background image

 

 

 

 

 

 

February, 2019 

              eMAX-MR62e-Man 

Page 8 of 16

  

8.  Input Circuit Wiring: 

The eMAX-MR62e provided Six (6) inputs that are typically used to monitor door position, request to 
exit,  or  alarm  contacts.    Input  circuits  can  be  configured  as  unsupervised  or  supervised.    When 
unsupervised, reporting consists of only the open or closed states.   

When configured as supervised, the input circuit will report not only open and closed, but also open 
circuit, shorted, grounded*, and foreign voltage*.  A supervised input circuit requires two resistors be 
added  to  the  circuit  to  facilitate  proper  reporting.    The  standard  supervised  circuit  requires  dual  1K 
Ohm,  1%  resistors  and  should  be  located  as  close  to  the  sensor  as  possible.    Custom  end  of  line 
(EOL) resistances may be configured via the host software. 

NOTE:  Grounded and foreign voltage states are not a requirement of UL 294 and therefore not 
verified by UL. 

The input circuit wiring configurations shown are supported but may not be typical:  

1K,1%

1K,1%

1K,1%

1K,1%

Standard Supervised Circuit,
Normally Closed Contact

Standard Supervised Circuit,
Normally Open Contact

Unsupervised Circuit,
Normally Open Contact

Unsupervised Circuit,
Normally Closed Contact

TB2

IN4

IN2

IN3

1

IN1

TB1

1

}

 

9.  Relay Circuit Wiring: 

The eMAX-MR62e includes four (4) relays with Form-C contacts (dry) that provide for controlling door 
lock mechanisms or alarm signaling.  Each relay contact is rated at 

2A @ 30Vdc resistive.

  When 

controlling the delivery of power to the door strike, the Normally Open and Common poles are 
typically used.  When momentarily removing power to unlock the door, as with a mag lock, the 
Normally Closed and Common poles are typically used.  Check with local building codes for proper 
egress door installation.   

Door lock mechanisms can generate feedback to the relay circuit that can cause damage and 
premature failure of the relay.  For this reason, it is recommended that a diode be used to protect the 
relay.  Wire should be of sufficient gauge to avoid voltage loss.

 

 

 

It is possible for the eMAX-MR62e to provide power for a 12 Vdc door strike providing the maximum 
current is not exceeded.  See specification section.

  

 

TB5

 

 
DIODE SELECTION:

 

 
DIODE Current Rating > 1 X STRIKE CURRENT 
DIODE Break Down Voltage: 4X STRIKE VOLTAGE 
FOR 12VDC or 24VDC STRIKE, DIODE 1N4002 
(100V /1A) TYPICAL 

Summary of Contents for eMAX-MR62e

Page 1: ...ER INTERFACE MODULE Installation Guide and Specifications This device complies with FCC Part 15 Class A Specifications The device meets CE Specifications and is RoHS Certified This device is UL 294 Recognized February 2019 ...

Page 2: ...Erase Configuration Memory 6 5 Input Power 7 6 Communication Wiring 7 7 OSDP Reader Wiring 7 8 Input Circuit Wiring 8 9 Relay Circuit Wiring 8 10 Status LEDs 9 11 IT Security 9 12 Specifications 10 13 Additional Mounting Information 11 14 Warranty and Liability 12 Appendix A Configuring the eMAX MR62 Network 13 Change History Original Document Original February 2019 ...

Page 3: ...ial 2 wire RS 485 data communication port is available and can accommodate up to four OSDP readers that are controlling two 2 portals In Out paired reader mode Four Form C Relay Outputs may be used for door strike control or alarm signaling The relay contacts are rated at 2 A 30 Vdc resistive and are in a dry contact configuration Six inputs are provided that may be used for monitoring the door co...

Page 4: ...VO GND TR TR J3 J4 J1 10519 0000 F REV A 7 6 5 4 3 2 1 2 3 4 1 S1 ON V INPUTS RELAYS J5 INPUT POWER SELECT 12 Vdc IN AUX POWER OUTPUT 2 55 64 77 2 55 64 77 5 4 137 16 STATUS LEDs 2 35 59 69 2 75 69 85 2 5 08 S1 DIP SWITCH J3 TAMPER SWITCH TO OSDP READERS LINK GREEN SPEED YELLOW J4 TIA 485 TERMINATION JUMPER Ø 125 3 18 6 PLACES EARTH GROUND J1 ETHERNET RJ45 CONNECTOR eMAX MR62e Layout ...

Page 5: ... Normally Open Contact TB5 2 1 C Relay K1 Common Contact TB5 3 NC Relay K1 Normally Closed Contact TB5 4 NO Relay K2 Normally Open Contact TB5 5 2 C Relay K2 Common Contact TB5 6 NC Relay K2 Normally Closed Contact TB6 1 NO Relay K3 Normally Open Contact TB6 2 3 C Relay K3 Common Contact TB6 3 NC Relay K3 Normally Closed Contact TB6 4 NO Relay K4 Normally Open Contact TB6 5 4 C Relay K4 Common Con...

Page 6: ...OFF Use OEM default communication parameters Contact system manufacture for details See Bulk Erase section below ON ON OFF OFF Bulk Erase prompt mode at power up See Bulk Erase below All other switch settings are unassigned and reserved for future use X don t care Factory Default Communication Parameters Network static IP address 192 168 0 251 Subnet Mask 255 255 255 0 Default Gateway 192 168 0 1 ...

Page 7: ...ut is limited to 5 A maximum The OSDP reader wiring diagram below shows the use of a 2 pair cable for data and power If this cable cannot support the voltage current requirements a 1 pair cable of sufficient gauge must be used for power See specification section The RS 485 termination jumper J4 is only installed if the eMAX MR62e is at one end of the communication bus Only devices at each end of t...

Page 8: ...dard Supervised Circuit Normally Open Contact Unsupervised Circuit Normally Open Contact Unsupervised Circuit Normally Closed Contact TB2 IN4 IN2 IN3 1 IN1 TB1 1 9 Relay Circuit Wiring The eMAX MR62e includes four 4 relays with Form C contacts dry that provide for controlling door lock mechanisms or alarm signaling Each relay contact is rated at 2A 30Vdc resistive When controlling the delivery of ...

Page 9: ...nk ON Good Link Flashing Ethernet Activity Note 2 If this input is defined every three seconds the LED is pulsed to its opposite state for 0 1 second otherwise the LED is off 11 IT Security When installing When installing the eMAX MR62e it is important to ensure that it is done in a secure manner Upon installation the user accounts to the web configuration page should be created with secure passwo...

Page 10: ... 2 A 30 Vdc Inputs Six unsupervised supervised End of Line resistors 1k 1k ohm 1 watt standard Reader Interface Power 12 Vdc 5 A maximum RVO TB7 4 Communication 2 Wire RS 485 OSDP protocol four devices maximum Cable Requirements Communication Ethernet Category 5 minimum External Input Power 1 twisted pair 18 AWG if required Alarm Inputs 1 twisted pair per input 30 ohm maximum Relay Outputs As requ...

Page 11: ...e Levels Feature Level Standby Power I Endurance IV Line Security I Destructive Attack I 13 Additional Mounting information Sources for the optional items shown below 3 gang stainless steel blank cover Available from Leviton part number 84033 40 Graybar part number 88158404 Magnetic switch set G R I part number 505 Side View FIELD WIRING MR51e WITH INCLUDED MOUNTING PLATE TO ETHERNET NETWORK OPTIO...

Page 12: ...ds nor does it authorize any agent or representative to make any other warranties implied or otherwise and expressly excludes and disclaims all implied warranties of merchantability or fitness for a particular purpose Returned units are repaired or replaced from a stock of reconditioned units Returns must be accompanied by a return authorization number RMA obtained from customer service and prepai...

Page 13: ..._ _____ Gateway IP _____ ______ ______ _____ Connecting to the eMAX MR62e local controller 1 Connect the device to a computer using a standard network cable 2 Set the computer s IP to a Statis IP Address of 192 168 0 10 3 At the eMAX MR62e Module be sure to turn dipswitch 1 to the ON position This enables the use of the DEFAULT Login credentials and will time out in 5 minutes 4 Connect to the devi...

Page 14: ...rname admin and password password The following message will appear if you FAILED to turn Switch 1 to ON or if 5 minutes have elapsed since turning switch 1 to ON If you entered the incorrect UserName or Password you will see the Login Screen display Login Failed and you should click on Retry ...

Page 15: ...ayed Click on the Network page to configure the IP parameters Click on the Use Static IP configuration circle to enable the configuration and use of the Static IP addressing Configure the required IP Address Subnet Mask Default Gateway as applicable for the eMAX MR62e To SAVE Click on Accept button then select the Apply Settings button ...

Page 16: ...then click on the Apply and Reboot box to proceed You should see a message that says Board is rebooting You can then logout Remember that you should ALWAYS create a USER Account When a new user is added it disables the default admin user It is strongly recommended that a new user account be added during this configuration process Browse to the Users link and add a user If the new user details are ...

Reviews: