109
outdoor unit
Shredder valve with
core in place
Shredder valve with core removed
Most split systems have a suitable connection on the outdoor unit
Shredder valves provide easy system access for pressure reading and addition of refrigerant. On small
systems, they provide a reasonable connection for evacuation also. However, Shredder valves and the
hoses connected to them can cause very severe pressure drops and can multiply evacuation time by a factor
of 4 or 5.
On the positive side, Shredder valves provide a restriction that slows the speed of liquid charging into the
suction side. When a pressure drop is desirable (charging liquid into suction), connect via a Shredder valve.
When a pressure drop is detrimental (evacuation), connect via an open fitting.
HOW MUCH REFRIGERANT?
The proper refrigerant charge should follow the volume as recommended by manufacturer and
recommendation should be followed by the installer. Refer to the table of Refrigerant Charge Level.
If the installer cannot find the correct charge but the system must be started, refrigerant should be carefully
added to the system until reasonable sub-cooling is measured in the liquid line and reasonable suction
superheat is measured at the compressor suction. Suction and discharge pressures must be monitored
carefully during the charging process.
CHARGE LIMITS
Copeland Scroll compressors have the different charge limits for different compressor models as shown in
table below. If the total charge exceeds these limits, the system should have a crankcase heater and/or
pump down cycle and/or accumulator to prevent liquid damage to the compressor. Some systems may
require accumulators to limit liquid floodback even though the charge is lower than the published limit.
Compressor Range
Model
lbs.
kg.
Quest
ZR46 to ZR81
10
4.5
Summit
ZR84 to ZR144
16
7.3
Specter
ZR90 to ZR19M
17
7.7
CHARGING PROCEDURES - SINGLE PHASE COMPRESSORS
Evacuate the system to 500 microns Hg. (67Pa). To reduce evacuation time, use short, large diameter hoses
and connect to unrestricted service ports on the system. Quality of vacuum cannot be determined by time – a
reliable vacuum gauge must be used. A battery powered model similar to the gauge shown below is practical
since it avoids the necessity of finding a correct power outlet.
Turn the refrigerant cylinder upside down, purge the charging hose and charge liquid through the liquid line
charging port until refrigerant no longer flows or until the correct charge has been weighed in. If additional
charge is required start the system and slowly bleed liquid into the suction side until the system is full.
Shredder core
Summary of Contents for M4MC075D
Page 71: ...70 Blower Performance Curves BLOWER PERFORMANCE CURVE MDB 075D...
Page 72: ...71 BLOWER PERFORMANCE CURVE MDB 100D...
Page 73: ...72 BLOWER PERFORMANCE CURVE MDB 125D...
Page 74: ...73 BLOWER PERFORMANCE CURVE MDB 150D...
Page 75: ...74 BLOWER PERFORMANCE CURVE MDB 200D...
Page 76: ...75 BLOWER PERFORMANCE CURVE MDB 250D L s 70 65 60...
Page 77: ...76 BLOWER PERFORMANCE CURVE MDB 300D...
Page 78: ...77 BLOWER PERFORMANCE CURVE MDB 400D...
Page 79: ...78 BLOWER PERFORMANCE CURVE MDB 500D...
Page 80: ...79 BLOWER PERFORMANCE CURVE MDB 075D DR VERY HIGH STATIC...
Page 81: ...80 BLOWER PERFORMANCE CURVE MDB 100D DR VERY HIGH STATIC...
Page 82: ...81 BLOWER PERFORMANCE CURVE MDB 125D DR VERY HIGH STATIC...
Page 83: ...82 BLOWER PERFORMANCE CURVE MDB 150D DR VERY HIGH STATIC...
Page 89: ...88 MODEL MDB 500D4 DR4 NOTE 1 WITH SEQUENTIAL CONTROLLER 2 VERTICAL AIR DISCHARGE...
Page 90: ...89 Outlines And Dimensions Outdoor MODEL MMC 075 100D DR MODEL MDB 125D DR...
Page 91: ...90 MODEL MMC 150D DR OUTDOOR UNIT WITH BALL VALVE MODEL MMC 075D...
Page 92: ...91 MODEL MMC 100D MODEL MMC 125D...
Page 93: ...92 MODEL MMC 150D...
Page 97: ...96 MODEL MDB 400D4 vs MMC 100D x 4 MDB 500D4 vs MMC 125D x 4 WITH SEQUENTIAL CONTROLLER...
Page 101: ...100 MODEL MDB 400DR4 vs MMC 100DR x 4 MDB 500DR4 vs MMC 125DR x 4 WITH SEQUENTIAL CONTROLLER...
Page 102: ...101 Refrigerant Circuit Diagram MODEL MMC 075D 100D 125D 150D...
Page 103: ...102 MODEL MLC 061C...
Page 104: ...103 MODEL MMC 075DR 100DR 125DR 150DR R22 M4MC 75DR 100DR 125DR 150DR R407C...
Page 177: ...2004 McQuay International 1 800 432 1342 www mcquay com ISO 9002 REGISTERED...