TEST:
Verify that the motor is getting power.
PROCEDURE:
Connect “+” test probe on brown wire.
Connect “-” test probe to ground, e.g. valve
body or appliance chassis.
Push UP FLAME button on the handset.
RESULT:
The reading should be 5-6 Volts and motor
should move. If there is no motor movement,
the motor may be damaged. Replace motor
(motor kits available).
Troubleshooting the GV60
Verifying Motor Operation
Connect “+” test probe on the brown wire.