900D 800D 1400D 1200D 1000D Note The press...

Page 12: ...51 94 143 218 2 902x244x25 2 600D 1214 1314 984 948 987 1047 534 150 251 94 143 218 2 1002x244x25 3 800D 1464 1564 1234 1198 1237 1297 534 150 251 94 143 218 3 1252x244x25 3 900D 1564 1664 1334 1298 1...

Page 13: ...series H M L are connected to SHF HF MF respectively MODEL MCW 200 1400 POWER SOURCE ORANGE DRAWING NO M08024067082 N L MF LF SHF HF L M BROWN H YELLOW FAN BLACK FAN SPEED SWITCH NOTE MOTOR 1 BLACK F...

Page 14: ...to the carrier with a formal claim LOCATION Before installation please check the following 1 There must be enough space for unit installation and maintenance Please refer to the unit s drawings and di...

Page 15: ...IPE CONNECTION 1 Using suitable fittings as water pipe connections Refer to the specification 2 The water inlet is on the bottom while outlet on top 3 The connection must be concealed with rubberized...

Page 16: ...15 Exploded view Part List 8 FAN 6 FILTER 7 MOTOR 2 FANDECK 4 PLENUM 1 TOP PLATE 3 DRAIN GUIDE PLATE 5 COIL 9 DRAIN PAN 10 HEDER OUTLET 11 HEADER NLET...

Page 17: ...4061142 M02124061198 M02124061198 MODEL 800D 900D 1000D 1200D 1400D 1 TOP PLATE PART NO M01014060796 M01014060797 M01014060798 M01014060796 M01014060798 2 FAN DECK PART NO M01014060806 M01014060807 M0...

Page 18: ...amless copper tubes slit type aluminum blue fins bonded to the tubes by mechanical expansion Each coil has a manual air vent and two Rc3 4 water pipe connections with a working pressure of 1 6MPa 3 Fa...

Page 19: ...ect at the time of going to press we are constantly striving for improvement and therefore reserve the right to alter model specifications and equipment without notice Details of specifications and eq...

Reviews: