1. INTRODUCTION

 

MaviGard  MG-400  is  a  4  channel,  24  V  DC  operating  voltage  combined  gas  and  fire  alarm  control  panel. 

Each channel can host 1 gas detector or 20 fire detectors with unlimited number of manual call points. Panel 
power supply unit has an automatic battery charger and charging control circuit. Alarm and fault conditions are 
showed  on  8x40  character backlight  LCD.  Panel  sounder outputs  are  supervised for  open  and  short  circuit 
conditions. The  panel  has  built-in  buzzer. Settings to  the  panel are  made  by  use  of  navigation  buttons and 
menu. The panel is microprocessor-controlled. Channels can be inhibited, sounder outputs and relays can be 
tested, 
Any  channel  can  be  disabled,  sounder  outputs  and  relays  can  be  test.  Gas  detectors  can  be  zeroed  and 
calibrated. These features are also told in the section of 

“Panel Menu” in detail. The panel is equipped with 2 

units  of  24  V  DC  500  mA  sounder  outputs  and  has  4  voltage-free changeover  contact  relay  outputs  (Low 
alarm  relay,  High  alarm  relay,  over-range  relay  and  fault  relay.  Panel  also  has  24  V  DC  500  mA  auxiliary 
power supply output. By use of remote control inputs, alarm can be silenced and all the channels in the panel 
can be disabled. 

 

Producer-

manufacturer or importer firms’ title, address, and telephone number 

Manufacturer Firm: 

MAVILI ELEKTRONIK TICARET VE SANAYI A.S. 
SERIFALI MAHALLESI, KUTUP SOKAK NO: 27/1-2-4 UMRANIYE / ISTANBUL / TURKEY 
TEL: +90 216 466 45 05 - +90 216 466 45 10 
 

Service stations’ communication information that related spare parts have been provided 
Authorized Services: 

MAVILI ELEKTRONIK TICARET VE SANAYI A.S. 
SERIFALI MAHALLESI, KUTUP SOKAK NO: 27/1-2-4 UMRANIYE / ISTANBUL / TURKEY 
TEL: +90 216 466 45 05 - +90 216 466 45 10 
 
TEKSIS TEKNIK ELEKTRONIK SIS.TIC. VE SAN. LTD. STI. 
SERIFALI MAHALLESI, KUTUP SOKAK NO: 27/3 UMRANIYE / ISTANBUL / TURKEY 
TEL: +90 216 313 60 60 - +90 216 313 47 49 
 

Expected operation life which has been determined and announced by related ministry 

This device’s expected operation life is 7 years. 

 

2- WARNING 

The equipment contains static-sensitive high quality electronic control equipment. Do not use the panel before 
reading this manual. In case of any fault, only the technicians of the manufacturer or technicians authorized by 
the  manufacturer  should  repair  or  maintain  the  panel.  Use  the  recommended  cable  types  defined  in  this 
manual for cabling of  power supply, detection and sounder circuits. Do not remove any  connections and  do 
not make any connections while mains power supply is connected. Pane

l’s earth connection must be made. 

The cabinet must be connected to a suitable earth point. 

Under no  circumstances should voltage or  current outside of  the limits described in  this  manual be 
used with system units. Otherwise, damage on panel may occur, which is not subject to maintenance

 

under warranty.

 

 

3- MOUNTING THE PANEL

 

MG-400;  is  not  suitable  for  hazardous  areas.  Panels  should  be  located  into  safe  areas.  With  appropriate 
protection material gas  and fire detectors can  be  connected to  the  hazardous areas. To do  that  hazardous 
areas should be checked and the protection material need to be select according to condition of this area. 
While  mounting  the  system  in  a  hazardous  area,  experienced  and  educated  technical  team  should  be 
assigned. Panel should be placed to an easy reachable, clean and dry place without forming any vibration. 
The  LCD  on  the  panel  should be  located in  flat  wall on  eye  level and  pay attention to  mount inside  of  any 
cabinet or near to high heat emitting devices.  Screws or bolts of a minimum of 4mm diameter must be used 
to  mount the  cabinet  in  3  mounting  points.  Please check  out  Annex. B.  Figure 2.  Panel  cable  entries  from 
back and top of the panel are available for easy mounting. 

 

 
 
 
 

Summary of Contents for MG-400

Page 1: ...MG 400 COMMISSIONING OPERATING AND MAINTENANCE MANUAL MODEL MAVIGARD SERIES SUB MODEL CONVENTIONAL SYSTEM COMBINED GAS AND FIRE ALARM CONTROL PANEL ...

Page 2: ...l inputs 5 5 PANEL OUTPUTS 5 5 1 Sounder outputs 5 5 2 24V DC Power Supply Aux Output 5 5 3 Relay Outputs 5 5 3 1 Low alarm relay 5 5 3 2 High Alarm relay 5 5 3 3 Over range Relay 5 5 3 4 Fault relay 6 6 CONTROL BUTTONS 6 7 PANEL INDICATORS 6 8 FUSES 7 9 POWERING THE PANEL 8 9 1 Normal 8 9 2 Alarm 8 9 3 Fault 8 10 PANEL MENUS 8 10 1 Visualization 8 10 2 Access Level 2 11 11 OPERATING WITH REPEATER...

Page 3: ...E SAN LTD STI SERIFALI MAHALLESI KUTUP SOKAK NO 27 3 UMRANIYE ISTANBUL TURKEY TEL 90 216 313 60 60 90 216 313 47 49 Expected operation life which has been determined and announced by related ministry This device s expected operation life is 7 years 2 WARNING The equipment contains static sensitive high quality electronic control equipment Do not use the panel before reading this manual In case of ...

Page 4: ... be connected as an end of line element Channel jumper setting should be set as fire If zener barrier will use the jumper of zener barrier must be adjust accordingly Connections are seen as in Annex A Figure 3 4 3 2 4 20mA input It provides 28V DC supply voltage for both fire and gas detectors It follows 4 20 mA analogue current input via 100 Ohms resistor It is possible to mount 2 or 3 wire gas o...

Page 5: ...ng of sounder outputs Connections should be made according to Annex A Figure 4 Polarised type sounders should be used Otherwise fire alarm control panel displays a fault condition 5 2 24V DC Power Supply Aux Output The panel is equipped with an auxiliary 24V DC 500mA power supply output The output is used to energise external devices such as telephone dialler or gas detector Overloading the output...

Page 6: ...is used to reset the system when there is a gas or fire alarm situation in the system Up and down Buttons Up and Down buttons are used to make a pass through panel functions Enter Button Enter button is used to activate the selected function Exit Button Exit button is used to go back one menu up Microprocessor reset button Microprocessor is locked when it cannot run the system and System fault in ...

Page 7: ... F4 F4 is self resetting and activates on 500 mА current overload or a short circuit on battery inputs Illuminating of the respective LED indicator on SMPS and silk screen label means the batteries are disconnected 24 V DC Auxiliary Power Supply Output Fuse F5 F5 is self resetting and activates on 500 mА current overload On the fuse activation the 24 V DC Fault LED illuminates Channel Fuses F6 F7 ...

Page 8: ...matically turns back to its normal operating status 10 PANEL MENUS In normal mode access level of the panel is 1 In order to see the panel configuration and reach the functions of access level 2 first you need to main menu To do this in normal operating mode press Enter button Under the main menu there are 2 submenus These are Visualization and Access level 2 menus These menus are selected by usin...

Page 9: ...er outputs are active or not SOUNDERS STATUS Sounder 1 Not active Sounder 2 Active Menu Exit Pre 10 1 3 Signal Levels Input of each channel s signal level can be tracked SIGNAL LEVELS Channel 1 00 0 mA Channel 2 05 5 mA Channel 3 10 7 mA Channel 4 25 5 mA Exit Pre Menu 10 1 4 Configuration System operation is seen from the operating configuration of channels sounders and relays It is composed of 4...

Page 10: ... range Relay Latching OK NO Fault Relay Non Latching NO Exit Pre menu 10 1 4 3 Sounder settings It is possible to check how panel s sounder outputs operates latching or non latching SOUNDER SETTINGS Sounder 1 Latching Sounder 2 Non latching Exit Pre menu 10 1 4 4 Channel settings Operating condition of all channels are monitored CHANNEL SETTINGS Channel 1 configuration Channel 2 configuration Chan...

Page 11: ...o the access level 2 person shall use the password 1111 Password display as the following table ACCESS LEVEL 2 Enter Access Level 2 Password Exit Pre Menu In this screen first press to Up button and instead of the star number 1 comes to the end Then by pressing Enter button 4 times makes the user to get in access level 2 The screen of the Access Leve2 pops up if correct password is entered by the ...

Page 12: ...sing Up button changes the text Inhibited is active into Inhibited is inactive and channel is no longer inhibited 10 2 2 Zeroing When zero adjustment wants to apply channels this function is used ZEROING Select the channel for zeroing 1 Channel1 Enter Ok Exit Pre Menu First of all the channel which want to be zeroed is selected To do that Up and Down buttons are used and after determining the spec...

Page 13: ...ration level sub function is selected When you press Enter button on the right side of the Calibration Level text the sign is seen In this position calibration level value is adjusted between 25 and 100 To confirm the value press Enter Button Once you done with these adjustments calibration process can be started For calibration Calibrate sub function is selected and then Enter is pressed In such ...

Page 14: ...lay sign is present After selecting relay press Up button to test it 10 2 4 2 Sounder Test When you enter the sounder test function the current condition of the sounders is monitored SOUNDER TEST Sounder 1 Active Sounder 2 Not Active Enter OK Exit Pre Menu On this screen it is possible to select the sounder output which you may want to test using arrow buttons On the left sign should be next to th...

Page 15: ...y s operating conditions can be selected as latching non latching and latching acceptance operating status These features can be defined as below Latching When the gas level in the medium exceeds the pre determined threshold value for that channel relay gets activated The gas level even then lowers than the threshold value relay does not get back to its previous position In order to make the relay...

Page 16: ... may want to adjust setting using Up and Down arrow buttons On the left sign should be next to that channel By pressing Enter channel is selected In this condition this screen is monitored as CHANNEL SETTINGS Channel 1 configuration Device Type DET 4 20 Source Channel Name Channel 1 Zone Name Mavili Elektronik Measuring Unit LEL Enter OK Exit Pre Menu Using Type function detector type is selected ...

Page 17: ...on that during fire alarm condition when pressed to Reset the determination of interruption time of the energy of the channel which detector connected to that channel is adjusted Low alarm direction Function that estimates the sensitivity of low alarm warning as increasing or decreasing level of the gas in the medium Low alarm opening level Function that determines the threshold of gas level of th...

Page 18: ... kg Body Panel Box 1 2 mm front 1 5 mm DKP Operating Temperature 10ºC 55ºC Relative Humidity 0 95 Mounting Surface mounting Cable Inputs Upper and back inputs 12 2 Electrical Features Gas Channel 4 Operating Voltage 24 V DC Battery 2 x 12 V 7Ah Supply Voltage 220 V AC 50 Hz Sounder Output 2 x 500 mA 24 V DC 24V DC Output 500 mA 24 V DC Extinguishant Output 500 mA 24 V DC Low Alarm Relay 30 V DC 8 ...

Page 19: ...KK 642 014 Rev No 1 01 08 12 Page 19 ANNEX A CONNECTION SCHEME OF THE PANEL ...

Page 20: ...KK 642 014 Rev No 1 01 08 12 Page 20 ANNEX B PANEL DIMENSIONS ...