56
COOLING (R22)
MODEL : MDB400D4 vs. MMC100D x 4
Indoor WB
Outdoor DB, °C
°C
19.4
25
30
35
40
46
50
52
54
13.9
31,860
34,627
37,097
39,567
42,037
45,002
46,978
47,966
48,954
15
32,110
34,939
37,465
39,992
42,518
45,549
47,570
48,581
49,591
16.7
32,496
35,422
38,035
40,648
43,260
46,396
48,486
49,531
50,576
18
32,791
35,791
38,470
41,149
43,828
47,043
49,186
50,258
51,329
19.4
33,109
35,647
37,914
40,180
43,616
47,740
50,489
51,864
53,238
20
33,245
36,343
39,109
41,874
44,640
47,959
50,172
51,278
52,385
22
33,699
36,855
39,673
42,491
45,309
48,690
50,945
52,072
53,199
22.2
33,744
36,906
39,729
42,553
45,376
48,763
51,022
52,151
53,280
24
34,153
37,367
40,237
43,107
45,977
49,421
51,717
52,865
54,013
MODEL : MDB500D4 vs. MMC125D x 4
Indoor WB
Outdoor DB, °C
°C
19.4
25
30
35
40
46
50
52
54
13.9
40,256
43,823
47,008
50,193
53,379
57,201
59,749
61,023
62,297
15
40,600
44,230
47,472
50,714
53,956
57,846
60,440
61,736
63,033
16.7
41,131
44,860
48,189
51,519
54,848
58,844
61,507
62,839
64,171
18
41,537
45,341
48,738
52,134
55,531
59,606
62,324
63,682
65,041
19.4
41,974
45,240
48,156
51,072
55,325
60,428
63,830
65,531
67,232
20
42,162
46,073
49,565
53,057
56,549
60,740
63,534
64,930
66,327
22
42,786
46,785
50,355
53,925
57,495
61,779
64,635
66,063
67,491
22.2
42,849
46,856
50,434
54,012
57,590
61,883
64,745
66,177
67,608
24
43,411
47,497
51,145
54,793
58,441
62,819
65,737
67,196
68,655
All power units in watts
Summary of Contents for M4MC075D
Page 71: ...70 Blower Performance Curves BLOWER PERFORMANCE CURVE MDB 075D...
Page 72: ...71 BLOWER PERFORMANCE CURVE MDB 100D...
Page 73: ...72 BLOWER PERFORMANCE CURVE MDB 125D...
Page 74: ...73 BLOWER PERFORMANCE CURVE MDB 150D...
Page 75: ...74 BLOWER PERFORMANCE CURVE MDB 200D...
Page 76: ...75 BLOWER PERFORMANCE CURVE MDB 250D L s 70 65 60...
Page 77: ...76 BLOWER PERFORMANCE CURVE MDB 300D...
Page 78: ...77 BLOWER PERFORMANCE CURVE MDB 400D...
Page 79: ...78 BLOWER PERFORMANCE CURVE MDB 500D...
Page 80: ...79 BLOWER PERFORMANCE CURVE MDB 075D DR VERY HIGH STATIC...
Page 81: ...80 BLOWER PERFORMANCE CURVE MDB 100D DR VERY HIGH STATIC...
Page 82: ...81 BLOWER PERFORMANCE CURVE MDB 125D DR VERY HIGH STATIC...
Page 83: ...82 BLOWER PERFORMANCE CURVE MDB 150D DR VERY HIGH STATIC...
Page 89: ...88 MODEL MDB 500D4 DR4 NOTE 1 WITH SEQUENTIAL CONTROLLER 2 VERTICAL AIR DISCHARGE...
Page 90: ...89 Outlines And Dimensions Outdoor MODEL MMC 075 100D DR MODEL MDB 125D DR...
Page 91: ...90 MODEL MMC 150D DR OUTDOOR UNIT WITH BALL VALVE MODEL MMC 075D...
Page 92: ...91 MODEL MMC 100D MODEL MMC 125D...
Page 93: ...92 MODEL MMC 150D...
Page 97: ...96 MODEL MDB 400D4 vs MMC 100D x 4 MDB 500D4 vs MMC 125D x 4 WITH SEQUENTIAL CONTROLLER...
Page 101: ...100 MODEL MDB 400DR4 vs MMC 100DR x 4 MDB 500DR4 vs MMC 125DR x 4 WITH SEQUENTIAL CONTROLLER...
Page 102: ...101 Refrigerant Circuit Diagram MODEL MMC 075D 100D 125D 150D...
Page 103: ...102 MODEL MLC 061C...
Page 104: ...103 MODEL MMC 075DR 100DR 125DR 150DR R22 M4MC 75DR 100DR 125DR 150DR R407C...
Page 177: ...2004 McQuay International 1 800 432 1342 www mcquay com ISO 9002 REGISTERED...