background image

26

 

BEFORE YOU CALL YOUR SERVICER

•  Check the thermostat 

to confirm that it is properly set.

•  Wait 15 minutes

. Some devices in the outdoor unit or 

in programmable thermostats will prevent compressor 

operation for awhile, and then reset automatically. Also, 

some power companies will install devices which shut off 

air conditioners for several minutes on hot days. If you wait 

several minutes, the unit may begin operation on its own.

• 

Check the electrical panel  for tripped circuit breakers  or 

failed fuses. Reset the circuit breakers or replace fuses as necessary. 

•  Check the disconnect switch

 near the indoor furnace or blower to confirm that it is closed.

• 

Check for obstructions on the outdoor unit . Confirm that it has not been covered on the sides or the top. Remove any obstruction 

that can be safely  removed. If  the unit is covered with dirt or debris, call a qualified servicer to clean it.

• 

Check for blockage of the indoor air inlets and outlets. Confirm that they are open and have not been blocked by objects (rugs, 

curtains or furniture). 

• 

Check the filter. If it is dirty, clean or replace it.

• 

Listen for any unusual noise(s), other than normal operating noise, that might be coming from the outdoor unit.   If you hear 

unusual noise(s) coming from the unit, call a qualified servicer.

 

AIR HANDLER

AIR HANDLER HOMEOWNER’S

 

ROUTINE MAINTENANCE RECOMMENDATIONS

We strongly recommend a bi-annual maintenance checkup be performed before the heating and cooling seasons begin by a 

qualified servicer

.

REPLACE OR CLEAN FILTER

IMPORTANT NOTE: 

Never operate unit without a filter installed as dust and lint will build up on internal parts resulting in loss of effi

-

ciency, equipment damage and possible fire. 
An indoor air filter must be used with your comfort system. A properly maintained filter will keep the indoor coil of your comfort system 

clean. A dirty coil could cause poor operation and/or severe equipment damage.
Your air filter or filters could be located in your furnace, in a blower unit, or in “filter grilles” in your ceiling or walls. The installer of your 

air conditioner or heat pump can tell you where your filter(s) are, and how to clean or replace them.
Check your filter(s) at least once a month. When they are dirty, replace or clean as required. Disposable type filters should be replaced. 

Reusable type filters may be cleaned.
You may want to ask your dealer about high efficiency filters. High efficiency filters are available in both electronic and non-electronic 

types. These filters can do a better job of catching small airborne particles.

MOTOR

S

Indoor and outdoor fan motors are permanently lubricated and 

do not require additional oiling.

ALUMINUM INDOOR COIL CLEANING

(QUALIFIED SERVICER ONLY)

This unit is equipped with an aluminum tube evaporator coil. The 

safest way to clean the evaporator coil is to simply flush the coil 

with water. This cleaning practice remains as the recommended cleaning method for both copper tube and aluminum tube residential 

evaporator coils.
It has been determined that many coil cleaners and drain pan tablets contain corrosive chemicals that can be harmful to aluminum 

tube and fin evaporator coils. Even a one-time application of these corrosive chemicals can cause premature aluminum evaporator 

coil failure. Any cleaners that contain corrosive chemicals including, but not limited to, chlorine and hydroxides, should not be used.
An alternate cleaning method is to use one of the products listed in TP-109* to clean the coils. The cleaners listed are the only agents 

deemed safe and approved for use to clean round tube aluminum coils. TP-109 is also available on the web site in Partner Link > Service 

Toolkit.
NOTE: Ensure coils are rinsed well after use of any chemical cleaners.

Summary of Contents for Amana AVPTC 14 Series

Page 1: ...nt The manufac turer will not be responsible for any injury or property dam age arising from improper service or servide procedures If you service this unit you assume responsibility for any injury or...

Page 2: ...ards Institute ANSI National Fire Protection Association NFPA 70 and local state codes In Canada electrical grounding is to be in accordance with the Canadian Electric Code CSA C22 1 uninterrupted unb...

Page 3: ...this document with the unit Carefully read all instruc tions for the installation prior to installing product Make sure each step or procedure is understood and any special consid erations are taken...

Page 4: ...CMK0014 Condensate Kit AVPTC25B14 AVPTC29B14 AVPTC31C14 AVPTC49D14 AVPTC33C14 AVPTC49C14 AVPTC37B14 AVPTC37C14 AVPTC61D14 AVPTC39C14 AVPTC37D14 AVPTC59C14 AVPTC59D14 CONDENSATE KIT TABLE 1 6 3 Downflo...

Page 5: ...follow the specification for the condenser heat pump 7 2 Tubing Preparation All cut ends are to be round burr free and clean Failure to follow this practice increases the chances for refrigerant leak...

Page 6: ...so will result in improper condensate drainage COIL INSTALLATION FOR DOWNFLOW Figure 8 Upper Tie Plate Control Deck Downflow Bracket Center Support Filter Bracket Filter Access Panel ACCESS PANEL CONF...

Page 7: ...e liquid line at the liquid line service valve and 4 6 from the compressor on the suction line Ensure the thermometer makes adequate contact and is insulated for best possible readings Use liquid line...

Page 8: ...above a finished living space to prevent sweating Install a condensate trap to ensure proper drainage NOTE When units are installed above ceilings or in other locationswheredamagefromcondensateoverfl...

Page 9: ...on the ONLY heat kits that are permitted to be used are the HKS series Refer to the air handler unit s Serial and Rating plate or the HKS specification sheets to determine the heat kits compatible wit...

Page 10: ...ll after 20 minutes the system would allow for an additional 20 heat pump run 20 of the 20 minute target is an additional 4 minutes In this case the system would turn on back up electric heat after 24...

Page 11: ...sconnect ALL power before servicing Multiple power sources may be present HIGH VOLTAGE To avoid property damage personal injury or death due to electrical shock this unit MUST have an electrical groun...

Page 12: ...the female connections on the casing down If the motor is not oriented with the connections down water could collect in the motor and may cause premature failure FEMALE CONNECTIONS SIDE VIEW WARN ING...

Page 13: ...outdoor control board power Two stage outdoor units may not behave properly without this 24 VAC transformer Figure 15 3 Download the Cool Cloud HVAC phone application for charging and to configure te...

Page 14: ...stage Heat Pumps 4 Go to the Tonnage Units Menu and select the ton nage value that corresponds to the desired airflow for the outdoor unit See the following table NOTE For the two stage non communicat...

Page 15: ...on 19 Auxiliary Alarm Switch The control is equipped with a 24VAC Aux Alarm to be used for a condensate switch install designated by CON DENSATE IN OUT on the control By default the connected AUX swit...

Page 16: ...nce and increase comfort level Select the desired ramping profile using the Cool Cloud phone application or the push button menus Figure 22 23 Electric Air Cleaner Warning The control is equipped with...

Page 17: ...rom any areas where there may be objectionable odors flammable vapors or products of combustion such ascarbon monoxide CO which may cause serious personal injury or death 25 Regular Maintenance HIGH V...

Page 18: ...e or disconnected wiring connection at circulator motor power leads Open circuit in inductor or loose wiring connection at inductor 3 4 Hp and 1 Hp models only Failed circulator blower motor Tighten o...

Page 19: ...otor if necessary No Air Handler operation Circulator blower motor shuts down for over or under voltage condition Circulator blower motor shuts down due to over temperature condition on power module H...

Page 20: ...stage heat pumps Indoor Airflow for non communicating outdoor units values based on 400CFM per ton default 3 0 Ton Cooling Airflow Trim default 0 Cooling Airflow Profile setting default profile D sho...

Page 21: ...ing the next heat call if the heat pump fails to satisfy the custom target time for this number of consecutive cycles default 20 cycles Menu is enabled if the menu is set to 6 if the addition of low s...

Page 22: ...comm units Compressor Heat Low Stage Comm Units Compressor Heat High Stage Comm Units Electric Heat Single Stage Electric Heat Low Stage Electric Heat High Stage Defrost Single Stage Electric Heat non...

Page 23: ...avigation and Selection Instructions Using Phone Application over Bluetooth Network 1 Connect to the air handler instructions provided by phone during connection process 2 Select desired settings menu...

Page 24: ...24 29 Wiring Diagrams HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJURY OR DEATH WARNING...

Page 25: ...ng diagram on the unit for the most up to date wiring HIGH VOLTAGE DISCONNECT ALL POWER BEFORE SERVICING MULTIPLE POWER SOURCES MAY BE PRESENT FAILURE TO DO SO MAY CAUSE PROPERTY DAMAGE PERSONAL INJUR...

Page 26: ...maintained filter will keep the indoor coil of your comfort system clean A dirty coil could cause poor operation and or severe equipment damage Your air filter or filters could be located in your fur...

Page 27: ...27 THIS PAGE WAS LEFT BLANK INTENTIONALLY...

Page 28: ...u purchased to be directed to the feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a...

Reviews: