OM AGSD-1
65
EXB1 status shows whether the pCOe at tLAN address 1 is online or offline. The digital
input and digital output status is shown, with either a “0” or a “1” on the bottom line of the
screen designating off and on states.
VIEW UNIT STATUS (8)
EXB4 {Status}
D.I. 1234 D.O. 1234
XXXX XXXX
EXB4 status shows whether the pCOe at tLAN address 4 is online or offline. The digital
input and digital output status is shown, with either a “0” or a “1” on the bottom line of the
screen designating off and on states.
View Unit Temperature
VIEW UNIT TEMP (1)
Evap LWT= XXX.X
o
F
Evap EWT= XXX.X
o
F
Active SP= XXX.X
o
F
VIEW UNIT TEMP (2)
LWT Pulldn= 0.0
o
F/m
Evap Delta T= XX.X
OAT= XXX.X
o
F
View Circuit Status
In the following VIEW CIR screens, the N field indicates which circuit (#1, #2, and #3
when applicable) is being viewed.
VIEW CIR N STATUS(1)
{Circuit Status}
Slide Pos= 000.0%
Slide Target=000.0%
Circuit Status will display one of the following:
Off:Ready
Off:Stage
Up
Delay
Off:Cycle
Timer
Off:Low OAT Lock
Off:Keypad Disable
Off:Pumpdown Switch
Off:Alarm
Off:Test
Mode
EXV
Preopen
Run:Pumpdown
Run:Normal
Run:LWT
PullDn
Limit
Run:Unit Cap Limit
Run:High LWT Limit
Run:Disc SH Low
Run:Evap Press Low
Run:Lift Press High
Off:pLAN failure
VIEW CIR N STATUS(2)
Hours = XXXXX
Starts = XXXXX
Summary of Contents for AGS 225D
Page 79: ...OM AGSD 1 79 FIELD WIRING DIAGRAM continued...
Page 80: ...80 OM AGSD 1 FIELD WIRING DIAGRAM continued...
Page 81: ...OM AGSD 1 81...