64
OM
AGSD-1
Unit Status will display one of the following:
Auto
Off:Ice Mode Timer
Off:All Cir Disabled
Off:Unit
Alarm
Off:Keypad
Disable
Off:Remote
Switch
Off:BAS
Disable Off:Unit
Switch
Off:Test
Mode
Auto:Wait for load
Auto:OAT Lockout
Auto:Evap Recirc
Auto:Wait for flow
Auto:Pumpdown
Unit mode can show ‘Cool Mode’, ‘Ice Mode’, or ‘Test Mode’.
Pump states include Off, Start, and Run.
VIEW UNIT STATUS (2)
Softload Limit=XXX.X
Demand Limit= XXX.X
Network Limit= XXX.X
Values are in percent.
VIEW UNIT STATUS (3)
Unit Capacity=XXX.X%
Ice Delay= XXh XXm
Unit capacity is based on slide valve(s) position.
Ice delay will be visible only when unit mode is ICE.
VIEW UNIT STATUS (4)
CP1 D.O. 111111111
123456789012345678
XXXXXXXXXXXXXXXXXX
The digital output (D.O.) above and input (D.I.) below, status will show either a “0” or a “1”
designating off and on states.
VIEW UNIT STATUS (5)
CP1 D.I. 111111111
123456789012345678
XXXXXXXXXXXXXXXXXX
VIEW UNIT STATUS (6)
CP1 Analog Outputs
#1=000.0% #2=000.0%
#3=000.0% #4=000.0%
VIEW UNIT STATUS (7)
EXB1 {Status}
D.I. 1234 D.O. 1234
XXXX XXXX