background image

3

2  Shipping Inspection

Always transport the unit upright; laying the unit on its side or top 

during transit may cause equipment damage. The installer should in

-

spect the product upon receipt for shipping damage and subsequent 

investigation is the responsibility of the carrier.  The installer must 

verify the model number, specifications, electrical characteristics, 

and accessories are correct prior to installation. The distributor or 

manufacturer will not accept claims from dealers for transportation 

damage or installation of incorrectly shipped units. 

2.1 Parts

 

Also inspect the unit to verify all required components are 

present and intact.  Report any missing components imme-

diately to Goodman or to the distributor.  Use only factory 

authorized replacement parts (see Section 5). Make sure to 

include the full product model number and serial number 

when reporting and/or obtaining service parts.

2.2 Handling

 

Use caution when transporting/carrying the unit. Do not move 

unit using shipping straps. Do not carry unit with hooks or sharp 

objects. The preferred method of carrying the unit after arrival 

at the job site is to carry via a two-wheel hand truck from the 

back or sides or via hand by carrying at the cabinet corners.

3  Codes & Regulations

This product is designed and manufactured to comply with appli

-

cable national codes. Installation in accordance with such codes 

and/or prevailing local codes/regulations is the responsibility of the 

installer. The manufacturer assumes no responsibility for equipment 

installed in violation of any codes or regulations.

The United States Environmental Protection Agency (EPA) has 

issued various regulations regarding the introduction and disposal 

of refrigerants. Failure to follow these regulations may harm the 

environment and can lead to the imposition of substantial fines. 

Should you have any questions please contact the local office of the 

EPA and/or refer to EPA’s website www.epa.gov.

4  Replacement Parts

When reporting shortages or damages, or ordering repair parts, 

give the complete product model and serial numbers as stamped 

on the product.  Replacement parts for this product  are available 

through your contractor or local distributor. For the location of your 

nearest distributor consult the white business pages, the yellow 

page section of the local telephone book or contact:

HOMEOWNER SUPPORT

GOODMAN MANUFACTURING COMPANY, L.P.

19001 KERMIER ROAD,

WALLER, TX 77484

(877) 254-4729

5  Pre-Installation Considerations

5.1  Preparation

 

Keep this document with the unit. Carefully read all instruc

-

tions for the installation prior to installing product. Make sure 

each step or procedure is understood and any special consid

-

erations are taken into account before starting installation. 

Assemble all tools, hardware and supplies needed to complete 

the installation. Some items may need to be purchased locally. 

Make sure everything needed to install the product is on hand 

before starting.

5.2  System Matches

 

The  entire  system  (combination  of  indoor  and  outdoor 

sections) must be manufacturer approved and Air-Condi

-

tioning, Heating, and Refrigeration Institute (AHRI) listed. 

 

NOTE: 

Installation of unmatched systems is not permitted.  

Damage or repairs due to installation of unmatched systems 

is not covered under the warranty.

5.3  Interconnecting Tubing

 

Give special consideration to minimize the length of refrigerant 

tubing when installing air handlers. Refer to Remote Cooling/

Heat Pump Service Manual RS6200006, and TP-107 Long Line 

Set Application R-410A for tubing guidelines. If possible, allow 

adequate length of tubing such that the coil may be removed 

(for inspection or cleaning services) from the cabinet without 

disconnecting the tubing.

5.4 Clearances

 

The unit clearance from a combustible surface may be 0”. 

However, service clearance must take precedence. A minimum 

of 24” in front of the unit for service clearance is  required. 

Additional clearance on one side or top will be required for 

electrical wiring connections. Consult all appropriate reg

-

ulatory codes prior to determining final clearances. When 

installing this unit in an area that may become wet (such as 

crawl spaces), elevate the unit with a sturdy, non-porous ma

-

terial. In installations that may lead to physical damage (i.e. a 

garage) it is advised to install a protective barrier to prevent 

such damage. Always install units such that a positive slope 

in condensate line (1/4” per foot) is allowed.

5.5  Horizontal Applications

 

If installed above a finished living space, a secondary drain 

pan (as required by many building codes), must be installed 

under the entire unit and its condensate drain line must be 

routed to a location such that the user will see the condensate 

discharge.

6  Installation Location

NOTE: 

These air handlers are designed for 

indoor installation only

.

The AVPTC**14** product line may be installed in one of the up

-

flow, downflow, horizontal left or horizontal right orientations as 

shown in Figures 2, 3, 4 and 5. The unit may be installed in upflow 

or horizontal left orientation as shipped (refer to specific sections 

for more information). 
Minor field modifications are necessary to convert to downflow 

or horizontal right as indicated in below sections. 

Summary of Contents for Amana AVPTC 14 Series

Page 1: ...nt The manufac turer will not be responsible for any injury or property dam age arising from improper service or servide procedures If you service this unit you assume responsibility for any injury or...

