OM AGSD-1
19
Expansion I/O Controller 4
EXB4 is connected to CP1 for additional I/O.
Analog Inputs
#
Description
Signal Source
Expected Range
1
Chilled Water Reset
4-20 mA Current
4 to 20 mA
2
Demand Limit
4-20 mA Current
4 to 20 mA
3
Oil Pressure #1
4-20 mA Current
3 to 22 mA
4
Oil Pressure #2
4-20 mA Current
3 to 22 mA
Analog Outputs
# Description
Output
Signal
Range
1
Open
Digital Inputs
#
Description
Signal Off
Signal On
1
Open
2
External Alarm
Alarm active
Alarm not active
3
Open
4
Open
Digital Outputs
#
Description
Output Off
Output On
1
Fan motor 15/16
Fans Off
Fans On
2
Fan motor 17/18/19
Fans Off
Fans On
3
Fan motor 25/26
Fans Off
Fans On
4
Fan motor 27/28/29
Fans Off
Fans On
Expansion I/O Controller 3
EXB3 is connected to CP1 for additional I/O.
Analog Inputs
# Description
Signal
Source
Range
1 Open
2 Open
3 Open
4 Open
Analog Outputs
# Description
Output
Signal
Range
1 Open
Digital Inputs
#
Description
Signal Off
Signal On
1
Pump #1 alarm
Pump Failure
Pump OK
2
Pump #2 alarm
Pump Failure
Pump OK
3 Open
4 Open
Digital Outputs
#
Description
Output Off
Output On
1
Evap Water Pump Output #2
Pump Off
Pump On
2
Compressor Status Enable #1
Compressor Off
Compressor On
3
Compressor Status Enable #2
Compressor Off
Compressor On
4
Compressor Status Enable #3
Compressor Off
Compressor On
Summary of Contents for AGS 225D
Page 79: ...OM AGSD 1 79 FIELD WIRING DIAGRAM continued...
Page 80: ...80 OM AGSD 1 FIELD WIRING DIAGRAM continued...
Page 81: ...OM AGSD 1 81...