12

Electrical wiring connection must be done according to the following wiring diagram. The unit must be GROUNDED 

to the earth system of the building. All field wiring must be installed in accordance with the national wiring regulation 

and Fire Department regulation. 

Wiring Diagrams

Note: 

For MCWD series, (H. M. L.) are connected to (SHF. HF. MF.) respectively.

MODEL: MCW 200~1400

POWER

SOURCE

ORANGE

DRAWING NO.:M08024067082

N

L

MF

LF

SHF

HF

L

M

BROWN

H

YELLOW

FAN

BLACK

FAN SPEED

SWITCH

NOTE:

MOTOR

1

BLACK

FAN MOTOR
CAPACITOR

MOTOR

CAPACITOR

2

BLACK

FAN MOTOR

BLACK

FAN

RED

RED

YELLOW

BROWN

ORANGE

BLUE

BLUE

HF: HIGH SPEED

MF: MEDIUM SPEED

LF: LOW SPEED

SHF: SUPER HIGH SPEED

FIELD WIRING

FAN MOTOR2 APPLY TO 800~1400 UNITS

50~60Pa UNITS: (H,M,L) CONNECT TO (HF,MF,LF)

70~80Pa UNITS: (H,M,L) CONNECT TO (SHF,HF,MF) 

Summary of Contents for MCW1000D

Page 1: ...ING CONCEALED Chilled Water Fan Coil Unit Models MCW200D MCW800D MCW300D MCW900D MCW400D MCW1000D MCW500D MCW1200D MCW600D MCW1400D Technical Manual Engineered for flexibility and performance TM MCWD...

Page 2: ...in illustrations cover the general appearance of McQuay International products at the time of publication We reserve the right to change design and construction specifications at any time without noti...

Page 3: ...ler L Extended Drain Pan Controller M Extended Drain Pan 2 Way Valve Controller N Extended Drain Pan 3 Way Valve Controller O Standard Drain Pan 2 Way Valve Controller P Standard Drain Pan 3 Way Valve...

Page 4: ...customer requirements the new FCUs adopt the most reasonable and optimization water circuit design and utilize the national level thermal test room to guarantee both the perfect performance and a low...

Page 5: ...75 75 75 75 75 75 in wg 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 0 3 RATED POWER INPUT W 74 98 107 123 167 268 275 304 501 555 SOUND PRESSURE LEVEL DB A 42 9 43 1 45 9 46 2 47 9 50 0 48 8 49 1 53 3 53 0 C...

Page 6: ...n TESTING PRESSURE Pressure test 3 3MPa for 1 minute Leakage test 1 6MPa for 5 minutes TUBE MATERIAL COPPER DIAMETER mm 9 52 in 3 8 THICKNESS mm 0 3 in 0 012 FIN MATERIAL ALUMINIUM THICKNESS mm 0 11 i...

Page 7: ...20 46 9 21 30 40 41 41 38 32 24 46 6 MEDIUM 21 31 40 42 41 38 28 19 46 5 21 31 40 41 40 38 31 23 46 2 LOW 18 29 38 40 39 35 25 16 44 4 20 30 38 40 38 36 28 19 44 6 600D HIGH 22 31 41 42 43 40 30 20 4...

Page 8: ...5 14 5 3 4 2 4 0 344 15 8 MCW500D 75 24 0 17 9 5 5 14 5 3 8 2 7 0 389 7 2 MCW600D 75 24 0 17 9 5 5 14 5 5 0 3 7 0 482 11 4 MCW800D 75 24 0 17 9 5 5 14 5 6 2 4 6 0 618 10 0 MCW900D 75 24 0 17 9 5 5 14...

Page 9: ...783 1651 1536 1420 1408 1347 1241 1120 L 1496 1413 1365 1281 1233 1143 1096 1088 1002 892 900D H 2197 2113 2027 1920 1795 1683 1622 1560 1455 1325 M 2078 1994 1902 1814 1685 1586 1538 1477 1370 1247 L...

Page 10: ...ING LIMITS Maximum water side pressure 16 bar Minimum entering water temperature 3 C Maximum entering water temperature 95 C Minimum air inlet temperature 5 C Maximum air inlet temperature 43 C Power...

Page 11: ...30 40 50 60 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8 1 9 2 0 Water Flow m 3 h Water Pressure Drop kPa 400D 300D 200D 600D 500D 900D 800D 1400D 1200D 1000D Note The press...

Page 12: ...51 94 143 218 2 902x244x25 2 600D 1214 1314 984 948 987 1047 534 150 251 94 143 218 2 1002x244x25 3 800D 1464 1564 1234 1198 1237 1297 534 150 251 94 143 218 3 1252x244x25 3 900D 1564 1664 1334 1298 1...

Page 13: ...series H M L are connected to SHF HF MF respectively MODEL MCW 200 1400 POWER SOURCE ORANGE DRAWING NO M08024067082 N L MF LF SHF HF L M BROWN H YELLOW FAN BLACK FAN SPEED SWITCH NOTE MOTOR 1 BLACK F...

Page 14: ...to the carrier with a formal claim LOCATION Before installation please check the following 1 There must be enough space for unit installation and maintenance Please refer to the unit s drawings and di...

Page 15: ...IPE CONNECTION 1 Using suitable fittings as water pipe connections Refer to the specification 2 The water inlet is on the bottom while outlet on top 3 The connection must be concealed with rubberized...

Page 16: ...15 Exploded view Part List 8 FAN 6 FILTER 7 MOTOR 2 FANDECK 4 PLENUM 1 TOP PLATE 3 DRAIN GUIDE PLATE 5 COIL 9 DRAIN PAN 10 HEDER OUTLET 11 HEADER NLET...

Page 17: ...4061142 M02124061198 M02124061198 MODEL 800D 900D 1000D 1200D 1400D 1 TOP PLATE PART NO M01014060796 M01014060797 M01014060798 M01014060796 M01014060798 2 FAN DECK PART NO M01014060806 M01014060807 M0...

Page 18: ...amless copper tubes slit type aluminum blue fins bonded to the tubes by mechanical expansion Each coil has a manual air vent and two Rc3 4 water pipe connections with a working pressure of 1 6MPa 3 Fa...

Page 19: ...ect at the time of going to press we are constantly striving for improvement and therefore reserve the right to alter model specifications and equipment without notice Details of specifications and eq...