background image

Installation and operation manual 

Fan coil units

English

Installation and operation manual

Fan coil units

FWE04FF/T
FWE05FF/T
FWE06FF/T
FWE08FF/T
FWE10FF/T
FWE12FF/T
FWE14FF/T
FWE16FF/T
FWE20FF/T
FWE24FF/T

Summary of Contents for FWE04FF/T

Page 1: ...tallation and operation manual Fan coil units English Installation and operation manual Fan coil units FWE04FF T FWE05FF T FWE06FF T FWE08FF T FWE10FF T FWE12FF T FWE14FF T FWE16FF T FWE20FF T FWE24FF...

Page 2: ...iau nurodytas direktyvas arba reglamentus su s lyga kad gaminiai bus eksploatuojami laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instr...

Page 3: ...s or regulation s provided that the products are used in accordance with our instructions as amended S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibil...

Page 4: ...Shortened maintenance and replacement cycles 18 14 Troubleshooting 18 14 1 To solve the problems with your fan coil unit 18 14 2 Relocation 19 15 Disposal 19 16 Technical data 20 16 1 Wiring diagram 2...

Page 5: ...or equipment on top of the unit Do NOT sit climb or stand on the unit DANGER RISK OF ELECTROCUTION Make sure that the system is earthed properly Turn OFF the power supply before servicing Install the...

Page 6: ...g of soft material or protective plates together with a rope when lifting the unit This to avoid damage or scratches to the unit 1 Lift the unit by holding onto the hanger brackets without exerting an...

Page 7: ...gs Make sure the installation site withstands the weight and vibration of the unit Take care that in the event of a water leak water cannot cause any damage to the installation space and surroundings...

Page 8: ...TICE Always use upper air purges 5 3 Mounting the unit 5 3 1 To install the suspension bolts Use the pattern to determine the suspension bolt positions upper part of the packing Suspension bolt positi...

Page 9: ...ield supply Adjust the unit to the correct position for installation 1 50 Check if the unit is horizontally levelled Level Make sure the unit is level at all 4 corners using a level or a water filled...

Page 10: ...he fan coil unit is off but water keeps circulating in the unit condensation will form on the unit and water may drip NOTICE Do not use excessive force when connecting the piping This could deform the...

Page 11: ...s during the initial operating hours of the system Additional filling with water afterwards may be required NOTICE Make sure water quality complies with EU directive 2020 2184 5 5 Drain piping install...

Page 12: ...nt installation 5 6 1 Preparing of optional equipment INFORMATION Optional equipment When installing optional equipment also read the installation manual of the optional equipment Depending on the fie...

Page 13: ...missible voltage and current permitted for the equipment in use NOTICE The equipment described in this manual may cause electronic noise generated from radio frequency energy The equipment complies to...

Page 14: ...hen connecting wiring which is the same thickness do as shown in the figure above For wiring use the designated power wire and connect firmly then secure to prevent outside pressure being exerted on t...

Page 15: ...clean the air conditioner or air filter be sure to stop operation and turn all power supplies OFF Otherwise an electrical shock and injury may result WARNING Keep any required ventilation openings cl...

Page 16: ...nment Avoid excessive heating or cooling Prevent direct sunlight from entering a room during cooling operation by using curtains or blinds Ventilate often Extended use requires special attention to ve...

Page 17: ...mly when washing the blade with water Possible consequence The surface sealing peels off Clean with a soft cloth If it is difficult to remove stains use water or a neutral detergent 13 3 1 To clean th...

Page 18: ...Troubleshooting If one of the following malfunctions occurs take the measures shown below and contact your dealer The system MUST be repaired by a qualified service person Malfunction Measure If a saf...

Page 19: ...urself dismantling the system treatment of the refrigerant of oil and of other parts MUST be done by an authorised installer and MUST comply with applicable legislation Units MUST be treated at a spec...

Page 20: ...27 Galvasined steel plastic foam 1 7 10 12 28 29 30 35 Rubber 19 25 26 31 36 EPP 20 Copper 17 16 Technical data A subset of the latest technical data is available on the regional Daikin website public...

Page 21: ...otes 1 Terminal block Field wiring 2 Refer to installation manual for power requirement 16 2 Dimensions Overview 57 5 462 SUSPENSION POSITION 19 38 237 AF SUSPENSION POSITION AD AE AG DRAIN HOSE 16 7...

Page 22: ...ncia el trica total ekilen toplam elektrik g c Total effekting ng Total elektrisk str meffekt Celkov elektrick p kon Ukupna primljena snaga elektri ne energije Teljes ramforr s bemenet Consum total d...

Page 23: ......

Page 24: ...TANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P756931 1 2023 11 Copyright 20...

Reviews: