INSTALLING COOKER INTO THE SYSTEM OF WATER HEATING
-for intake and output of water into the system of central heating, connections of of
1" on boiler are anticipated.
- cooker may be mounted on closed or open system of central heating.
Mounting to closed system of central heating
One of the way of proper installation is shown on the picture 5.
-
safety valve must be installed on the vicinity of boiler and must be set to pressure of
max. 3 bar (boiler is tested for 4 bar). Connection guide of safety valve must be as
shorter as possible and may not be capable for closing. This guide, also, may not
contain any valve or any other fixing.
- Closed expansion vessel is to be installed next to the boiler ad safety valve is short.
Volume of this vessel is to be determined based on capacity of boiler, thereat
propotion of 1kW:1l is valid.
- It is obligatory to install safety thermal valve of boiler on anticipated place. We
recommend safety thermal valve Caleffi 544.
E
ta
žn
i
šte
dn
ja
k
Fig. 5
Diagram of closed system of central heating
Mounting to open system of central heating