17
Adjusting the Pressure Regulator
(for Vented Units Only)
Remove small plug to access
the adjustment screw.
Turn the adjustment screw to set required burner pressure
(high fire). Pressure is increased by turning clockwise or
decreased by turning counterclockwise. This adjustment is
required for fuel conversions.
Control Valve Components