background image

7

7.3  Tubing Connections for TXV Models

 

TXV models come with factory installed TXV with the bulb 

pre-installed on the vapor tube.

1.  Remove refrigerant tubing panel or coil (lower) access pan

-

el.  

2.  Remove access valve fitting cap and depress the valve stem 

in access fitting to release pressure. No pressure indicates 

possible leak.

3.  Replace the refrigerant tubing panel.
4.  Remove the spin closure on both the liquid and suction 

tubes using a tubing cutter.

5.  Insert liquid line set into liquid tube expansion and slide 

grommet about 18” away from braze joint. 

6.  Insert suction line set into suction tube expansion and slide 

insulation and grommet about 18” away from braze joint. 

7.  Braze joints. Quench all brazed joints with water or a wet 

rag upon completion of brazing. 

NOTE

: The sensing bulb must be permanently located.  A heat 

shield, heat trap, or wet rag must be used during brazing to prevent 

damage to the TXV valve.

8. Replace access panels, suction line grommet, insulation and 

all screws.

RUBBER

GROMMET

SUCTION LINE

WITH SPIN CLOSURE

Suction Line Grommet

Figure 10

7.4   Thermal Expansion Valve System Adjustment

 

Run the system at Cooling for 10 minutes until refrigerant 

pressures stabilize. Use the following guidelines and meth

-

ods to check unit operation and ensure that the refrigerant 

charge is within limits. Charge the unit on low stage.

1.  Purge gauge lines. Connect service gauge manifold to base-

valve service ports.  

2.  Temporarily install a thermometer on the liquid line at the 

liquid line service valve and 4-6’’ from the compressor on 

the suction line. Ensure the thermometer makes adequate 

contact and is insulated for best possible readings. Use 

liquid line temperatice to determine subcooling and vapor 

temperature to determine superheat.

3.  Check subcooling and superheat. Systems with TXV applica

-

tion should have a subcooling of 7  to 9°F and superheat of 

7 to 9°F 

  a. If subcooling and superheat are low, adjust TXV to 7 to 

9°F, and then check subcooling.

NOTE

: To adjust superheat, turn the valve stem clockwise to in

-

crease and counter clockwise to decrease.

  b. If subcooling is low and superheat is high, 

add 

charge to 

raise subcooling  to 7 to 9°F, and then check superheat.

  c. If subcooling and superheat are high, 

adjust 

TXV valve to 

7 to 9° superheat, then check subcooling.

  d. If subcooling is high and superheat is low, 

adjust 

TXV valve 

to 7 to 9° superheat and 

remove 

charge to lower the sub

-

cooling to 7 to 9°F.

NOTE

: Do NOT adjust the charge based on suction pressure unless 

there is a gross undercharge.

4. Disconnect manifold set, and installation is complete.

NOTE

: Check the Schrader ports for leaks and tighten valve cores 

if necessary. Install caps finger-tight.

SUBCOOL FORMULA=
SAT. LIQUID LINE TEMP - LIQUID LINE TEMP
SUPERHEAT FORMULA=
SUCT. LINE TEMP - SAT. SUCT. TEMP

SUCTION PRESSURE

PSIG  

R-22  

R-410A  

50

26

1

52

28

3

54

29

4

56

31

6

58

32

7

60

34

8

62

35

10

64

37

11

66

38

13

68

40

14

70

41

15

72

42

16

74

44

17

76

45

19

78

46

20

80

48

21

85

50

24

90

53

26

95

56

29

100

59

31

110

64

36

120

69

41

130

73

45

140

78

49

150

83

53

160

86

56

170

90

60

SATURATED SUCTION PRESSURE

 TEMPERATURE CHART

SATURATED SUCTION 

TEMPERATURE ºF

Summary of Contents for Amana AVPTC 14 Series

Page 1: ...nt The manufac turer will not be responsible for any injury or property dam age arising from improper service or servide procedures If you service this unit you assume responsibility for any injury or...

Page 2: ...ards Institute ANSI National Fire Protection Association NFPA 70 and local state codes In Canada electrical grounding is to be in accordance with the Canadian Electric Code CSA C22 1 uninterrupted unb...

Page 3: ...this document with the unit Carefully read all instruc tions for the installation prior to installing product Make sure each step or procedure is understood and any special consid erations are taken...

