background image

12

at this entry point.  Some codes/municipalities require the 

supply wire to be enclosed in conduit.  Consult your local 

codes.

Side of

Cabinet

Top of

Cabinet

KNOCK-OUT FOR ELECTRICAL CONNECTIONS

Figure 12

 

13.4.1 Air Handler Only (Non-Heat Kit Models)

The building supply connects to the stripped black and red 

wires contained in the air handler electrical compartment 

cavity. A ground screw is also contained in this area.  Attach 

the Supply wires to the air handler conductors as shown in 

the unit wiring diagram using appropriately sized solderless 

connectors or other NEC or CEC approved means.

   13.4.2 Air Handler - Non-Circuit Breaker Heat Kits

 

A terminal block is provided with the HKS kit to attach the 

power supply and air handler connections. Follow the HKS 

Installation Manual and wiring diagram for complete wiring 

details. 

   13.4.3 Air Handler With Circuit Breaker Heat Kit

 

The air handler has a plastic cover on the upper access panel 

that will require either one or both sections to be removed 

to allow the heat kit circuit breaker(s) to be installed.  The 

circuit breakers have lugs for power supply connection. See 

the HKS Installation Instructions for further details. 

14  AVPTC Motor Orientation

If the unit is in the upflow position, there is no need to rotate the 

motor.  If the unit is in the downflow position, loosen motor mount 

and rotate motor as shown in the 

AVPTC Motor Orientation

 figure 

below.

 

Be sure motor is oriented with the female connections on 

the casing down.  If the motor is not oriented with the connections 

down, water could collect in the motor and may cause premature 

failure.

FEMALE CONNECTIONS

SIDE VIEW

W

ARN
IN

G

SO

FT

W

ARE

 VE

R.

TO

P

FRONT VIEW

AVPTC Motor Orientation

Figure 13

15 Cool Cloud HVAC Phone Application

NOTE

: This equipment has been tested and found to comply with 

the limits for a Class B digital device, pursuant to part 15 of the FCC 

Rules. These limits are designed to provide reasonable protection 

against harmful interference in a residential installation. This equip

-

ment generates, uses and can radiate radio frequency energy and, 

if not installed and used in accordance with the instructions, may 

cause harmful interference to radio communications. However, 

there is no guarantee that interference will not occur in a particular 

installation. If this equipment does cause harmful interference to 

radio or television reception, which can be determined by turning 

the equipment off and on, the user is encouraged to try to correct 

the interference by one or more of the following measures:

—Reorient or relocate the receiving antenna.
—Increase the separation between the equipment and receiver.
—Connect the equipment into an outlet on a circuit different 

from that to which the receiver is connected.

—Consult the dealer or an experienced radio/ TV technician 

for help.

Actual screens may look different based on the mobile device 

being used. 

Figure 14

This air handler is Bluetooth ready and functions with the Cool 

Cloud HVAC phone application designed to improve the contrac

-

tor’s setup / diagnostic experience. Users can see specific model 

Summary of Contents for Amana AVPTC 14 Series

Page 1: ...nt The manufac turer will not be responsible for any injury or property dam age arising from improper service or servide procedures If you service this unit you assume responsibility for any injury or...

Page 2: ...ards Institute ANSI National Fire Protection Association NFPA 70 and local state codes In Canada electrical grounding is to be in accordance with the Canadian Electric Code CSA C22 1 uninterrupted unb...

Page 3: ...this document with the unit Carefully read all instruc tions for the installation prior to installing product Make sure each step or procedure is understood and any special consid erations are taken...

Page 4: ...CMK0014 Condensate Kit AVPTC25B14 AVPTC29B14 AVPTC31C14 AVPTC49D14 AVPTC33C14 AVPTC49C14 AVPTC37B14 AVPTC37C14 AVPTC61D14 AVPTC39C14 AVPTC37D14 AVPTC59C14 AVPTC59D14 CONDENSATE KIT TABLE 1 6 3 Downflo...

Page 5: ...follow the specification for the condenser heat pump 7 2 Tubing Preparation All cut ends are to be round burr free and clean Failure to follow this practice increases the chances for refrigerant leak...

Page 6: ...so will result in improper condensate drainage COIL INSTALLATION FOR DOWNFLOW Figure 8 Upper Tie Plate Control Deck Downflow Bracket Center Support Filter Bracket Filter Access Panel ACCESS PANEL CONF...

Page 7: ...e liquid line at the liquid line service valve and 4 6 from the compressor on the suction line Ensure the thermometer makes adequate contact and is insulated for best possible readings Use liquid line...

Page 8: ...above a finished living space to prevent sweating Install a condensate trap to ensure proper drainage NOTE When units are installed above ceilings or in other locationswheredamagefromcondensateoverfl...

Page 9: ...on the ONLY heat kits that are permitted to be used are the HKS series Refer to the air handler unit s Serial and Rating plate or the HKS specification sheets to determine the heat kits compatible wit...

Page 10: ...ll after 20 minutes the system would allow for an additional 20 heat pump run 20 of the 20 minute target is an additional 4 minutes In this case the system would turn on back up electric heat after 24...

Page 11: ...sconnect ALL power before servicing Multiple power sources may be present HIGH VOLTAGE To avoid property damage personal injury or death due to electrical shock this unit MUST have an electrical groun...

Page 12: ...the female connections on the casing down If the motor is not oriented with the connections down water could collect in the motor and may cause premature failure FEMALE CONNECTIONS SIDE VIEW WARN ING...

Page 13: ...outdoor control board power Two stage outdoor units may not behave properly without this 24 VAC transformer Figure 15 3 Download the Cool Cloud HVAC phone application for charging and to configure te...

Page 14: ...stage Heat Pumps 4 Go to the Tonnage Units Menu and select the ton nage value that corresponds to the desired airflow for the outdoor unit See the following table NOTE For the two stage non communicat...

Page 15: ...on 19 Auxiliary Alarm Switch The control is equipped with a 24VAC Aux Alarm to be used for a condensate switch install designated by CON DENSATE IN OUT on the control By default the connected AUX swit...

Page 16: ...nce and increase comfort level Select the desired ramping profile using the Cool Cloud phone application or the push button menus Figure 22 23 Electric Air Cleaner Warning The control is equipped with...

Page 17: ...rom any areas where there may be objectionable odors flammable vapors or products of combustion such ascarbon monoxide CO which may cause serious personal injury or death 25 Regular Maintenance HIGH V...

Page 18: ...e or disconnected wiring connection at circulator motor power leads Open circuit in inductor or loose wiring connection at inductor 3 4 Hp and 1 Hp models only Failed circulator blower motor Tighten o...

Page 19: ...otor if necessary No Air Handler operation Circulator blower motor shuts down for over or under voltage condition Circulator blower motor shuts down due to over temperature condition on power module H...

Page 20: ...stage heat pumps Indoor Airflow for non communicating outdoor units values based on 400CFM per ton default 3 0 Ton Cooling Airflow Trim default 0 Cooling Airflow Profile setting default profile D sho...

Page 21: ...ing the next heat call if the heat pump fails to satisfy the custom target time for this number of consecutive cycles default 20 cycles Menu is enabled if the menu is set to 6 if the addition of low s...

Page 22: ...comm units Compressor Heat Low Stage Comm Units Compressor Heat High Stage Comm Units Electric Heat Single Stage Electric Heat Low Stage Electric Heat High Stage Defrost Single Stage Electric Heat non...

Page 23: ...avigation and Selection Instructions Using Phone Application over Bluetooth Network 1 Connect to the air handler instructions provided by phone during connection process 2 Select desired settings menu...

Page 24: ...24 29 Wiring Diagrams HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH WARNING...

Page 25: ...ng diagram on the unit for the most up to date wiring HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJUR...

Page 26: ...maintained filter will keep the indoor coil of your comfort system clean A dirty coil could cause poor operation and or severe equipment damage Your air filter or filters could be located in your fur...

Page 27: ...27 THIS PAGE WAS LEFT BLANK INTENTIONALLY...

Page 28: ...u purchased to be directed to the feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a...

Reviews: