Crossfire LCD - Installation and Programming Manual

 

8

 

Version 1.5  | Revision B | May 2012

 

 

 

Startup

 

 

During the panel startup all 

Led’s

 light up for a few seconds. The startup sequence ends with a BEEP tone. 

Confirming zones and auxiliary 24V output have a cool off period of 4 seconds.

 

 

 

Power

 

General Status 

LED’s

 

If lit, the panel is working. If it is off the system is not working.

 

Alarm 

 

Alarm has been verif ed in one or more zones. See the indicator led´s to identify which zone(s) is(are) in 
recondition. As the alarm led is lit, also the corresponding 

led’s

 of the zone in alarm light up.

 

 

Se um detector, ou botoneira entrar em alarme, iluminar-se-á o  led geral de alarme e a correspondente indicação 
surge no display.

 

 

Fault

 

There

s a fault on the system, zones, power supply or other. If there

s a fault on a zone circuit, the corresponding 

fault led also lights up.

 

 

Test

 

If this led is lit, means that one or more zones are in test mode. The fault led of specif c zone also lits.

 

Omit  

 

The system has one or more zones ommited. The siren outputs can also be omitted.

 

 

Delay

 

If the delay LED is lit, the system has the pre-alarm timer activated (Day mode).

 

 

 

Status LED

 

 

Micro

 

When lit, the microprocessor has encountered an error.

 

Shutdown the system completely and startup again. If the problem persists, contact your dealer.

 

 

 

Specific Indications LCD Display

 

 

 

Earth Fault

 

Ground connection is missing.

 

 
 

 

Power/Battery Fault

 

Fixed light indicates main power supply fault - 230V AC missing. 
Flashing indicates secondary power supply fault - low batteries.

 

 
 

 

Aux Fault

 

When lit indicates that the 24V Aux is in fault, by short-circuit 
or overload.

 

 

Fault Siren Outputs

 

Indicates that the siren output is at fault  for short circuit, open 
circuit or overload.It indicated the number of acoustic output that 
is malfunctioning.

 

Earth 
Fault

 

AC Power 
Fault

 

Battery 
Fault

 

Aux 
Fault

 

Sounder 1 
Fault

 

Summary of Contents for CROSSFIRE LCD

Page 1: ...CROSSFIRE LCD INSTALLATION AND PROGRAMMING MANUAL Version 1 5 Revision B May de 2012...

Page 2: ...15 Reset 16 Specifications 16 Installation Record 17 Warranty Policy Certificate 18 Wiring Diagram 19 Crossfire control panels are manufactured accordingly to the European directives These control pa...

Page 3: ...bill conditions of the package and contact name 3 If you return the panel please return it in the original package In your control panel package you must check for the following items Notes for Insta...

Page 4: ...el and drill a hole in the wall in point A Place the panel in point A and mark the remaining B marks Remove the panel and drill in the B points Finally place the panel and screw it to the wall 3 Do th...

Page 5: ...rogramming for further information Both Outputs are limited to 24V DC 1A Repeater output A repeater panel can be connected to this panel It indicates alarm common fault and common disable Crossfi re p...

Page 6: ...lations Detectors wiring Detectors are connected directly to the zone terminals It is also required to include a EOL resistor in the last device If is not fi tted a fault will be indicated in the zone...

Page 7: ...nal blocks of the panel Due to high current consumption the panel inverts the ter minals polarity in standby So it is required to plug a diode in the positive terminal of the terminal block of the sir...

Page 8: ...ng fault led also lights up Test If this led is lit means that one or more zones are in test mode The fault led of specif c zone also lits Omit The system has one or more zones ommited The siren outpu...

Page 9: ...te that the LED Keyboard is illuminated and in the display appears the message Active Keyboard In this mode you can access all the features of level 2 The keyboard is active for 30 seconds if not more...

Page 10: ...u press the Ent Esc key and use the cursor keys Left and Right to check the status of the alarm circuits In normal mode the LCD will display the message No Active Fault MENU 4 Disable Zones he Menu Di...

Page 11: ...trol Panel or when navigating the menus If you want to temporarily disable the buzzer f ex during a consultation event or a programming you must press the button for 3 seconds the message Buzzer Silen...

Page 12: ...mming Mode 3 Insert the password according to the scheme using the cursor keys After introduction of 4 digits you should hear a double BIP in case of entry the correct code In this case the LED Keyboa...

Page 13: ...event This option is especially suitable for use in zones of false alarms high risk or for integration with auto matic fire extinguishing The pairs of zones are set as described in Table 1 below Tabl...

Page 14: ...2 3 Sounder 2 O The Menu Sounder 1 lets you set the timer of ringing sirens connected to the Sounder 2 output signal To enter the menu you should press Ent Esc This time is configurable from 0 second...

Page 15: ...rows of information normally intended to a Name and Phone Number MENU 6 2 Info Enable The Menu Enable Info lets you define if the Control Panel shows the programmed information on the menu 6 1 MENU 7...

Page 16: ...on 300 mA Resettable Fuse Aux Output protection 300 mA Resettable Fuse Max current draw per zone 57 mA number of detectors per zone varies according to their power consumption Baterie time AC Power mi...

Page 17: ...d this info to your client or peel off this page and keep it on a safe place INSTALLER DETAILS TECHNICIAN INSTALATION DATE ZONE NAMES CABLING IDENTIFICATION ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 Z...

Page 18: ...r implied of merchantability or fitness of the products for a par ticular purpose or otherwise which extend beyond the description on the face hereof This limited Warranty Certificate is the Purchaser...

Page 19: ...19 Version 1 5 Revision B May 2012 Crossfire LCD Installation and Programming Manual Wiring Diagram CROSSFIRE LCD...

Page 20: ...Crossfire LCD Installation and Programming Manual NOTES 20 Version 1 5 I Revision B I May 2012...

Page 21: ......

Reviews: