Temperature Controller
METICOM TM10 Module
9. Default of parameters
Parameter
Default
Parameter
Default
Parameter
Default
SV
200
Sup
450
Snb
1
ALH
30
nSL
0
HEA
4
ALL
-30
rES
0
inA
18
LCK
0
Sn
0
Std
5
A-n
0
C-F
0
SHt
0
P
55
Sot
2
boS
0
i
120
t
1
EHo
0
d
30
Pub
0
VoL
16
Pb
0
Ain
15
SoL
0
Ads
0
Adr
0
SVP
0
10. Alarm messages
Alarm Code
Related
Parameter
Cut-off
Output
Troubles
Solution
S E r
Snb
Yes
Misconnection of
thermocouple & heater
Check the wiring, make Snb=0 if the
connection is right.
E r H
——
Yes
Thermocouple open
Check the sensor, or switch to manual
control mode.
E r L
——
Yes
Thermocouple inverse
H E A
HEA
No
Heater fault
Check the heater.
t r S
——
Yes
Triac error
Replace the triac.
A L H
ALH
Yes
High deviation alarm
Check the controller & the sensor.
A L L
ALL
No
Low deviation alarm
Check the system thermal insulation,
or switch to manual control mode.
Current in SV
flash
Ain
No
Over load
Check the load.
S H t
SHt
Yes
Short load
Check the load.
H E r
EHo
Yes
Thermocouple is out of its
position
Check the thermocouple.
H o t
AdS
No
Ambient temperature is too
high
Check the fans of mainframe.
H HH
VoL
Yes
Over voltage
Check the power supply.
F u S
——
Yes
Fuse Blowout
Check the load and replace the fuse.