OM AGSD-1
21
Digital Outputs
#
Description
Output OFF
Output ON
1
SSS Enable
Compressor Off
Compressor On
2 SV
Load
Off
Load
3 SV
Unload
Off
Unload
4 Open
5
SV Liquid Line
Off
Enabled
6
Fan motor 31/VFD enable
Off
Fan on
7
Fan motor 32
Off
Fan on
8
Fan motor 33/34
Off
Fans on
9 Open
10 Open
11 Open
12
EXV close #3
Open
Pumpdown
13 Open
14 Open
15 Open
16 Open
17 Open
18 Open
Expansion I/O Controller 5
EXB5 is connected to CP2 for additional I/O.
Analog Inputs
#
Description Signal
Source
Range
1
Suction Temperature #3
NTC Thermister
-45 to 195°F
2 Open
3 Open
4 Open
Analog Outputs
#
Description Output
Signal
Range
1 Open
Digital Inputs
#
Description
Signal Off
Signal On
1
Thermistor Fault #2
Fault
No Fault
2 Open
3 Open
4 Open
Digital Outputs
#
Description
Output Off
Output On
1 Open
2 Open
3
SV Economizer #3
Off
Enabled
4 Open