Page | 38
MINT – IO
REF NO: m25A/om/101
Issue No: 11
4.2.6 Modbus Address for configuration:
Parameter
Address
Description
Digital Output
00001
– 00016
Channel 1
– 16 DO Coils
1 = Set to ON
0 = Reset to OFF
Line State
10001
– 10016
16 channel line State
1 = Connected 0 = Disconnected
Channel Type
40001
– 40016
Channels 1
– 16 types:
0 = Normal ,1 = Single Pulse
2 = Continuous pulse
DO predefine value
40017
Channel 1
– 16
BIT 1 to BIT 16 , 1
– ON 0 – OFF
DO
– Pulse High
level Time
40021
– 40036
Channel 1
– 16 high level time in
ms. 1-500 (x 10msec)
DO
– Pulse Low level
Time
40037
– 40052
Channel 1
– 16 low level time in ms.
1-500 (x 10msec)
DO Pulse Predefined
Value
40053 to 40068
Channels 1 to 16 pulse Predefined
value.
In “Continuous Pulse” mode, after
the pulse value reached this
predefined value; the output will be
forced to OFF.
If this value is zero, the pulse
Output will be unlimited.
DO Pulse Predefined
Value Reset
40020
Channel 1
– 16, BIT 1 to BIT 16
1
– Reset
Channel Type
30001
– 30016
Read Only
DO predefine value
30017
Read Only
DO
– Pulse High
level Time
30021
– 30036
Read Only
DO
– Pulse Low level
Time
30037
– 30052
Read Only
DO Pulse Value
30053 to 30068
Read Only
DO Pulses
30069 to 30084
Channels 1 to 16
– number of
output pulses as per the Predefined
value defined in DO pulse
Predefined value
Line State - Word
30085
16 channel line State
– 16 BIT
1 = Connected 0 = Disconnected