Page 4: ...CMK0014 Condensate Kit AVPTC25B14 AVPTC29B14 AVPTC31C14 AVPTC49D14 AVPTC33C14 AVPTC49C14 AVPTC37B14 AVPTC37C14 AVPTC61D14 AVPTC39C14 AVPTC37D14 AVPTC59C14 AVPTC59D14 CONDENSATE KIT TABLE 1 6 3 Downflo...

Page 5: ...follow the specification for the condenser heat pump 7 2 Tubing Preparation All cut ends are to be round burr free and clean Failure to follow this practice increases the chances for refrigerant leak...

Page 6: ...so will result in improper condensate drainage COIL INSTALLATION FOR DOWNFLOW Figure 8 Upper Tie Plate Control Deck Downflow Bracket Center Support Filter Bracket Filter Access Panel ACCESS PANEL CONF...

Page 7: ...e liquid line at the liquid line service valve and 4 6 from the compressor on the suction line Ensure the thermometer makes adequate contact and is insulated for best possible readings Use liquid line...

Page 8: ...above a finished living space to prevent sweating Install a condensate trap to ensure proper drainage NOTE When units are installed above ceilings or in other locationswheredamagefromcondensateoverfl...

Page 9: ...on the ONLY heat kits that are permitted to be used are the HKS series Refer to the air handler unit s Serial and Rating plate or the HKS specification sheets to determine the heat kits compatible wit...

Page 10: ...ll after 20 minutes the system would allow for an additional 20 heat pump run 20 of the 20 minute target is an additional 4 minutes In this case the system would turn on back up electric heat after 24...

Page 11: ...sconnect ALL power before servicing Multiple power sources may be present HIGH VOLTAGE To avoid property damage personal injury or death due to electrical shock this unit MUST have an electrical groun...

Page 12: ...the female connections on the casing down If the motor is not oriented with the connections down water could collect in the motor and may cause premature failure FEMALE CONNECTIONS SIDE VIEW WARN ING...

Page 13: ...outdoor control board power Two stage outdoor units may not behave properly without this 24 VAC transformer Figure 15 3 Download the Cool Cloud HVAC phone application for charging and to configure te...

Page 14: ...stage Heat Pumps 4 Go to the Tonnage Units Menu and select the ton nage value that corresponds to the desired airflow for the outdoor unit See the following table NOTE For the two stage non communicat...

Page 15: ...on 19 Auxiliary Alarm Switch The control is equipped with a 24VAC Aux Alarm to be used for a condensate switch install designated by CON DENSATE IN OUT on the control By default the connected AUX swit...

Page 16: ...nce and increase comfort level Select the desired ramping profile using the Cool Cloud phone application or the push button menus Figure 22 23 Electric Air Cleaner Warning The control is equipped with...

Page 17: ...rom any areas where there may be objectionable odors flammable vapors or products of combustion such ascarbon monoxide CO which may cause serious personal injury or death 25 Regular Maintenance HIGH V...

Page 18: ...e or disconnected wiring connection at circulator motor power leads Open circuit in inductor or loose wiring connection at inductor 3 4 Hp and 1 Hp models only Failed circulator blower motor Tighten o...

Page 19: ...otor if necessary No Air Handler operation Circulator blower motor shuts down for over or under voltage condition Circulator blower motor shuts down due to over temperature condition on power module H...

Page 20: ...stage heat pumps Indoor Airflow for non communicating outdoor units values based on 400CFM per ton default 3 0 Ton Cooling Airflow Trim default 0 Cooling Airflow Profile setting default profile D sho...

Page 21: ...ing the next heat call if the heat pump fails to satisfy the custom target time for this number of consecutive cycles default 20 cycles Menu is enabled if the menu is set to 6 if the addition of low s...

Page 22: ...comm units Compressor Heat Low Stage Comm Units Compressor Heat High Stage Comm Units Electric Heat Single Stage Electric Heat Low Stage Electric Heat High Stage Defrost Single Stage Electric Heat non...

Page 23: ...avigation and Selection Instructions Using Phone Application over Bluetooth Network 1 Connect to the air handler instructions provided by phone during connection process 2 Select desired settings menu...

Page 24: ...24 29 Wiring Diagrams HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH WARNING...

Page 25: ...ng diagram on the unit for the most up to date wiring HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJUR...

Page 26: ...maintained filter will keep the indoor coil of your comfort system clean A dirty coil could cause poor operation and or severe equipment damage Your air filter or filters could be located in your fur...

Page 27: ...27 THIS PAGE WAS LEFT BLANK INTENTIONALLY...

Page 28: ...u purchased to be directed to the feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a...

Reviews: