KK-642.014 Rev.No:1 01.08.12 Page | 17
·By “2mA detection” function, in case of decreasing current which comes from detector or converter card, the
system response is determined. In this condition system may give fault warning, notification warning or
cannot be counted as a warning status.
·By “Warm-up delay” function, it is told to the control panel that, in the start –up session, the signals coming
from the detectors cannot be evaluated by the panel. This is because detector will have more stable values
after warm-up time. Hence they will measure accurate values.
After adjusting these settings press
“Down (-)” button to see the upcoming 3
rd
screen.
*** CHANNELS
***
Channel 1
configuration
> Fire Reset Time : Alarm
L1 Direction : Alarm L1
On Threshold: Alarm L1
Off Threshold:
------------------------------------------------------------
Enter
– OK
Exit
– Pre Menu
·“Fire Reset Time”: Function that during fire alarm condition, when pressed to “Reset”, the determination of
interruption time of the energy of the channel which detector connected to that channel is adjusted.
· “Low alarm direction”: Function that estimates the sensitivity of low alarm warning as increasing or
decreasing level of the gas in the medium.
· “Low alarm opening level” Function that determines the threshold of gas level of the low alarm warning
value.
·“Low alarm closing level”: Function that determines the gas level, when panel pass from low alarm to
warning to normal status.
After adjusting these settings press
“Down (-)” button to see the upcoming 4
th
screen.
*** CHANNELS
***
Channel 1
configuration
> 2
nd
level Alarm Direction:
2
nd
level Alarm Input Value:
------------------------------------------------------------
Enter
– OK
Exit
– Pre Menu
·“High alarm direction” Function that estimates the sensitivity of high alarm warning as increasing or
decreasing level of the gas in the medium.
·“High alarm opening level” Function that determines the threshold of gas level of the high alarm warning
value.