106
FIELD PIPING
To ensure satisfactory operation and performance, the following points should be noted for the field piping
arrangements of the complete refrigerant cycle.
a) Liquid loops or oil traps must be provided according to the position of the outdoor and the indoor units (depending on
whether the indoor unit is above or below the outdoor unit).
b) Field supplied filter dryer should be provided as close to the expansion valve(s) of the indoor unit (evaporator) as
possible.
c) Field supplied sight glass must be assembled and mounted next to filter dryer.
MAXIMUM PIPE LENGTH AND MAXIMUM NUMBER OF BENDS
When the pipe is too long, the required refrigerant quantity increases. Both the capacity and reliability drops as a result.
As the number of bends increases, system piping resistance to the refrigerant flow increases, thus lowering the cooling
capacity and the compressor may become defective. If the height difference between the evaporator and the condenser
is excessive, the cooling capacity drops, the lubricating oil return is retarded, affecting the compressor efficiency
adversely.
Always choose the shortest piping path and follow the recommendations as shown below :
Model
Max. Elevation, m
(ft.)
Max. Length,
M (ft)
Max. Total
Length, m (ft.)
Max. of Bends
MMC 075/100/125/150D/DR
20(65.6)
15 (49.2)
35(114.8)
8
CAUTION:
1) Our guarantee on the performance of our air-conditioners is strictly revoked if the height, length and/or the
number of bends of the refrigerant piping system installed is beyond the limit above.
2) Bendings must be carefully made so as not to crush the pipe. Use a pipe bender to bend a pipe as far as
possible.
Maximum Allowable Piping Length & Elevation Difference
INSTALLATION CLEARANCE
A) For MMC – D/DR series (Single/Multiple Condensing Unit)
When two or more outdoor units are installed in a location, they must be positioned such that one unit will not be taking
the hot discharge air from another to avoid hot air short circuiting.
This also applies when two or more units are installed one above the other. Below are the installation clearance
guidelines :
Model
MMC 075/100/125/150D/DR
2 x
MMC 075/100/125/150D/DR
3 x
MMC 075/100/125/150D/DR
4 x
MMC 075/100/125/150D/DR
A (mm)
300
600
600
600
B (mm)
1000
1000
1000
1000
C (mm)
1500
1500
2000
2000
Summary of Contents for M4MC075D
Page 71: ...70 Blower Performance Curves BLOWER PERFORMANCE CURVE MDB 075D...
Page 72: ...71 BLOWER PERFORMANCE CURVE MDB 100D...
Page 73: ...72 BLOWER PERFORMANCE CURVE MDB 125D...
Page 74: ...73 BLOWER PERFORMANCE CURVE MDB 150D...
Page 75: ...74 BLOWER PERFORMANCE CURVE MDB 200D...
Page 76: ...75 BLOWER PERFORMANCE CURVE MDB 250D L s 70 65 60...
Page 77: ...76 BLOWER PERFORMANCE CURVE MDB 300D...
Page 78: ...77 BLOWER PERFORMANCE CURVE MDB 400D...
Page 79: ...78 BLOWER PERFORMANCE CURVE MDB 500D...
Page 80: ...79 BLOWER PERFORMANCE CURVE MDB 075D DR VERY HIGH STATIC...
Page 81: ...80 BLOWER PERFORMANCE CURVE MDB 100D DR VERY HIGH STATIC...
Page 82: ...81 BLOWER PERFORMANCE CURVE MDB 125D DR VERY HIGH STATIC...
Page 83: ...82 BLOWER PERFORMANCE CURVE MDB 150D DR VERY HIGH STATIC...
Page 89: ...88 MODEL MDB 500D4 DR4 NOTE 1 WITH SEQUENTIAL CONTROLLER 2 VERTICAL AIR DISCHARGE...
Page 90: ...89 Outlines And Dimensions Outdoor MODEL MMC 075 100D DR MODEL MDB 125D DR...
Page 91: ...90 MODEL MMC 150D DR OUTDOOR UNIT WITH BALL VALVE MODEL MMC 075D...
Page 92: ...91 MODEL MMC 100D MODEL MMC 125D...
Page 93: ...92 MODEL MMC 150D...
Page 97: ...96 MODEL MDB 400D4 vs MMC 100D x 4 MDB 500D4 vs MMC 125D x 4 WITH SEQUENTIAL CONTROLLER...
Page 101: ...100 MODEL MDB 400DR4 vs MMC 100DR x 4 MDB 500DR4 vs MMC 125DR x 4 WITH SEQUENTIAL CONTROLLER...
Page 102: ...101 Refrigerant Circuit Diagram MODEL MMC 075D 100D 125D 150D...
Page 103: ...102 MODEL MLC 061C...
Page 104: ...103 MODEL MMC 075DR 100DR 125DR 150DR R22 M4MC 75DR 100DR 125DR 150DR R407C...
Page 177: ...2004 McQuay International 1 800 432 1342 www mcquay com ISO 9002 REGISTERED...