Crossfire LCD - Installation and Programming Manual

 

5

 

Version 1.5  | Revision B | May 2012

 

 

 

General 

Inputs

 

Zones

 

The panel has 4 or 8 input zones of conventional detection, up to 30 detectors per zone, fully 
monitored.

 

 

Outputs

 

 

Siren outputs

 

The panel has 2 independent siren outputs fully monitored. These outputs are fully programmable. 
Each output can be activated by one or more zones and the delay is also confi gurable. The load of 
both outputs is limited to 24V DC 300 mA each.

 

 

Relay outputs

 

There are available 2 relay outputs. One for alarm and other is for fault. You can confi gure which

 

alarms and faults activate the relays. Please refer to the section 

“Programming”

 for further information. 

Both Outputs are limited to 24V DC 1A.

 

 

Repeater output

 

A repeater panel can be connected to this panel. It indicates alarm, common fault and common 
disable. Crossfi re panels are fully compatible with GST 116RP repeater panels.

 

 

24V auxiliary output

 

The panel has a 24V output (fully supervised) and can be confi gured as resettable or not. 
This output is limited to 300 mA.

 

 

Access levels

 

 

This system has 3 access levels with different functions:

 

 

Level 1

 

The user has basic permission to the functions. (Acnowledge alarm and mute buzzer).

 

 

Level 2

 

The user has access to all functions. To 

change access level, press for 3 sec. the “ACCESS” button until

 

double bip sounds.

 

 

Level 3

 

Engineering Level. The user has access to all functions and ability to re-confi gure the system. The access 
to the Level 3 is protected by a 4 digit password.

 

Summary of Contents for CROSSFIRE LCD

Page 1: ...CROSSFIRE LCD INSTALLATION AND PROGRAMMING MANUAL Version 1 5 Revision B May de 2012...

Page 2: ...15 Reset 16 Specifications 16 Installation Record 17 Warranty Policy Certificate 18 Wiring Diagram 19 Crossfire control panels are manufactured accordingly to the European directives These control pa...

Page 3: ...bill conditions of the package and contact name 3 If you return the panel please return it in the original package In your control panel package you must check for the following items Notes for Insta...

Page 4: ...el and drill a hole in the wall in point A Place the panel in point A and mark the remaining B marks Remove the panel and drill in the B points Finally place the panel and screw it to the wall 3 Do th...

Page 5: ...rogramming for further information Both Outputs are limited to 24V DC 1A Repeater output A repeater panel can be connected to this panel It indicates alarm common fault and common disable Crossfi re p...

Page 6: ...lations Detectors wiring Detectors are connected directly to the zone terminals It is also required to include a EOL resistor in the last device If is not fi tted a fault will be indicated in the zone...

Page 7: ...nal blocks of the panel Due to high current consumption the panel inverts the ter minals polarity in standby So it is required to plug a diode in the positive terminal of the terminal block of the sir...

Page 8: ...ng fault led also lights up Test If this led is lit means that one or more zones are in test mode The fault led of specif c zone also lits Omit The system has one or more zones ommited The siren outpu...

Page 9: ...te that the LED Keyboard is illuminated and in the display appears the message Active Keyboard In this mode you can access all the features of level 2 The keyboard is active for 30 seconds if not more...

Page 10: ...u press the Ent Esc key and use the cursor keys Left and Right to check the status of the alarm circuits In normal mode the LCD will display the message No Active Fault MENU 4 Disable Zones he Menu Di...

Page 11: ...trol Panel or when navigating the menus If you want to temporarily disable the buzzer f ex during a consultation event or a programming you must press the button for 3 seconds the message Buzzer Silen...

Page 12: ...mming Mode 3 Insert the password according to the scheme using the cursor keys After introduction of 4 digits you should hear a double BIP in case of entry the correct code In this case the LED Keyboa...

Page 13: ...event This option is especially suitable for use in zones of false alarms high risk or for integration with auto matic fire extinguishing The pairs of zones are set as described in Table 1 below Tabl...

Page 14: ...2 3 Sounder 2 O The Menu Sounder 1 lets you set the timer of ringing sirens connected to the Sounder 2 output signal To enter the menu you should press Ent Esc This time is configurable from 0 second...

Page 15: ...rows of information normally intended to a Name and Phone Number MENU 6 2 Info Enable The Menu Enable Info lets you define if the Control Panel shows the programmed information on the menu 6 1 MENU 7...

Page 16: ...on 300 mA Resettable Fuse Aux Output protection 300 mA Resettable Fuse Max current draw per zone 57 mA number of detectors per zone varies according to their power consumption Baterie time AC Power mi...

Page 17: ...d this info to your client or peel off this page and keep it on a safe place INSTALLER DETAILS TECHNICIAN INSTALATION DATE ZONE NAMES CABLING IDENTIFICATION ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 Z...

Page 18: ...r implied of merchantability or fitness of the products for a par ticular purpose or otherwise which extend beyond the description on the face hereof This limited Warranty Certificate is the Purchaser...

Page 19: ...19 Version 1 5 Revision B May 2012 Crossfire LCD Installation and Programming Manual Wiring Diagram CROSSFIRE LCD...

Page 20: ...Crossfire LCD Installation and Programming Manual NOTES 20 Version 1 5 I Revision B I May 2012...

Page 21: ......

Reviews: