Maytag MLG-45PDB Installation Manual Download Page 7

113489- 3  (W10185535)

Maytag Co.

7

EXAMPLE: For a bank of 4 dryers, 2 unrestricted openings
measuring 20-inches by 22.5-inches (50.80 cm by 57.15 cm)
are acceptable.
To compensate for the use of registers or louvers used over
the openings, this area must be increased by approximately
33%.  Make-up air openings should not be located in an area
directly near where exhaust vents exit the building.
Allowances must be made for remote or constricting
passageways or where dryers are located at high altitudes
or predominantly low pressure areas.

IMPORTANT:

 Make-up air must be free of dry cleaning

solvent fumes.  Make-up air that is contaminated by dry
cleaning solvent fumes will result in irreparable damage to
the motors and other dryer components.

NOTE:

 

Component failure due to dry cleaning solvent

fumes will void the warranty.

Exhaust Requirements ________________

Exhaust ductwork should be designed and installed by a
qualified professional.  Improperly sized ductwork will create
excessive back pressure, which results in slow drying,
increased use of energy, and shutdown of the burner by the
airflow (sail) switch, burner hi-limits, or lint chamber hi-limit
protector thermostat.  The dryer must be installed with a proper
exhaust duct connection to the outside.

A = 20-inches (50.80 cm)
B = 22.5-inches (57.15 cm)

Dryer Enclosure Requirements _______

 A

The requirement to allow the dryer door to open
completely is 33.5-inches (85.1 cm).

B

A minimum overhead clearance of 12-inches (30.48 cm)
is required.

C

Dryer should be positioned a minimum of 12-inches
(30.48 cm) away from the nearest obstruction.  24-inches
(60.96 cm) is recommended for ease of installation,
maintenance, and service.

D

1/16” (1.5875 mm) minimum is required.

E

Flooring should be level or below dryer cabinet for ease
of removing panels during maintenance.

F

Dryers may be positioned sidewall to sidewall, however
a 1/16” (1.5875 mm) minimum allowance must be made
for the opening and closing of the control door, along
with the removal of panels during maintenance.

G

4-inch (10.16 cm) maximum.

Fresh Air Supply Requirements _______

When the dryer is operating, it draws in room air, heats it,
passes this air through the tumbler, and exhausts it out of the
building.  Therefore, the room air must be continually
replenished from the outdoors.  If the make-up air is
inadequate, drying time and drying efficiency will be adversely
affected.  Ignition problems and sail switch “fluttering”
problems may result, as well as premature motor failure from
overheating.  The dryer must be installed with provisions for
adequate combustion and make-up air supply.
Air supply (make-up air) must be given careful consideration
to ensure proper performance of each dryer.  Fresh air
ventilation openings shall not be blocked and/or sealed.  As
a general rule, an unrestricted air entrance from the outdoors
of 224 inch

2

 (1,445 cm

2

) is required for each dryer.  (Based on

1 inch

2

 [6.5 cm

2

] per 1,000 Btu [252 kcal].)

It is not necessary to have a separate make-up air opening
for each dryer.  Common make-up air openings are
acceptable.  However, they must be set up in such a manner
that the make-up air is distributed equally to all the dryers.

Fire Hazard

Use a heavy metal vent.
Do not use a plastic vent.
Do not use a metal foil vent.
Failure to follow these instructions can result in
death or fire.

 

WARNING

!

Summary of Contents for MLG-45PDB

Page 1: ...MLG 45PDB Installation Manual Stack Dryer Part No 113489 3 W10185535 RETAIN THESE INSTRUCTIONS IN A SAFE PLACE FOR FUTURE REFERENCE...

Page 2: ...to light any appliance Do not touch any electrical switch Do not use any phone in your building Clear the room building or area of all occupants Immediately call your gas supplier from a neighbor s ph...

Page 3: ...iminate static unless recommended by the manufacturer of the fabric softener or product Do not use heat to dry articles containing foam rubber or similarly textured rubber like materials Clean lint sc...

Page 4: ...l entretien des commandes tiquetez tous les fils avant de les d brancher Des erreurs de c blage peuvent entra ner un fonctionnement inad quat et dangereux WARNING The dryer must never be operated wit...

Page 5: ...TAINER 8 16 DRYERS PER 48 53 TRUCK 25 27 VOLTAGE AVAILABLE 120 240V 1 2w 50 60 Hz APPROXIMATE NET WEIGHT 1 015 lb 460 40 kg APPROXIMATE SHIPPING WEIGHT 1 080 lb 489 88 kg AIRFLOW PER POCKET 60 Hz 600...

Page 6: ...st be installed with adequate clearance for air openings into the combustion chamber IMPORTANT The dryer must be installed in a location environment which the ambient temperature remains between 40 F...

Page 7: ...from the nearest obstruction 24 inches 60 96 cm is recommended for ease of installation maintenance and service D 1 16 1 5875 mm minimum is required E Flooring should be level or below dryer cabinet f...

Page 8: ...6 in wc 1 48 mb NOTE When the exhaust ductwork passes through a wall ceiling or roof made of combustible materials the opening must be 2 inches 5 08 cm larger than the duct all the way around The duct...

Page 9: ...uct to the nearest obstruction The length of the ductwork from the dryer to the outside exhaust outlet must not exceed 20 feet 6 09 meters The minimum diameter of this ductwork must be at least 8 inch...

Page 10: ...ode ANSI NFPA NO 70 LATEST EDITION or in Canada the installation must conform to applicable Canada Standards Canadian Electrical Codes Parts 1 2 CSA C22 1 1990 or LATEST EDITION The ground connection...

Page 11: ...erials and workmanship conform to local and state regulations or codes of the country of destination In the absence of such codes all plumbing connections materials and workmanship must conform to the...

Page 12: ...nections The dryer is provided with a 3 4 N P T inlet pipe connection on top of the dryer It is recommended that a gas shutoff valve be provided to the gas supply line of each dryer for ease in servic...

Page 13: ...s desired setting NOTE When a cycle is interrupted by opening the main door cycle time will continue to count downward regardless if the door is open or closed Selection setting changes can be made at...

Page 14: ...r cabinet s avoid using harsh abrasives A product intended for the cleaning of appliances is recommended Adjustments 7 Days After Installation and Every 12 Months Thereafter Inspect bolts nuts screws...

Reviews: