7  COMMISSIONING, DECOMMISSIONING 

 

7.1 

Commissioning 

 

CAUTION! 

Check the polarity of all wiring before 
commissioning: plus connected to plus (red 
cables), minus connected to minus (black 
cables).  
The DIP-switches must be adjusted prior to 
commissioning; see chapter 6. 

 
Follow the steps described below to switch on the Mass Sine 
Ultra. 

Tighten all strain reliefs; 

Check all wiring and connections; 

Close the front cover plate of the connection 
compartment; 

Place the DC-fuse(s) of the DC-distribution to connect 
the batteries to the Mass Sine Ultra. 

 

WARNING 

When placing this fuse, a spark can occur, 
caused by the capacitors used in the Mass Sine 
Ultra. This is particularly dangerous in places with 
insufficient ventilation, due to the gassing of the 
batteries an explosion can occur and avoid 
having flammable materials close by. 
 

 
Now the Mass Sine Ultra is ready for operation. 
 

7.2 

Decommissioning 

If it is necessary to put the Mass Sine Ultra out of operation, 
follow the instructions in order of succession as described 
below: 

Move the Main-switch of the Mass Sine Ultra to “Off”; 

Remove DC-distribution fuses and/or disconnect the 
batteries; 

Open the connection compartment of the Mass Sine 
Ultra; 

Check with a suitable voltage meter whether the input 
and the output of the Mass Sine Ultra are voltage free; 

Disconnect all the wiring. 

 
Now the Mass Sine Ultra can be demounted in a safe way. 
 

7.3 

Trouble shooting 

If a failure occurs, the origin of the failure is displayed by 
means of the LED’s at the front of the Mass Sine, see figure 
7-3. 
 

 

Figure 7-3: Error LED’s 

 
The table  at section 7.3.1 shows the meaning of the error 
indications and their solutions, together with other directions. 
If you cannot solve a problem using this table, contact your 
local Mastervolt Service Centre. See www.mastervolt.com. 
Make sure you have the following information present if you 
have to contact your local Mastervolt Service Centre to solve 
a problem: 
 

  Article and serial number (see section 1.7). 

  Software version (see summary page in MasterAdjust or 

the Configuration page in MasterView control panel). 

 

 

 

Summary of Contents for Mass Sine Ultra 24/4000

Page 1: ...w mastervolt com products inverters sine wave DE Siehe www mastervolt com products inverters sine wave FR Voir www mastervolt com products inverters sine wave ES Vea www mastervolt com products invert...

Page 2: ...W MASS SINE ULTRA Figure 0 1 Overview of the Mass Sine Ultra 1 Display with front switch 6 Fan 3x 2 Battery negative 7 Ground stud 3 Battery positive 8 Sync connector 2x 4 AC output 9 MasterBus connec...

Page 3: ...9 3 6 Daily use MasterBus monitoring 10 4 INSTALLATION 11 4 1 Unpacking 11 4 2 Environment 11 4 3 Wiring 11 4 4 Things you need 12 4 5 Removal of the front lid 12 4 6 Mounting the cabinet to a surface...

Page 4: ...guration via dip switches 20 6 2 MasterBus configuration 21 7 COMMISSIONING DECOMMISSIONING 23 7 1 Commissioning 23 7 2 Decommissioning 23 7 3 Trouble shooting 23 8 TECHNICAL DATA 25 8 1 Specification...

Page 5: ...t warranty of the Mass Sine Ultra during two years after purchase on the condition that all instructions and warnings given in this manual are taken into account during installation and operation Amon...

Page 6: ...s not hold itself liable for any damage resulting from the above 2 3 Organizational measures The user must always have access to the user s manual be familiar with the contents of this manual This app...

Page 7: ...ra parts and or to commit to undertake such testing as a part of the manufacturing process In addition the manufacturer must agree to indemnify and not hold Mastervolt responsible for any claims arisi...

Page 8: ...rs at the front side of the housing If the Mass Sine Ultra is activated and as long as none of the red indicators are illuminated no failure is detected and the unit is operating normally 3 3 1 AC Out...

Page 9: ...ver and under voltage See specifications The Mass Sine Ultra switches off if the DC input voltage is out of range 3 4 4 Dynamic DC input window Figure 3 4 Dynamic DC input window The Mass Sine Ultra w...

Page 10: ...m Index General Device state The state of your Mass Sine Ultra Standby Inverting Alarm Overload Low battery 1 1 16 Inverter Option to switch Off the inverter to prevent depleting of your batteries On...

Page 11: ...e mounted in such a way that obstruction of the airflow through the ventilation openings will be prevented No objects must be located within a distance of 10 cm 4 inch around the Mass Sine Ultra Keep...

Page 12: ...rth terminal PE GND to the hull or the chassis with a minimum 10 mm CAUTION For safe installation it is necessary to connect the neutral conductor N of the AC output to the earth PE GND insert a Resid...

Page 13: ...owermost bolts 5 Fasten all bolts securely 6 Fix cabinet to the surface with remaining two bolts 4 7 Wiring instructions WARNING Have installation work done by a licensed electrician only Before conne...

Page 14: ...8 Installation overview Figure 4 8 Installation overview for one Mass Sine Ultra CAUTION Ensure correct polarities cross sections and fuses for all wiring An RCD according to local regulations must be...

Page 15: ...ly flexible for extended system configuration Mastervolt also offers several interfaces like the Modbus interface making even non MasterBus devices suitable to operate in the MasterBus network For cen...

Page 16: ...ly unlimited three phase power can be made available 5 2 General installation guidelines When using Mass Sine Ultra s in a multiple configuration the following requirements are Only identical Mass Sin...

Page 17: ...the communication module As you see the MasterBus network has a terminator on both ends Figure 5 4 Three Mass Sine Ultra s connected in 3 phase 5 5 Multi Mass Sine Ultra communication Within the Maste...

Page 18: ...proposed If not enough Mass Sine Ultra s are available for the cluster the topology needs approval Needs approval Needs approval approved Phase L1 L2 L3 shows in 3 ph cluster only Phase groups with sc...

Page 19: ...or parallel settings of two Mass Sine Ultra s See table below and section 6 1 MasterBus configuration is necessary for more Mass Sine Ultra s in a parallel connection By operating the DIP switches you...

Page 20: ...out in the menu When a DIP switch is set to 0 the corresponding MasterBus setting becomes default too regardless the previous setting 6 1 Configuration via dip switches The DIP switches are located i...

Page 21: ...oltage AC voltage 230 V 180 260 V Frequency AC frequency 50 Hz 50 Hz 60 Hz Energy save mode Option to enable Energy save mode Not checked Not checked checked Scanning below The Mass Sine Ultra starts...

Page 22: ...ot inside the unit Check all connections System error Internal Mass Sine Ultra error Contact your Mastervolt supplier 6 2 2 List of event sources This is the Mass Sine Ultra list of event sources Thes...

Page 23: ...ne Ultra out of operation follow the instructions in order of succession as described below 1 Move the Main switch of the Mass Sine Ultra to Off 2 Remove DC distribution fuses and or disconnect the ba...

Page 24: ...erting Errors Mass Sine Ultra shuts down 1 and 3 red 2 yellow Over temperature Mass Sine Ultra too hot Restart when alarm is over Check ventilation Reduce load 1 and 3 red System error Sync error Conf...

Page 25: ...al DC current at full load 200 A Recommended batteries 200 600 Ah No load DC drain Off mode hard switched 0 W Inverter off mode remote 4 W Normal operation mode 16 W Parallelling 3 phase Parallel stac...

Page 26: ...EN Mass Sine Ultra 26 8 2 Dimensions Figure 8 1 Dimensions in mm...

Page 27: ...ft 77042500 MasterBus connection cable UTP patch cable 25 m 82 ft 77045000 100 m 330 ft MasterBus cable UTP cable 77040010 MasterBus RJ45 conn 8 pole 25 pcs 77040015 Cover for RJ45 conn set a 25 st 77...

Reviews: