background image

-6-

ANTI-TIP DEVICE INSTALLATION INSTRUCTIONS

STEP 3 - Range Installation

A. Free-standing and slide-in ranges may be installed by

one person. The drop-in requires two persons due to
adjusting leveling legs and making electrical
connection while range is suspended in cut-out.

B. Align the range to its designated location and slide it

back into position. Note: A minimum clearance of 1/4

²

is required between the range and the leveling foot
that will engage the ANTI-TIP bracket, see figure 6.

CAUTION:

Damage to the range may occur if range

is moved or lifted by grasping the main top or
backguard. (If equipped).

C. All slide-in and drop-in ranges are equipped with a

non lift-up top. All free-standing ranges with a glass
top are non lift-up. Coil tops are lift-up.

D. For SAFETY CONSIDERATIONS as well as optimum

performance adjust the range so that it is level. This
may be checked by placing a spirit level or a large
pan of water on the cooktop or the oven rack. If an
adjustment is required on free-standing, pull the range
forward, tip the range and rotate the leveling feet as
required. Slide-in and drop-in ranges require total
removal from cabinet before an adjustment can be
made.

E. To check the range for proper installation of the

anti-tip bracket: Use a flashlight and look underneath
the bottom of the range to see that one of the rear
leveling legs is engaged in the bracket slot.

F. Proceed with the remainder of the installation

instructions provided with the range.

FIGURE 6

Summary of Contents for PER5715BAW

Page 1: ...e of range can result in serious injury or property damage CLEARANCE DIMENSIONS For complete information in regard to installation of free standing drop in and slide in ranges see figures 1 through 4...

Page 2: ...L INSPECTOR A 30 inches minimum clearance between the top of the cooking surface and the bottom of an unprotected wood or metal cabinet or A 24 inches minimum when bottom of wood or metal cabinet is p...

Page 3: ...SELF CLEAN RANGE DISCOLORATION OR DELAMINATION MAY OCCUR TO AVOID POSSIBLE DAMAGE WE RECOMMEND INCREASING THE 30 CABINET OPENING TO 31 1 4 MINIMUM AND USING HEAT SHIELD KIT CABKIT V THE COUNTERTOP CU...

Page 4: ...23 1 4 CUT DEPTH PROVIDE FOR 120 208 120 240 VOLT JUNCTION BOX FOR RANGE CONDUIT BELOW UNIT 1 1 4 27 1 2 FROM TOP OF COUNTER 30 CABINET OPENING RECOMMEND THE USE OF 3 1 2 WIDE SLATS ON EACH SIDE 24 C...

Page 5: ...l C Use the bracket as a template and mark the required holes as shown in figure 5 for the type of construction you will be using D Free standing and slide in ranges may be secured to either floor or...

Page 6: ...are equipped with a non lift up top All free standing ranges with a glass top are non lift up Coil tops are lift up D For SAFETY CONSIDERATIONS as well as optimum performance adjust the range so that...

Page 7: ...ire plug in outlet placed at a convenient point near the back of the range The range is then connected to this outlet through an approved range connector pigtail fastened securely to the terminal bloc...

Page 8: ...d Only a 4 wire cord or conduit should be used 2 The ground wire from the service cord or conduit must connect to the range chassis using the green ground screw 3 The white wire of the service cord or...

Reviews: