background image

10

NOTE:

  The Temperature Rise Tables can also be used to estimate 

the air handler airflow delivery.  When using these tables for this 

purpose set the room thermostat to maximum heat and allow the 

system to reach steady state conditions.  Insert two thermometers, 

one in the return air and one in the supply air.  The temperature 

rise is the supply air temperature minus the return air temperature. 

Using the temperature rise calculated, CFM can be estimated from 

the TR formula above. See Spec Sheets and/or Service Manual for 

more information.

Comfort Setting Menu (CFS):

 There are 6 options 

available in the Comfort Setting Menu which impacts 

system target run time and electric heat functionality. 

Electric heat operation adjustments only apply if a 

communicating heat pump is installed. Comfort Setting 

Options 1 – 5 have set values for the System Target 

Runtime and option 6 enables additional menus to 

customize all comfort settings.  See list below for the 

System Target Runtimes associated with the first 5 Comfort 

Settings. These first 5 options are setup to help satisfy the 

thermostat slower or faster based on the selection where 

option 1, with a 10 minute Target Runtime, is attempting to 

satisfy much faster than option 5, with a 30 minute Target 

Runtime.

System Target Runtime:

Comfort Setting Option 1) 10 Minute System Target 

Runtime

Comfort Setting Option 2) 15 Minute System Target 

Runtime

Comfort Setting Option 3) 20 Minute System Target 

Runtime

Comfort Setting Option 4) 25 Minute System Target 

Runtime

Comfort Setting Option 5) 30 Minute System Target 

Runtime

Electric Heat Adjustment:

  This system will automatically 

determine if the heat pump is capable of satisfying the 

thermostat in the selected System Target Runtime.  If the 

heat pump is unable to satisfy in the selected time, electric 

heat settings will determine how many attempts should be 

given to the heat pump before temporarily locking it out 

and using the furnace. These electric heat settings also 

determine at what time the system should remove the 

temporary heat pump lockout and run the heat pump again.

There are four adjustable items associated with back up 

electric heat operation control. In the same way as the 

System Target Time, each of these items have defaulted 

values for Comfort Settings 1 – 5.  Only when Comfort 

Setting 6 is selected will each item be available for full 

adjustment.

1. 

Stage Up Percent (7 segment menu SUP):

 This is a value 

that determines how far past the target runtime the system 

should continue running the heat pump before transitioning 

to the furnace. For example, assume this menu was set to 

20% with a target runtime of 20 minutes.  If the thermostat 

did not remove the heating call after 20 minutes, the system 

would allow for an additional 20% heat pump run (20% of 

the 20 minute target is an additional 4 minutes). In this 

case, the system would turn on back up electric heat after 

24 minutes if the thermostat call was still present. Each 

time this occurs, the system records this as a strike against 

the heat pump (the strike is important when looking at the 

Over Target Threshold)

2. 

Over Target Threshold (7 segment menu Ott):

 If the heat 

pump has consecutively activated back up electric heat 

for the selected Over Target Threshold amount of times, 

meaning for this many consecutive cycles it has been unable 

to satisfy the target time by itself,  then the heat pump will 

be temporarily locked out and the furnace will become the 

primary heat source.

3. 

Stage Down Percent (7 segment menu SdP):

 This only 

applies when the heat pump and back up electric heat are 

activated on initial start-up.  In this case, the system will try 

to determine when the best time to operate the heat pump 

individually again.  To determine this, the system looks at 

how easily the air handler is able to satisfy the thermostat 

using the heat pump with back up electric heat.  Assume this 

setting is 15% and the target time is 20 minutes. If the heat 

pump with back up electric heat can satisfy the thermostat 

in less than 17 minutes (20 minutes - 15% = 17 minutes) 

then the algorithm records a strike against the air handler 

(this strike is important when looking at the Under Target 

Threshold).

4. 

Under Target Threshold (7 segment menu Utt):

  If the air 

handler is able to satisfy the thermostat using the heat pump 

with back up electric heat for the selected number of consec

-

utive cycles the electric heat operation will be temporarily 

removed.  The heat pump will then be used during the next 

cycle. If the heat pump can satisfy the thermostat in less 

than the System Target Runtime the back up heat operation 

will be completely removed and the heat pump will become 

the primary heat source again. if it fails to do so, the strike 

count against the furnace will be reset and the furnace will 

remain the temporary primary heat source until the Under 

Target Threshold is reached again.

The system will automatically make adjustments in an 

attempt to satisfy the thermostat as close to this target 

runtime as possible.  After a power cycle or mode change 

(cooling to heating or heating to cooling) the system will 

run full capacity for the selected mode during the first 

thermostat call.  Based on the selected target runtime and 

how long the initial cycle takes to satisfy the thermostat, 

the control algorithm will adjust the system stage times for 

a 2 stage unit or the capacity demand percentage for an 

inverter / modulating unit for the next cycle.  Note: actual 

runtimes may change depending on variations of load 

throughout the day.

The following table shows the default values for all Comfort 

Setting Options (1 – 5)

Summary of Contents for Amana AVPTC 14 Series

Page 1: ...nt The manufac turer will not be responsible for any injury or property dam age arising from improper service or servide procedures If you service this unit you assume responsibility for any injury or...

Page 2: ...ards Institute ANSI National Fire Protection Association NFPA 70 and local state codes In Canada electrical grounding is to be in accordance with the Canadian Electric Code CSA C22 1 uninterrupted unb...

Page 3: ...this document with the unit Carefully read all instruc tions for the installation prior to installing product Make sure each step or procedure is understood and any special consid erations are taken...

Page 4: ...CMK0014 Condensate Kit AVPTC25B14 AVPTC29B14 AVPTC31C14 AVPTC49D14 AVPTC33C14 AVPTC49C14 AVPTC37B14 AVPTC37C14 AVPTC61D14 AVPTC39C14 AVPTC37D14 AVPTC59C14 AVPTC59D14 CONDENSATE KIT TABLE 1 6 3 Downflo...

Page 5: ...follow the specification for the condenser heat pump 7 2 Tubing Preparation All cut ends are to be round burr free and clean Failure to follow this practice increases the chances for refrigerant leak...

Page 6: ...so will result in improper condensate drainage COIL INSTALLATION FOR DOWNFLOW Figure 8 Upper Tie Plate Control Deck Downflow Bracket Center Support Filter Bracket Filter Access Panel ACCESS PANEL CONF...

Page 7: ...e liquid line at the liquid line service valve and 4 6 from the compressor on the suction line Ensure the thermometer makes adequate contact and is insulated for best possible readings Use liquid line...

Page 8: ...above a finished living space to prevent sweating Install a condensate trap to ensure proper drainage NOTE When units are installed above ceilings or in other locationswheredamagefromcondensateoverfl...

Page 9: ...on the ONLY heat kits that are permitted to be used are the HKS series Refer to the air handler unit s Serial and Rating plate or the HKS specification sheets to determine the heat kits compatible wit...

Page 10: ...ll after 20 minutes the system would allow for an additional 20 heat pump run 20 of the 20 minute target is an additional 4 minutes In this case the system would turn on back up electric heat after 24...

Page 11: ...sconnect ALL power before servicing Multiple power sources may be present HIGH VOLTAGE To avoid property damage personal injury or death due to electrical shock this unit MUST have an electrical groun...

Page 12: ...the female connections on the casing down If the motor is not oriented with the connections down water could collect in the motor and may cause premature failure FEMALE CONNECTIONS SIDE VIEW WARN ING...

Page 13: ...outdoor control board power Two stage outdoor units may not behave properly without this 24 VAC transformer Figure 15 3 Download the Cool Cloud HVAC phone application for charging and to configure te...

Page 14: ...stage Heat Pumps 4 Go to the Tonnage Units Menu and select the ton nage value that corresponds to the desired airflow for the outdoor unit See the following table NOTE For the two stage non communicat...

Page 15: ...on 19 Auxiliary Alarm Switch The control is equipped with a 24VAC Aux Alarm to be used for a condensate switch install designated by CON DENSATE IN OUT on the control By default the connected AUX swit...

Page 16: ...nce and increase comfort level Select the desired ramping profile using the Cool Cloud phone application or the push button menus Figure 22 23 Electric Air Cleaner Warning The control is equipped with...

Page 17: ...rom any areas where there may be objectionable odors flammable vapors or products of combustion such ascarbon monoxide CO which may cause serious personal injury or death 25 Regular Maintenance HIGH V...

Page 18: ...e or disconnected wiring connection at circulator motor power leads Open circuit in inductor or loose wiring connection at inductor 3 4 Hp and 1 Hp models only Failed circulator blower motor Tighten o...

Page 19: ...otor if necessary No Air Handler operation Circulator blower motor shuts down for over or under voltage condition Circulator blower motor shuts down due to over temperature condition on power module H...

Page 20: ...stage heat pumps Indoor Airflow for non communicating outdoor units values based on 400CFM per ton default 3 0 Ton Cooling Airflow Trim default 0 Cooling Airflow Profile setting default profile D sho...

Page 21: ...ing the next heat call if the heat pump fails to satisfy the custom target time for this number of consecutive cycles default 20 cycles Menu is enabled if the menu is set to 6 if the addition of low s...

Page 22: ...comm units Compressor Heat Low Stage Comm Units Compressor Heat High Stage Comm Units Electric Heat Single Stage Electric Heat Low Stage Electric Heat High Stage Defrost Single Stage Electric Heat non...

Page 23: ...avigation and Selection Instructions Using Phone Application over Bluetooth Network 1 Connect to the air handler instructions provided by phone during connection process 2 Select desired settings menu...

Page 24: ...24 29 Wiring Diagrams HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH WARNING...

Page 25: ...ng diagram on the unit for the most up to date wiring HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJUR...

Page 26: ...maintained filter will keep the indoor coil of your comfort system clean A dirty coil could cause poor operation and or severe equipment damage Your air filter or filters could be located in your fur...

Page 27: ...27 THIS PAGE WAS LEFT BLANK INTENTIONALLY...

Page 28: ...u purchased to be directed to the feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a...

Reviews: