KK-642.014 Rev.No:1 01.08.12 Page | 15
10.2.5.1 System
Panel: Network Address, communication rate, panel name, serial number and panel language are adjusted
by the help of system menu.
***
SYSTEM
***
> Language: English
Access Level 2 Password: Active
--------------------------------------------------------------
Enter
– Ok
Exit
– Pre Menu
10.2.5.2 Common Relay Settings
In this sub-function, relays operating structure are set as latching, non-latching or latching acceptance of
operating status and N/O or N/C is adjusted.
***
COMMON RELAY SETTINGS
***
> Low Alarm Relay
High Alarm Relay
Over-range Relay
------------------------------------------------------------
Enter
– OK
Exit
– Pre Menu
On this screen, it is possible to select the relay which you may want to adjust setting, using
“Up(+)” and
“Down(-)”arrow buttons. (On the left ‘>’ sign should be next to that relay.) By pressing “Enter” relay is
selected. In this condition, this screen is monitored;
***
COMMON RELAY SETTINGS
***
Low Alarm Relay
> Relay Type: Latching
Normally :Open
------------------------------------------------------------
Enter
– OK
Exit
– Pre Menu
“Relay Type” Sub-function:
By this sub-function, relay
’s operating conditions can be selected as latching
non-latching and latching acceptance operating status. These features can be defined as below:
-
Latching:
W hen the gas level in the medium, exceeds the pre-determined threshold value for that
channel, relay gets activated. The gas level even then lowers than the threshold value; relay does not get
back to its previous position. In order to make the relay turns back to its previous position,
“Alarm Silence”
button should be used.
-
Non-Latching:
When the gas level in the medium, exceeds the pre-determined threshold value for that
channel, The gas level even then lowers than the threshold value; relay gets back to its previous position
without any interfering to the system.
-
Latching Accept:
When the gas level in the medium, exceeds the pre-determined threshold value for that
channel. When system is in Alarm condition, it may possible to turn back the relay back its previous
condition. To do that
“Latching Accept” is selected and then press to “Alarm Silence” button. Additionally,
the operating condition of the relay whether normally Open or normally closed is set from tjis sub-function.