Cooling Capacity ( The table below is an example)
Performance Data
NOTES:
1. COOLING CAPACITY AND HEATING CAPAITY ARE GIVEN WITH ESP OF 75PA AT MEDIUM SPEED.
2. COOLING CAPACITY IS BASED ON 5.5°C ENTERING WATER TEMPERATURE AND 14.5°C LEAVING WATER TEM-
PERATURE.
ON COIL CONDITIONS ARE SHOWN IN THE TABLES
3. HEATING CAPACITY IS BASED ON 21°C ENTERING AIR TEMPERATURE(DB) AND 60 °C ENTERING WATER TEM-
PERATURE WITH THE SAME AMOUNT OF WATER FLOW VOLUME AS COOLING
4. CAPACITY UNDER DIFFERENT ENTERING WATER TEMPERATURE AND SPEED CAN BE DERIVED BY SELECT
SOFTWARE.
Model
ESP
Entering air
Temperature(°C)
Water
Temperature(°C)
Cooling Capacity (kw)
Water flow
Water
Pressure Drop
(Pa)
DB
WB
In
Out
Total
Sensible
m
3
/h
kPa
MCW200D
75
24.0
17.9
5.5
14.5
1.5
1.0.
0.167
3.5
MCW300D
75
24.0
17.9
5.5
14.5
2.7
1.8
0.270
8.0
MCW400D
75
24.0
17.9
5.5
14.5
3.4
2.4
0.344
15.8
MCW500D
75
24.0
17.9
5.5
14.5
3.8
2.7
0.389
7.2
MCW600D
75
24.0
17.9
5.5
14.5
5.0
3.7
0.482
11.4
MCW800D
75
24.0
17.9
5.5
14.5
6.2
4.6
0.618
10.0
MCW900D
75
24.0
17.9
5.5
14.5
6.9
5.0
0.685
12.7
MCW1000D
75
24.0
17.9
5.5
14.5
8.3
6.2
0.825
21.0
MCW1200D
75
24.0
17.9
5.5
14.5
8.8
7.1
0.899
12.9
MCW1400D
75
24.0
17.9
5.5
14.5
10.0
7.8
1.031
18.4
Model
ESP
Entering air
Temperature(°C)
Water
Temperature(°C)
Cooling Capacity (kw)
Water flow
Water
Pressure Drop
(Pa)
DB
WB
In
Out
Total
Sensible
m
3
/h
kPa
MCW200D
75
27.0
19.5
5.5
14.5
2.1
1.3
0.223
5.7
MCW300D
75
27.0
19.5
5.5
14.5
3.4
2.2
0.341
12.0
MCW400D
75
27.0
19.5
5.5
14.5
4.4
2.9
0.439
24.6
MCW500D
75
27.0
19.5
5.5
14.5
5.0
3.4
0.499
11.1
MCW600D
75
27.0
19.5
5.5
14.5
6.3
4.5
0.632
18.2
MCW800D
75
27.0
19.5
5.5
14.5
8.0
5.7
0.803
15.8
MCW900D
75
27.0
19.5
5.5
14.5
8.9
6.2
0.889
19.9
MCW1000D
75
27.0
19.5
5.5
14.5
10.8
7.7
1.067
29.0
MCW1200D
75
27.0
19.5
5.5
14.5
11.7
8.9
1.223
22.2
MCW1400D
75
27.0
19.5
5.5
14.5
13.1
9.7
1.368
30.3