EN / Mass Sine Ultra
10
3.6
Daily use, MasterBus monitoring
The MasterBus Monitoring page offers the option to do your daily settings and it shows your settings from the Configuration page.
The table below shows the Mass Sine Ultra monitoring values. The values with a default value are adjustable.
Value
Meaning
Default
Range
Group-item
Index
General
Device state
The state of your Mass Sine Ultra
Standby; Inverting; Alarm;
Overload; Low battery
1-1
16
Inverter
Option to switch Off the inverter to
prevent depleting of your batteries
On
On, Off
1-3
20
Mode
User mode
Disabled; On; Error; Shutdown
1-4
60
Battery (DC)
Main battery
Battery voltage
0..32 V
2-2
6
Main battery
Approximate battery current (minus
is discharging)
-500..0 A
2-3
7
AC output
AC output
AC output voltage
0..300 V
5-1
10
AC output
AC output current
0..70 A
5-2
11
AC output
AC output power
0..20000 W
5-3
98