0: Auto mode when power on; initial power output is same as auto mode when shift to manual mode.
1: Auto mode when power on; initial power output is same as parameter A-n when shift to manual mode.
2: Manual mode when power on; initial power output is 0%.
3: Manual mode when power on; initial power output is same as parameter A-n.
4: If auto mode when power off, same as nSL=1 when power on;
If manual mode when power off, same as nSL=3 when power on.
9) rES: initialize controller.
0: Off.
1: All parameters are reset to factory setting after power-on.
8-3. Engineer parameters 2
1) Sn: sensor type.
0: J type thermocouple; 1: K type thermocouple.
Notes: It can be changed quickly by press DISP key >9s.
2) C-F: temperature unit.
0:
℃
; 1:
℉
.
3) Sot: soft start (heater dehumidify) function.
0: Off; 1~10: On, soft start time= Sot×80s
Notes
:
The rest of soft start time reduced to one-third if the process temperature reached 100
℃
(212
℉
).
4) t: output control type.
0: phase control output;
1~10: zero-switching control output, proportional cycle = t×1s
phase control
zero-switching control
8-4. Engineer parameters 3
1) Snb: diagnostic function for misconnection of heater and thermocouple.
0: Off.
1: Checking the heater after power on, if the controller judge it as thermocouple, alarm and cut off output to protect
it.
Notes
:
It may cause a false alarm if the heater power is large. When identified as false alarm, please set Snb=0.
2: Reserved
2) HEA: diagnostic function for heater
(
It is used as HEA=1 in manual mode, no matter the setting is
)
.
0: Off.
1~10: Checking the load current when output is HEA×10%, if the controller judge the heater fault, it will alarm.
Recommended setting is HEA=3~5.