4
Specifications
General Data
MODEL
200D
300D
400D
500D
600D
800D
900D
1000D 1200D 1400D
AIR FLOW
HIGH
m
3
/h
332
606
757
894
1154
1446
1622
2115
2455
2748
CFM
195
356
445
526
679
851
954
1244
1444
1616
MEDIUM
m
3
/h
311
527
709
859
1120
1408
1538
1980
2217
2576
CFM
183
310
417
505
659
828
905
1165
1304
1515
LOW
m
3
/h
237
331
501
616
770
1096
1201
1465
1569
1870
CFM
139
195
295
362
453
645
706
862
923
1100
TOTAL COOLING CAPACITY
W
2044
3350
4402
5003
6300
8087
9022
10808
11939
13523
BTU/h
6974
11430
15020
17070
21496
27593
30783
36877
40736
46140
SENSIBLE COOLING CAPACITY
W
1224
2150
2897
3450
4502
5468
6428
7710
8898
10084
BTU/h
4176
7336
9885
11771
15361
18657
21932
26307
30360
34407
WATER FLOW RATE
m
3
/h
0.223
0.341
0.439
0.499
0.632
0.803
0.889
1.067
1.223
1.368
USGPM
0.981
1.500
1.932
2.196
2.781
3.533
3.912
4.695
5.381
6.019
WATER PRESSURE DROP
(COOLING)
KPa
5.7
12.0
24.6
11.1
18.2
15.8
19.9
29.0
22.2
30.3
PSI
0.827
1.740
3.567
1.610
2.639
2.291
2.886
4.205
3.219
4.394
EXTERNAL STATIC PRESSURE
Pa
75
75
75
75
75
75
75
75
75
75
in.wg
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
RATED POWER INPUT
W
74
98
107
123
167
268
275
304
501
555
SOUND PRESSURE LEVEL
DB(A)
42.9
43.1
45.9
46.2
47.9
50.0
48.8
49.1
53.3
53.0
CONDENSATE DRAIN PIPE
R3/4
DIMENSION
LENGTH
mm
714
934
1014
1114
1214
1464
1564
1664
1464
1664
WIDTH
mm
534
534
534
534
534
534
534
534
599
599
HEIGHT
mm
251
251
251
251
251
251
251
251
295
295
PACKING DIMENSION
LENGTH
mm
737
957
1037
1137
1237
1487
1587
1687
1487
1687
WIDTH
mm
553
553
553
553
553
553
553
553
618
618
HEIGHT
mm
276
276
276
276
276
276
276
276
321
321
NET WEIGHT
kg
21
25
29
31
33
44
46
49
53
57
lb
46.2
55
63.8
68.2
72.6
96.8
101.2
107.8
116.6
125.4
GROSS WEIGHT
kg
23
28
32
34
37
48
51
54
58
63
lb
50.6
61.6
70.4
74.8
81.4
105.6
112.2
118.8
127.6
138.6
OPERATING WEIGHT
kg
22
26
31
33
35
46
49
52
56
61
Notes:
1
.
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2. ALL THE UNITS ARE BEING TESTED UNDER FOLLOWING CONDITION:
a) COOLING: 27°C DB/19.5°C WB INDOOR AND WATER INLET 7°C OUTLET 12°C
b) HEATING: 21°C DB INDOOR AND WATER 60°C INLET.WATER FLOW:SAME WITH COOLING CONDITION.
3. THE NOMINAL AIR FLOW, POWER INPUT AND CAPACITY TEST IS UNDER THE POWER SUPPLY OF 220V/1PH/50HZ.