Page 2: ...ards Institute ANSI National Fire Protection Association NFPA 70 and local state codes In Canada electrical grounding is to be in accordance with the Canadian Electric Code CSA C22 1 uninterrupted unb...

Page 3: ...this document with the unit Carefully read all instruc tions for the installation prior to installing product Make sure each step or procedure is understood and any special consid erations are taken...

Page 4: ...CMK0014 Condensate Kit AVPTC25B14 AVPTC29B14 AVPTC31C14 AVPTC49D14 AVPTC33C14 AVPTC49C14 AVPTC37B14 AVPTC37C14 AVPTC61D14 AVPTC39C14 AVPTC37D14 AVPTC59C14 AVPTC59D14 CONDENSATE KIT TABLE 1 6 3 Downflo...

Page 5: ...follow the specification for the condenser heat pump 7 2 Tubing Preparation All cut ends are to be round burr free and clean Failure to follow this practice increases the chances for refrigerant leak...

Page 6: ...so will result in improper condensate drainage COIL INSTALLATION FOR DOWNFLOW Figure 8 Upper Tie Plate Control Deck Downflow Bracket Center Support Filter Bracket Filter Access Panel ACCESS PANEL CONF...

Page 7: ...e liquid line at the liquid line service valve and 4 6 from the compressor on the suction line Ensure the thermometer makes adequate contact and is insulated for best possible readings Use liquid line...

Page 8: ...above a finished living space to prevent sweating Install a condensate trap to ensure proper drainage NOTE When units are installed above ceilings or in other locationswheredamagefromcondensateoverfl...

Page 9: ...on the ONLY heat kits that are permitted to be used are the HKS series Refer to the air handler unit s Serial and Rating plate or the HKS specification sheets to determine the heat kits compatible wit...

Page 10: ...ll after 20 minutes the system would allow for an additional 20 heat pump run 20 of the 20 minute target is an additional 4 minutes In this case the system would turn on back up electric heat after 24...

Page 11: ...sconnect ALL power before servicing Multiple power sources may be present HIGH VOLTAGE To avoid property damage personal injury or death due to electrical shock this unit MUST have an electrical groun...

Page 12: ...the female connections on the casing down If the motor is not oriented with the connections down water could collect in the motor and may cause premature failure FEMALE CONNECTIONS SIDE VIEW WARN ING...

Page 13: ...outdoor control board power Two stage outdoor units may not behave properly without this 24 VAC transformer Figure 15 3 Download the Cool Cloud HVAC phone application for charging and to configure te...

Page 14: ...stage Heat Pumps 4 Go to the Tonnage Units Menu and select the ton nage value that corresponds to the desired airflow for the outdoor unit See the following table NOTE For the two stage non communicat...

Page 15: ...on 19 Auxiliary Alarm Switch The control is equipped with a 24VAC Aux Alarm to be used for a condensate switch install designated by CON DENSATE IN OUT on the control By default the connected AUX swit...

Page 16: ...nce and increase comfort level Select the desired ramping profile using the Cool Cloud phone application or the push button menus Figure 22 23 Electric Air Cleaner Warning The control is equipped with...

Page 17: ...rom any areas where there may be objectionable odors flammable vapors or products of combustion such ascarbon monoxide CO which may cause serious personal injury or death 25 Regular Maintenance HIGH V...

Page 18: ...e or disconnected wiring connection at circulator motor power leads Open circuit in inductor or loose wiring connection at inductor 3 4 Hp and 1 Hp models only Failed circulator blower motor Tighten o...

Page 19: ...otor if necessary No Air Handler operation Circulator blower motor shuts down for over or under voltage condition Circulator blower motor shuts down due to over temperature condition on power module H...

Page 20: ...stage heat pumps Indoor Airflow for non communicating outdoor units values based on 400CFM per ton default 3 0 Ton Cooling Airflow Trim default 0 Cooling Airflow Profile setting default profile D sho...

Page 21: ...ing the next heat call if the heat pump fails to satisfy the custom target time for this number of consecutive cycles default 20 cycles Menu is enabled if the menu is set to 6 if the addition of low s...

Page 22: ...comm units Compressor Heat Low Stage Comm Units Compressor Heat High Stage Comm Units Electric Heat Single Stage Electric Heat Low Stage Electric Heat High Stage Defrost Single Stage Electric Heat non...

Page 23: ...avigation and Selection Instructions Using Phone Application over Bluetooth Network 1 Connect to the air handler instructions provided by phone during connection process 2 Select desired settings menu...

Page 24: ...24 29 Wiring Diagrams HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH WARNING...

Page 25: ...ng diagram on the unit for the most up to date wiring HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJUR...

Page 26: ...maintained filter will keep the indoor coil of your comfort system clean A dirty coil could cause poor operation and or severe equipment damage Your air filter or filters could be located in your fur...

Page 27: ...27 THIS PAGE WAS LEFT BLANK INTENTIONALLY...

Page 28: ...u purchased to be directed to the feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a...

Reviews: