OM AGSD-1
35
Type Index I/O
Description
LONworks BACnet
Modbus
I 5 O
Active
alarms
5
x
x
x
I 6 O
Active
alarms
6
x x
x
I 7 O
Active
alarms
7
x x
x
I 8 O
Active
alarms
8
x
x
x
I 9 O
Active
alarms
9
x x
x
I 10 O
Active
alarms
10
x
x
x
I 11 O
Active
alarms
11
x
x
x
I 12 O
Active
alarms
12
x
x
x
I 13 O
Active
alarms
13
x x
x
I 14 O
Active
alarms
14
x x
x
I 15 O
Active
alarms
15
x
x x
I 16 O
Active
alarms
16
x x
x
I
17
I
Network chiller mode set point
x
x
x
I
18
O
LON Chiller run mode
x
x
x
I
19
O
Active unit mode
x
x
x
I
20
I
Network Capacity Limit default set point
x
I
21
I
Network chiller mode default set point
x
I
22
O
CSM unit full load/circuit available status
x x
x
I
28
O
Unit model type, refrigerant
x x
x
I 29 O
Unit
language
x x
x
I
30
O
Unit software version
x x
x
I 32 I
Compressor
select
x
x
x
I 35
I/O
Clock
year
x
x
I 36
I/O
Clock
month
x
x
I
37
I/O Clock day of month
x
x
I
38
I/O Clock day of week
x x
I 39
I/O
Clock
hours
x
x
I 40
I/O
Clock
minutes
x
x
I 45 O
Compressor
starts
x
x
x
I
46
O
Compressor run hours
x
x
x
D
1
I/O Network chiller enable set point
x
x
x
D 2 O
Chiller
enable
status
x
x
x
D
3
O
Active alarm indicator
x
x x
D
4
O
Chiller run enabled
x
x x
D
5
O
Chiller local control
x x
x
D
6
O
Chiller capacity limited
x
x
x
D
7
O
Evaporator Water Flow
x x
x
D
8
O
Condenser Water Flow
x x
x
D
9
I
Network chiller enable default set point
x
D
10
I
Ignore network defaults
x
D
12
I
Set clock command
x
x
D
24
I
Network clear alarm signal
x
x
x
D 29 O
Evaporator
pump
x x
x
Parameter Details
Units of Measure
Parameters are expressed in different units depending on the protocol selected.
ParameterType
Modbus Units
BACnet Units
LONworksUnits
Temperature
o
F X 10
o
F X 10
o
C X 100
Pressure
PSI X 10
PSI X 10
KPa X 10
Percentage
% X 10
% X 10
% X 200