i
‐
SHWAK
V4
Inverter
air/water
chillers
and
heat
pumps
with
floor
‐
standing
and
remote
condensing
units
41
15.2
MAXIMUM
POWER
CONSUMPTION/MAXIMUM
INPUT
CURRENT
OF
THE
INDOOR
UNITS
14
‐
16
Model
Electric
heater
MAR1
14
‐
16
MAR3
14
‐
16
MARS1
14
‐
16
MARS3
14
‐
16
NOT
PRESENT
0,19
kW
1,51
A
0,19
kW
1,51
A
0,27
kW
2,11
A
0,27
kW
2,11
A
DHW
heater
of
1,2
kW
1,45
kW
6,99
A
1,53
kW
7,59
A
DHW
heater
of
2
kW
2,19
kW
10,20
A
2,19
kW
4,40
A
2,27
kW
10,80
A
2,27
kW
5,00
A
DHW
heater
of
3
kW
3,19
kW
14,55
A
3,19
kW
5,84
A
3,27
kW
15,15
A
3,27
kW
6,44
A
DHW
heater
of
4,5
kW
4,69
kW
21,07
A
4,69
kW
8,01
A
4,77
kW
21,67
A
4,77
kW
8,61
A
DHW
heater
of
3+3
kW
6,19
kW
10,18
A
DHW
heater
of
4,5+3
kW
7,69
kW
12,35
A
DHW
heater
of
4,5+4,5
kW
9,19
kW
14,51
A
Power
supply
230V/1/50Hz
400V/3P+N+T/50Hz
230V/1/50Hz
400V/3P+N+T/50Hz
Model
Eectric
heater
MARP1
14
‐
16
MARP3
14
‐
16
MARPS1
14
‐
16
MARPS3
14
‐
16
NOT
PRESENT
0,19
kW
1,51
A
0,19
kW
1,51
A
0,27
kW
2,11
A
0,27
kW
2,11
A
DHW
electric
heater
of
1,2
kW
1,45
kW
6,99
A
1,53
kW
7,59
A
Plant
side
electric
heater
of
1,2
kW
1,45
kW
6,99
A
1,53
kW
7,59
A
DHW
E
‐
heater
of
1,2
kW
and
plant
E
‐
heater
of
1,2
kW
2,71
kW
12,46
A
2,79
kW
13,06
A
DHW
E
‐
heater
of
2
kW
2,19
kW
10,20
A
2,19
kW
4,40
A
2,27
kW
10,80
A
2,27
kW
5,00
A
DHW
E
‐
heater
of
3
kW
3,19
kW
14,55
A
3,19
kW
5,84
A
3,27
kW
15,15
A
3,27
kW
6,44
A
DHW
E
‐
heater
of
4,5kW
4,69
kW
21,07
A
4,69
kW
8,01
A
4,77
kW
21,67
A
4,77
kW
8,61
A
Plant
side
E
‐
heater
of
2
kW
2,19
kW
10,20
A
2,19
kW
4,40
A
2,27
kW
10,80
A
2,27
kW
5,00
A
Plant
side
E
‐
heater
of
3
kW
3,19
kW
14,55
A
3,19
kW
5,84
A
3,27
kW
15,15
A
3,27
kW
6,44
A
Plant
side
E
‐
heater
of
4,5kW
4,69
kW
21,07
A
4,69
kW
8,01
A
4,77
kW
21,67
A
4,77
kW
8,61
A
DHW
E
‐
heater
2kW
and
Plant
side
E
‐
heater
2kW
4,19
kW
18,90
A
4,19
kW
7,29
A
4,27
kW
19,50
A
4,27
kW
7,89
A
DHW
E
‐
heater
2kW
and
plant
side
E
‐
heater
3kW
5,19
kW
8,73
A
5,27
kW
9,33
A
DHW
E
‐
heater
2kW
and
plant
side
E
‐
heater
4,5kW
6,69
kW
10,90
A
6,77
kW
11,50
A
DHW
E
‐
heater
3kW
and
plant
side
E
‐
heater
2kW
5,19
kW
8,73
A
5,27
kW
9,33
A
DHW
E
‐
heater
3kW
and
plant
side
E
‐
heater
3kW
6,19
kW
10,18
A
6,27
kW
10,78
A
DHW
E
‐
heater
3kW
and
plant
side
E
‐
heater
4,5kW
7,69
kW
12,35
A
7,77
kW
12,95
A
DHW
E
‐
heater
of
3+3kW
6,19
kW
10,18
A
DHW
E
‐
heaters
3+3kW
and
plant
E
‐
heater
side
2kW
8,19
kW
13,07
A
DHW
E
‐
heaters
3+3kW
and
plant
side
E
‐
heater
3kW
9,19
kW
14,51
A
DHW
E
‐
heater
4,5kW
and
plant
side
E
‐
heater
2kW
6,69
kW
10,90
A
6,77
kW
11,50
A
DHW
E
‐
heater
4,5kW
and
plant
side
E
‐
heater
3kW
7,69
kW
12,35
A
7,77
kW
12,95
A
DHW
E
‐
heater
4,5kW
and
plant
side
E
‐
heater
4,5kW
9,19
kW
14,51
A
9,27
kW
15,11
A
DHW
E
‐
heaters
of
4,5+3kW
7,69
kW
12,35
A
DHW
E
‐
heaters
of
4,5+4,5kW
9,19
kW
14,51
A
Power
supply
230V/1/50Hz
400V/3P+N+T/50Hz
230V/1/50Hz
400V/3P+N+T/50Hz
The
electrical
data
of
the
outdoor
and
indoor
units
are
set
to
scale
the
size
of
the
circuit
breakers
and
power
supply
cables.
You
have
to
add
the
input
power
of
the
outdoor
unit
(see
Paragraph
14.2)
and
indoor
unit
taking
into
account
the
power
of
the
installed
electric
heater