KK-642.014 Rev.No:1 01.08.12 Page | 16
10.2.5.3 Sounder settings
The sounder outputs of the control panel are adjusted.
***
SOUNDER SETTINGS
* **
> Sounder 1 : Latching
Sounder 2 : Non-latching
------------------------------------------------------------
Enter
– OK
Exit
– Pre Menu
On this screen, it is possible to find the sounder output which you may want to adjust setting, using
“Up(+)”
and
“Down(-)”arrow buttons. (On the left ‘>’ sign should be next to that sounder output.) By pressing “Enter”
sounder output is selected. After selecting sounder output, pressing
“Up(+)” button enables to select the
sounder output as
“latching”, “non-latching” or “latching accept”. These operating features were just
described on section 10.2.5.2.
10.2.5.4 Channel settings
The operating features of the channels of the control panel are adjusted.
*** CHANNEL SETTINGS
***
> Channel 1 configuration
Channel 2 configuration
Channel 3 configuration
Channel 4 configuration
------------------------------------------------------------
Enter
– OK
Exit
– Pre Menu
On this screen, it is possible to find the channel which you may want to adjust setting, using
“Up(+)” and
“Down(-)”arrow buttons. (On the left ‘>’ sign should be next to that channel.) By pressing “Enter” channel is
selected. In this condition, this screen is monitored as;
*** CHANNEL SETTINGS
***
Channel 1 configuration
> Device Type: DET 4-20 Source
Channel Name : Channel 1
Zone Name :Mavili Elektronik
Measuring Unit: % LEL
------------------------------------------------------------
Enter
– OK
Exit
– Pre Menu
· Using “Type” function, detector type is selected. “Fire 4-20 Sink”, “Fire 4-20 Source”, “Detector 4-20
Sink
”, “Detector 4-20 Source”, “Fire Conventional”, “ESU” and “None” features can be selected.
·Using “Name” function, panel name can be written.
·Using “Zone” function, the zone name of the control panel can be given.
·Using “Unit” function, gas measuring unit can be selected as: “%LEL”, “PPB”, “PPM”, “%VOL” and “FIRE”.
After adjusting these settings press
“Down (-)” button to see the upcoming screen.
*** CHANNEL SETTINGS
***
Channel 1 configuration
> Detector Measuring Range: 9999
Zero Suppression: Active
2mA Status: Fault
Warm-Up Delay: 120 sec.
------------------------------------------------------------
Enter
– OK
Exit
– Pre Menu
·By “Measuring Range” function, detector’s gas measuring range is estimated.
·By “Zero suppression” function, it is selected that zeroing process whether active or not.