TEST:
Check batteries for proper voltage.
PROCEDURE:
Connect “+” test probe on
last pin.
Connect “-” test probe to ground,
e.g. valve body or appliance chassis.
RESULT:
The reading should be 5 – 6VDC.
Troubleshooting the GV60
Testing the Batteries
© 2013, Maxitrol Company