1.2 Features
1.Testing voltages with broad range can be generated (from 250 V to 5 KV).
2.Testing voltage can be preset as 250 V, 500 V, 1 KV, 2.5 KV, or 5 KV, or as a voltage increasing
or decreasing in steps of 25 V or 100 V.
Broad Range of Testing
Voltage
Insulation Diagnosis
1.PI and DAR can be automatically calculated and displayed;
2.Step-voltage measurements and temperature compensation is carried out.
Large Storage Memory
1.Up to 100 manually tested data and 10 groups of log-test data can be saved.
2.Test data can be read on LCD, or uploaded to PC
Clear Display
1.Large-screen display. Test result is displayed with indication through a graduation bar.
2.LCD screen is backlit, which is suitable for viewing when it is dark
PC Communication
1.The meter is equipped with a USB interface, through which the saved test data can be
uploaded to a PC for further table/figure making and report generating with convenience.
Robust and Durable
1.With a compact structure, the tester is robust, durable and portable.
1.TWith a selection switch, the tester can be powered by an alkaline battery.
2.This tester can be continuously operated for a longer period of time than similar meters if a
LR14 alkaline battery is used.
Powered by Batteries
1.3 General Description of Test Methods
1.Use: for checking the insulation of high-voltage electrical equipment
2.Situation: high-voltage receiving station and transformer substation
3.Object: electric motor, transformer, and cable, etc.
1.3.1 Test conditions
When testing the insulation resistance, please make sure that the power to the test equipment is turned off.
1.3.2 Test procedures
1.3.2.1 Preparations for the test
Before starting the measurement, please first check:
Mode of power supply
Status of the battery selection switch
Settings of date and time
Connection of the test probes.
1.3.2.2 Start testing
1.3.2.3 Insulation resistance test
1)Make sure that power supply
to the test equipment is turned
off.
2) Push and hold POWER key
for 2 seconds to turn on meter.
3) Connect test probes to +/-
terminals and the test
equipment as shown in Fig. 1-1
4) Push
button and set
test voltage, as shown in Fig.
1-2.
voltage
5) Push and hold ‘ TEST’ button
for 1 sec to generate test
and start measurement.
6) Read data
shown in Fig.
1-3
as
7) Push ‘TEST’ button to stop
the test
Test is ended when voltage is
lower than 10 V.