Mastervolt Mass Sine Ultra 24/4000 User And Installation Manual Download Page 16

EN / Mass Sine Ultra 

16 

 

 

 

5  INSTALLATION OF MULTIPLE CLUSTERED MASS SINE ULTRA’S 

 
This installation instruction serves as a guideline for the safe 
and effective installation of the Mass Sine Ultra in a multiple 
configuration, i.e.  

  a parallel configuration, or 

  a split phase configuration, or 

  a three phase configuration, or 

  a combination of a split phase or three phase in a parallel 

configuration. 

 

5.1 

Purpose of a multiple configuration  

There are several reasons for a multiple configuration of the 
Mass Sine Ultra:  

  If more output power is needed than one Mass Sine Ultra 

can supply, two up to ten Mass Sine Ultra’s can be 
connected in parallel; 

  If redundancy is required, Mass Sine Ultra’s can be 

connected in parallel to maintain reliable power supply if 
one of the Mass Sine Ultra’s fails in operation; 

  Three Mass Sine Ultra’s can be connected in a 3-phase 

configuration to supply three phase AC power. By 
connecting more Mass Sine Ultra’s in parallel as well, 
virtually unlimited three phase power can be made 
available.  

5.2 

General installation guidelines 

When using Mass Sine Ultra’s in a multiple configuration, the 
following requirements are:  

  Only identical Mass Sine Ultra’s with the same article 

numbers may be used in a multiple configuration;  

  Maximum number of Mass Sine Ultra’s in parallel: 10; 

  Maximum number of Mass Sine Ultra’s in a three phase 

-parallel configuration: 3 x 3;  

  Installation and commissioning of multiple Mass Sine 

Ultra’s requires configuration of MasterBus settings and 
programming of MasterBus events by means of  a 
MasterBus control panel or a PC (in combination with a 
MasterBus USB-interface) with MasterAdjust software 
installed. The installer must be familiar with MasterBus 
configuration tools and the programming of such events;  

  Allow sufficient ventilation to prevent build-up of hot air. 

When installing multiple Mass Sine Ultra’s either side by 
side or vertically above each other, at least 10 cm / 4 inch 
free space must be kept  in between  the units. If 
necessary, adequate measures must be taken to avoid 
one Mass Sine Ultra heating up the other. 

 

 

 

 

                                              
 

Figure 5-3: Two Mass Sine Ultra’s connected in parallel 

 

Summary of Contents for Mass Sine Ultra 24/4000

Page 1: ...w mastervolt com products inverters sine wave DE Siehe www mastervolt com products inverters sine wave FR Voir www mastervolt com products inverters sine wave ES Vea www mastervolt com products invert...

Page 2: ...W MASS SINE ULTRA Figure 0 1 Overview of the Mass Sine Ultra 1 Display with front switch 6 Fan 3x 2 Battery negative 7 Ground stud 3 Battery positive 8 Sync connector 2x 4 AC output 9 MasterBus connec...

Page 3: ...9 3 6 Daily use MasterBus monitoring 10 4 INSTALLATION 11 4 1 Unpacking 11 4 2 Environment 11 4 3 Wiring 11 4 4 Things you need 12 4 5 Removal of the front lid 12 4 6 Mounting the cabinet to a surface...

Page 4: ...guration via dip switches 20 6 2 MasterBus configuration 21 7 COMMISSIONING DECOMMISSIONING 23 7 1 Commissioning 23 7 2 Decommissioning 23 7 3 Trouble shooting 23 8 TECHNICAL DATA 25 8 1 Specification...

Page 5: ...t warranty of the Mass Sine Ultra during two years after purchase on the condition that all instructions and warnings given in this manual are taken into account during installation and operation Amon...

Page 6: ...s not hold itself liable for any damage resulting from the above 2 3 Organizational measures The user must always have access to the user s manual be familiar with the contents of this manual This app...

Page 7: ...ra parts and or to commit to undertake such testing as a part of the manufacturing process In addition the manufacturer must agree to indemnify and not hold Mastervolt responsible for any claims arisi...

Page 8: ...rs at the front side of the housing If the Mass Sine Ultra is activated and as long as none of the red indicators are illuminated no failure is detected and the unit is operating normally 3 3 1 AC Out...

Page 9: ...ver and under voltage See specifications The Mass Sine Ultra switches off if the DC input voltage is out of range 3 4 4 Dynamic DC input window Figure 3 4 Dynamic DC input window The Mass Sine Ultra w...

Page 10: ...m Index General Device state The state of your Mass Sine Ultra Standby Inverting Alarm Overload Low battery 1 1 16 Inverter Option to switch Off the inverter to prevent depleting of your batteries On...

Page 11: ...e mounted in such a way that obstruction of the airflow through the ventilation openings will be prevented No objects must be located within a distance of 10 cm 4 inch around the Mass Sine Ultra Keep...

Page 12: ...rth terminal PE GND to the hull or the chassis with a minimum 10 mm CAUTION For safe installation it is necessary to connect the neutral conductor N of the AC output to the earth PE GND insert a Resid...

Page 13: ...owermost bolts 5 Fasten all bolts securely 6 Fix cabinet to the surface with remaining two bolts 4 7 Wiring instructions WARNING Have installation work done by a licensed electrician only Before conne...

Page 14: ...8 Installation overview Figure 4 8 Installation overview for one Mass Sine Ultra CAUTION Ensure correct polarities cross sections and fuses for all wiring An RCD according to local regulations must be...

Page 15: ...ly flexible for extended system configuration Mastervolt also offers several interfaces like the Modbus interface making even non MasterBus devices suitable to operate in the MasterBus network For cen...

Page 16: ...ly unlimited three phase power can be made available 5 2 General installation guidelines When using Mass Sine Ultra s in a multiple configuration the following requirements are Only identical Mass Sin...

Page 17: ...the communication module As you see the MasterBus network has a terminator on both ends Figure 5 4 Three Mass Sine Ultra s connected in 3 phase 5 5 Multi Mass Sine Ultra communication Within the Maste...

Page 18: ...proposed If not enough Mass Sine Ultra s are available for the cluster the topology needs approval Needs approval Needs approval approved Phase L1 L2 L3 shows in 3 ph cluster only Phase groups with sc...

Page 19: ...or parallel settings of two Mass Sine Ultra s See table below and section 6 1 MasterBus configuration is necessary for more Mass Sine Ultra s in a parallel connection By operating the DIP switches you...

Page 20: ...out in the menu When a DIP switch is set to 0 the corresponding MasterBus setting becomes default too regardless the previous setting 6 1 Configuration via dip switches The DIP switches are located i...

Page 21: ...oltage AC voltage 230 V 180 260 V Frequency AC frequency 50 Hz 50 Hz 60 Hz Energy save mode Option to enable Energy save mode Not checked Not checked checked Scanning below The Mass Sine Ultra starts...

Page 22: ...ot inside the unit Check all connections System error Internal Mass Sine Ultra error Contact your Mastervolt supplier 6 2 2 List of event sources This is the Mass Sine Ultra list of event sources Thes...

Page 23: ...ne Ultra out of operation follow the instructions in order of succession as described below 1 Move the Main switch of the Mass Sine Ultra to Off 2 Remove DC distribution fuses and or disconnect the ba...

Page 24: ...erting Errors Mass Sine Ultra shuts down 1 and 3 red 2 yellow Over temperature Mass Sine Ultra too hot Restart when alarm is over Check ventilation Reduce load 1 and 3 red System error Sync error Conf...

Page 25: ...al DC current at full load 200 A Recommended batteries 200 600 Ah No load DC drain Off mode hard switched 0 W Inverter off mode remote 4 W Normal operation mode 16 W Parallelling 3 phase Parallel stac...

Page 26: ...EN Mass Sine Ultra 26 8 2 Dimensions Figure 8 1 Dimensions in mm...

Page 27: ...ft 77042500 MasterBus connection cable UTP patch cable 25 m 82 ft 77045000 100 m 330 ft MasterBus cable UTP cable 77040010 MasterBus RJ45 conn 8 pole 25 pcs 77040015 Cover for RJ45 conn set a 25 st 77...

Reviews: