background image

-8-

FIGURE 8

NORMAL - 3 WIRE PLUG

FIGURE 8
3-Wire Service Cord or Conduit Installation

1. Insure that the copper ground strap

IS CONNECTED

between the middle post of the main terminal
connection block and the range chassis.

2. The middle wire of the service cord or ground lead of

3-wire conduit

MUST

connect to the neutral (middle)

post of the main terminal block. The other two wires of
the service cord or conduit connect to the outside
posts of the main terminal connection block. Polarity is
unimportant.

3. An appropriate strain relief for service cord or conduit

MUST

be attached to the conduit plate.

FIGURE 9
4-Wire Service Cord or Conduit Installation

(Mobile Homes Or As Required By Codes)

1. The copper ground strap connected between the

neutral (middle) post of the main terminal block and the
chassis

MUST

be cut off as shown in figure 9. Save the

green ground screw to attach the ground from the 4
wire cord. Only a 4 wire cord or conduit should be
used.

2. The ground wire from the service cord or conduit must

connect to the range chassis using the green ground
screw.

3. The white wire of the service cord or conduit must

connect to the neutral (middle) post of the main
terminal block. The other two wires of the service cord
connect to the red and black posts of the main terminal
block, respectively.

4. An appropriate strain relief for service cord or conduit

MUST

be attached to the conduit plate.

FIGURE 9

4-WIRE PLUG

Conversion From 3-Wire To 4-Wire Service

(Free-Standing or Slide-in Models Only With 3-Wire
Service Cord Attached).

Disconnect range from power. Remove the access cover
on back of range and remove the 3-wire service cord from
the main terminal block. Follow instructions as outlined in
figure 9 to connect the 4-wire service cord.

NOTE:

Cord replacement -

ONLY

a power supply cord

rated at 240 volts minimum, 40 amperes or 50 amperes
power supply cord that is marked for use with nominal 1
3/8

²

(34.93 mm) diameter connection opening, with

closed loop terminals and marked for use with ranges
shall be used.

Summary of Contents for PER5715BAW

Page 1: ...e of range can result in serious injury or property damage CLEARANCE DIMENSIONS For complete information in regard to installation of free standing drop in and slide in ranges see figures 1 through 4...

Page 2: ...L INSPECTOR A 30 inches minimum clearance between the top of the cooking surface and the bottom of an unprotected wood or metal cabinet or A 24 inches minimum when bottom of wood or metal cabinet is p...

Page 3: ...SELF CLEAN RANGE DISCOLORATION OR DELAMINATION MAY OCCUR TO AVOID POSSIBLE DAMAGE WE RECOMMEND INCREASING THE 30 CABINET OPENING TO 31 1 4 MINIMUM AND USING HEAT SHIELD KIT CABKIT V THE COUNTERTOP CU...

Page 4: ...23 1 4 CUT DEPTH PROVIDE FOR 120 208 120 240 VOLT JUNCTION BOX FOR RANGE CONDUIT BELOW UNIT 1 1 4 27 1 2 FROM TOP OF COUNTER 30 CABINET OPENING RECOMMEND THE USE OF 3 1 2 WIDE SLATS ON EACH SIDE 24 C...

Page 5: ...l C Use the bracket as a template and mark the required holes as shown in figure 5 for the type of construction you will be using D Free standing and slide in ranges may be secured to either floor or...

Page 6: ...are equipped with a non lift up top All free standing ranges with a glass top are non lift up Coil tops are lift up D For SAFETY CONSIDERATIONS as well as optimum performance adjust the range so that...

Page 7: ...ire plug in outlet placed at a convenient point near the back of the range The range is then connected to this outlet through an approved range connector pigtail fastened securely to the terminal bloc...

Page 8: ...d Only a 4 wire cord or conduit should be used 2 The ground wire from the service cord or conduit must connect to the range chassis using the green ground screw 3 The white wire of the service cord or...

Reviews: